Product catalog summary
Features
  • The current transformer is designed to measure power for energy consumption data calculation.
  • Dimensions are 92 x 66 x 48.5mm.
  • It complies with CE directives.
Safety Instructions
  • Installation must be performed by qualified professionals in accordance with local laws and regulations.
  • Avoid connecting mains voltage or any external voltage to signal wiring to prevent system risks.
  • Ensure sufficient insulation between mains voltage and signal wiring.
  • Keep the device dry and uncovered during use.
  • Dispose of the device properly as it contains electronic parts, following WEEE regulations.
Transformer Installation
  1. Connect the transformer's terminals to KES Plus, ensuring correct polarity, before closing the clamp.
  2. Open the clamp, place the live cable inside, and close the clamp securing the lateral clip.
Transformer Specifications and Connections
  • Current range: 0.1 to 600A
  • Current Ratio: 600A/100mA
  • Operating temperature: -25ºC to +60ºC
  • Storage temperature: -30ºC to +90ºC
  • Accuracy: 1% at RL ≤ 10Ω
  • Linearity: ≤0.2% at RL ≤ 10Ω
  • Phase error: 1º at rated current range
  • Dielectric strength: 3.5KV
  • Maximal secondary side cable section: 2.5mm² (IEC) / 12AWG (UL)
  • Maximal secondary side cable length: 1.8m
  • Weight: 310g
  • Maximal diameter of primary side cable: Ø36mm
  • Transformer ratio (loops number): Np:Ns=1:6000
See more

Catalog excerpts

Accessory for KES Plus – 600A 9900045-1

Current Transformer •*Zennio Accessory for KES Plus - 600A 9900045 Technical Documentation FEATURES ■ Allows measuring power to calculate energy consumption data. ■ Please refer to the KES Plus datasheet for connection ■ Dimensions 92 x 66 x 48.5mm ■ Conformity with the CE directives TRANSFORMER INSTALLATION A Important: The terminals of the transformer must be connected to KES Plus (please observe polarity) before closing the clamp. 1. Open the transformer clamp and place the live cable inside, paying attention to the orientation. 2. Close the clamp around the cable fixing the lateral clip SAFETY INSTRUCTIONS Installation should only be performed by qualified professionals according to the laws and regulations applicable in each country. Do not connect the mains voltage nor any other external voltage to any point of the signal wiring; it would represent a risk for the entire system. The facility must have enough insulation between the mains (or auxiliary) voltage and the signal wiring or the wires of other accessories, in case of being installed. Keep the device away from water and do not cover it with clothes, paper or any other material while in use. The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructions at http://www.zennio.com/en/legal/weee-regulation. © Zennio Avance y Tecnologfa S.L. Ed. 1 Further information www.zennio.com Page 1 / 1

 Open the catalog to page 1