ALLinBOX 88 - 1

ALLinBOX 88 Multifunction device with KNX power supply, KNX-IP Interface, 8 outputs, 8 inputs and logical module ZPR88 TECHNICAL DOCUMENTATION 320mA KNX power supply with 29VDC auxiliary output KNX system voltage supply and monitorization Short-circuit and overvoltage protection Reset button and overload status LED KNXnet/IP tunneling protocol (up to 5 connections) Maximum APDU length of 254bytes Ethernet 10/100 BaseT IP with RJ45 socket 2 different configurable blocks: shutter channels (up to 4), individual outputs (up to 8) and 2/4-pipe fan coil controls (up to 1) Outputs suitable for capacitive loads, maximum 140µF Manual output operation through remote control Climate control for up to 4 rooms Output timing Total data saving on KNX bus failure DIN rail mounting (EN 50022), with fixing clamp Possibility of connecting different phases in adjacent channels Conformity with the CE directives (CE-mark on the right side) 3. Power supply status LED 6. IP factory reset button 11. Auxiliary power output 1. Main power supply 19. Remote control (not included, ref. 9900024) PROGRAMMING/TEST BUTTON: short press to set programming mode. If this button is held while providing main power supply to the device, it enters the safe mode. If this button is held for more than 3 seconds, the device enters the test mode. PROGRAMMING/TEST LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The manual mode is indicated by the green color. During the start-up (reset or after providing main power supply) and if the device is not in safe mode, it starts a blue blinking sequence. POWER SUPPLY STATUS LED: it indicates the status of the power supply (green color: the device is working properly; off LED: power supply failure; green blinking: short-circuit on KNX bus and/or auxiliary power output). OVERLOAD STATUS LED: it indicates an overload on the KNX line or on the auxiliary power output (red blinking: cut-off due to overload/short circuit on the KNX bus and/or the auxiliary power output*; red color: overload on bus and/or auxiliary power output line *). *Reduce the load on the bus and/or the auxiliary power output lines until its total consumption does not exceed the maximum current specified. KNX BUS LED: it indicates that the device is powering up the KNX bus (green color). ETHERNET LED: it indicates that the device is connected to Ethernet and has an IP address assigned (green color). RESET INDICATOR LED: it indicates that a reset of the KNX system has been performed by using the corresponding reset button (red blinking). To reset the bus power supply, the Reset button should be pressed (it is recommended to hold it for at least 5 seconds to verify the reset of all the devices in the line). The reset LED will blink slightly in red while the Reset button is pressed. IP FACTORY RESET INDICATOR LED: it indicates that the device has just performed an IP factory reset (red color). To reset the KNX IP Interface, the IP Factory reset button must be pressed for at least 3 seconds. MANUAL CONTROL: In order to perform manual control of the device, an IR remote control is necessary (Ref. 9900024) not included with the ALLinBOX 88. When the device is in Test On mode, the manual control can be done by pressing the corresponding buttons on the IR remote control (please, be sure that the remote IR emitter is pointing to the IR input of ALLinBOX 88). © Zennio Avance y Tecnología S.L.

Open the catalog to page 1
ALLinBOX 88 - 2

GENERAL SPECIFICATIONS CONCEPT Type of device External power supply DESCRIPTION Electric operation control device 110-240VAC 50/60Hz 250mA@110VAC / 125mA@230VAC 29VDC SELV (with KNX coil) 320mA Typical TP1 bus connector for 0.80mm Ø rigid cable 29VDC SELV IAD + IBUS ≤ 320mA -5°C .. +45°C -20°C .. +55°C 5 .. 95% 5 .. 95% Class B II / III (4000V) Continuous operation Type 1 Long IP20 / 2 (clean environment) Independent device to be mounted inside electrical panels with DIN rail (EN 50022) Not required 110ms 500mA Data saving according to parameterization Data recovery according to...

Open the catalog to page 2
ALLinBOX 88 - 3

⚠ In order to ensure the expected status of the relays, please check that the device is connected to the main power supply before energizing the power circuit. ABRIR OPEN CERRAR CLOSE ABRIR OPEN The fan and the valves to be connected must have the same nominal supply voltage. For a 4-pipe fan coil, the cooling valve should always be connected on the left side and the heating valve on the right side. Before the startup of the device, it must be assured that the valve is completely closed. CERRAR CLOSE Outputs that are not being used for valve control can be used as individual outputs or...

Open the catalog to page 3
ALLinBOX 88 - 4

Attaching ALLinBOX 88 to DIN rail: This device must be exclusively installed in a 35mm DIN rail inside a distribution box or an electrical panel. Ensure suitable ventilation to prevent the temperature from exceeding the permissible range. Main power must be connected to L, N and ground terminals. The coil integrated bus output must be connected through a standard KNX connector. The additional output connection must be connected according to the polarity indicated on the housing. Removing ALLinBOX 88 from DIN rail: Figure 2: Mounting ALLinBOX 88 on DIN rail SAFETY INSTRUCTIONS AND ADDITIONAL...

Open the catalog to page 4