ALLinBOX 1612 v2 Multifunction device with KNX power supply, KNX-IP Interface, 16 outputs, 12 inputs and logical module ZPR1612V2 TECHNICAL DOCUMENTATION 640mA KNX power supply with 29VDC auxiliary output Power generation for the KNX system (with LED indicator) Short-circuit and overvoltage protection Reset button and overload status LED KNXnet/IP tunneling protocol (up to 5 connections) Maximum APDU length of 254bytes Ethernet 10/100 BaseT IP with RJ45 socket 4 different configurable blocks: shutter channels (up to 8), individual outputs (up to 16) and 2/4-pipe fan coil controls (up to 2) Outputs suitable for capacitive loads, maximum 140µF Manual output operation through remote control Climate control for up to 4 rooms Output timing Total data saving on KNX bus failure DIN rail mounting (EN 50022), with fixing clamp Possibility of connecting different phases in adjacent channels Conformity with the CE directives (CE-mark on the right side) 3. Power supply status LED 6. IP factory reset button 11. Auxiliary power output 1. Main power supply 19. Remote control (not included, ref. 9900024) PROGRAMMING/TEST BUTTON: short press to set programming mode. If this button is held while providing main power supply to the device, it enters the safe mode. If this button is held for more than 3 seconds, the device enters the test mode. PROGRAMMING/TEST LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The manual mode is indicated by the green color. During the start-up (reset or after providing main power supply) and if the device is not in safe mode, it starts a blue blinking sequence. POWER SUPPLY STATUS LED: it indicates the status of the power supply (green color: the device is working properly; off LED: power supply failure; green blinking: short-circuit on KNX bus and/or auxiliary power output). OVERLOAD STATUS LED: it indicates an overload on the KNX line or on the auxiliary power output (red blinking: cut-off due to overload/short circuit on the KNX bus and/or the auxiliary power output*; red color: overload on bus and/or auxiliary power output line *). *Reduce the load on the bus and/or the auxiliary power output lines until its total consumption does not exceed the maximum current specified. KNX BUS LED: it indicates that the device is powering up the KNX bus (green color). ETHERNET LED: it indicates that the device is connected to Ethernet and has an IP address assigned (green color). RESET INDICATOR LED: it indicates that a reset of the KNX system has been performed by using the corresponding reset button (red blinking). To reset the bus power supply, the Reset button should be pressed (it is recommended to hold it for at least 5 seconds to verify the reset of all the devices in the line). The reset LED will blink slightly in red while the Reset button is pressed. IP FACTORY RESET INDICATOR LED: it indicates that the device has just performed an IP factory reset (red color). To reset the KNX IP Interface, the IP Factory reset button must be pressed for at least 3 seconds. MANUAL CONTROL: In order to perform manual control of the device, an IR remote control is necessary (Ref. 9900024) not included with the ALLinBOX 1612 v2. When the device is in Test On mode, the manual control can be done by pressing the corresponding buttons on the IR remote control (please, be sure that the remote IR emitter is pointing to the IR input of ALLinBOX 1612 v2). © Zennio Avance y Tecnología S.L.
Open the catalog to page 1GENERAL SPECIFICATIONS CONCEPT Type of device External power supply Voltage Maximum consumption Voltage (typical) KNX supply Maximum rated current (IBUS) Connection type Voltage (typical) Additional output Maximum rated current (IAD) Operation temperature Storage temperature Operation humidity Storage humidity Complementary characteristics Protection class / Overvoltage category Operation type Device action type Electrical stress period Degree of protection / Pollution degree Installation Minimum clearances Power failure back-up time Maximum current before overload notification Response on...
Open the catalog to page 2⚠ In order to ensure the expected status of the relays, please check that the device is connected to the main power supply before energizing the power circuit. For a 4-pipe fancoil, the cooling valve should always be connected on the left side and the heating valve on the right side. Before the startup of the device, it must be assured that the valve is completely closed. ABRIR OPEN CLOSE CERRAR ABRIR OPEN CLOSE CERRAR The fan and the valves to be connected must have the same nominal supply voltage. Outputs that are not being used for valve control can be used as individual outputs or...
Open the catalog to page 3Attaching ALLinBOX 1612 v2 to DIN rail: This device must be exclusively installed in a 35mm DIN rail inside a distribution box or an electrical panel. Ensure suitable ventilation to prevent the temperature from exceeding the permissible range. Main power must be connected to L, N and ground terminals. The coil integrated bus output must be connected through a standard KNX connector. The additional output connection must be connected according to the polarity indicated on the housing. Removing ALLinBOX 1612 v2 from DIN rail: Figure 3: Mounting ALLinBOX 1612 v2 on DIN rail SAFETY INSTRUCTIONS...
Open the catalog to page 4All ZENNIO AVANCE Y TECNOLOGIA catalogs and technical brochures
-
Zennio
63 Pages
-
ALLinBOX 88
4 Pages
-
ALLinBOX 46
4 Pages
-
Tecla 55 X1/X2/X4/X6
2 Pages
-
Product Catalogue
28 Pages