

Excertos do catálogo

Fire Damper for Circular Ducts • Type-approved and compliant with the EN 1366-2 and EN 13501-3 standards. • Design for installation in separating concrete and masonry walls and ceilings and lightweight plasterboard walls of fire compartments with fire resistance class EIS 30 to EIS 120. • Readiness for installation with all wall options as delivered - no additional frames needed. • Manufacture in accordance with the ISO 9001 quality system. • VTT, the Technical Research Centre of Finland, is responsible for external quality control. • Installation in circular ducts with diameter 160 to 500 mm. • Double sealing, ensuring that the blades are tight when the fire damper is closed before and during a fire. • Fire damper casing complying with the tightness requirements for Class C, EN 1751. • Fire damper tightness meeting smoke damper requirement S of standard EN 1366-2. • Suitability for use in ducts with a maximum pressure of 3100 Pa. • Damper closing tests performed at 15 m/s duct velocity. Product models and Accessories • Models equipped with either manual or electric actuators. Halton CARE FOR INDOOR AIR FDC - Fire Damper for Circular Ducts 1
Abrir o catálogo na página 1
When the damper is installed on concrete and masonry walls or ceilings, the size of the installation hole is D+50 mm. When the damper is installed on lightweight walls, consult the section 'Documents / Installation Instructions' for the size of the installation holes. Material and finishing The FDC fire damper casing, installation flange, and installation frame are made of galvanised steel. The closing blade is made of calcium silicate and equipped with a flexible silicone seal as well as a graphite mass seal. Product options and Accessories Actuators Manual actuator, MA (spring...
Abrir o catálogo na página 2
Function The FDC is a circular fire damper of fire resistance class EIS 30 to EIS 120, which prevents fire and smoke from spreading in ventilation ducts. The fire damper is equipped with either a motorised actuator or manual actuation arrangement. Both actuators have a visual position indicator. If the power in the motorised actuator system is switched off, the blade closes automatically. Europe and Russia models: In both actuator options, a fuse reacts to a rise in temperature, causing a spring-return blade to close. The motorised fire damper is delivered complete with a spring-return...
Abrir o catálogo na página 3
Installation on concrete and masonry walls When the fire damper is installed on concrete and masonry walls and ceilings between fire compartments, the blade shaft is always horizontal. An opening is always left in the separating element for the fire damper, and the product subsequently is grouted into this. To make installation easier, all products come with an installation flange, which is used to fasten the fire damper to the concrete surface with screws before grouting. During installation, the fire damper and actuator must be protected with, e.g., a plastic cover. The correct operation...
Abrir o catálogo na página 4
A fire damper of class EIS 30 to EIS 120 shall have a double sealing solution that ensures fire-gas resistance at all temperatures when the fire damper is closed. In motorised models, the fuse shall be activated at 72 °C (E and R models). In the manually operated system, the fuse activation temperature corresponds to the specifications (50, 65, 72, 100 °C). The fuse shall be located inside the damper, and it shall be possible to replace it from the outside. The fire damper shall have means for external opening / triggering of the release and closing. The fire damper shall include a position...
Abrir o catálogo na página 5Todos os catálogos e folhetos técnicos da HALTON
-
Halton Vita Cell Room (VCR)
2 Páginas
-
Halton Rex Expander (RXP)
16 Páginas
-
Halton CBD
8 Páginas
-
FS Halton AHUs
28 Páginas
-
Halton KCD
3 Páginas
-
KVE-CM
7 Páginas
-
KMC - MobiChef
5 Páginas
-
Halton MobiChef
12 Páginas
-
R6B
9 Páginas
-
Halton – Residential Ventilation System
20 Páginas
-
Halton Vario
20 Páginas
-
Halton FDS
7 Páginas
-
Halton FDR
6 Páginas
-
Halton FDI
6 Páginas
-
Halton FDE
8 Páginas
-
ALE/ALU
8 Páginas
-
AHF
5 Páginas
-
JTH
4 Páginas
-
Capture Jet solutions general brochure
12 Páginas
-
FDC
5 Páginas
-
AFB
7 Páginas
-
TCG 2013
4 Páginas
-
FCU 2013
6 Páginas
-
KVS-C Kiosk Ventilation Systems
3 Páginas
-
HFB - Airflow Management Damper
17 Páginas
-
VHB - Active VAV Diffuser
7 Páginas
-
TLD - Wall Diffuser Unit
9 Páginas
-
FDB2 -
4 Páginas
-
CPA - Passive Chilled Beam
13 Páginas
-
CCC - Adaptable Active Chilled Beam
13 Páginas
-
Product catalogue of air filtration
71 Páginas
Catálogos arquivados
-
FCU Vertical Fancoil Unit
4 Páginas
-
Halton ? AdaptableClimate
12 Páginas
-
Halton ? Ventilation fire safety
12 Páginas
-
Halton ? Chilled Beams
12 Páginas
-
HALTON-POLLUSTOP
4 Páginas
-
UNIPOINT
4 Páginas
-
HALTON-CYCLOCELL CASSETTE CEILING
2 Páginas
-
HALTON-KVD
6 Páginas
-
HALTON-KCE
10 Páginas
-
HALTON-KSK
6 Páginas
-
KCJ
12 Páginas
-
Halton - universal grilles
46 Páginas
-
Halton - displacement design guide
13 Páginas
-
Halton - beam design guide
31 Páginas
-
Halton - air diffusion design guide
6 Páginas