Product catalog summary
Overview
The document describes the HydroLogic Panel, a water-chilled raised floor tile designed for high-density cooling in data centers. It provides precise, individual, on-demand cooling and is scalable, space-efficient, and redundant.

Specifications
  • Cooling Capacity: 10 KW per panel, 20 KW per rack.
  • Water Temperature: 12°C in, 18°C out.
  • Voltage: 230 V, Power Consumption: 140 W.
  • Maximum Air Volume: 1600 m³/h, Maximum Water Volume: 1.43 m³/h.
  • Air Supply Temperature: 21°-25°C.
  • Water Connector: 3/4", Operation Pressure: 10 bar, Pressure Loss: 1 bar max.
  • Dimensions: 600 x 600 x 400 mm, Weight: 35 kg per panel.
  • Construction: Steel ventilation panel, powder-coated; Heat exchanger made of Aluminum/Copper.
  • Flammability Class: A1, Ground Resistance: < 109 Ohm.
  • Installation Heights: 500 - 2000 mm.

Functionality
  • The panel is placed in existing raster in hot and/or cold aisles.
  • Temperature sensors detect individual cooling demand.
  • Air is pressed through the heat exchanger into the cold aisle, drawn by servers, and released into the hot aisle.
  • Implemented dividers allow targeted airflow.

Connection and Installation
  • Requires connection to a separately needed chiller.
  • Supports closed and open loop configurations.
  • Redundant supply options available.

Contact Information
Weiss Doppelbodensysteme GmbH, Baenglesaecker 6 + 9, 73527 Schwaebisch Gmuend, Germany.
Tel: +49 (0) 7171 – 97601-0, Fax: +49 (0) 7171 – 97601-8, Email: [email protected]
Websites: www.hydrologicpanel.com, www.weiss-dbs.de
See more

Catalog excerpts

Hydrologi-1

Waterchilled Raised Floor Tile Hydr Logic Ventilated Panel steel Heat exchanger Catch your wave Waterchilled raised floor tile H igh Density Cooling 10 KW / Panel 20 KW per Rack* Different loops possible 1 Rack / many Racks in a row or containment (cold and or hot aisle) Precise, individual, on demand cooling Space efficient S calable, able to be retrofitted Redundant

 Open the catalog to page 1
Hydrologi-2

Open loop Closed Loop P anel is to be placed in existing raster in hot and / or cold aisle ir will be pressed through the heat exchanger into the cold aisle A T emperature sensors in rack and heat exchanger detect the individual cooling demand Server will draw in the demanded air volume and will release it into the hot aisle Panel is to be connected to separately needed chiller Air will be sucked in through the heat exchanger into the raised floor mplemented dividers allowing a targeted airflow I

 Open the catalog to page 2
Hydrologi-3

Connection to chiller 1-way – supply Redundant supply Technical data HydroLogic Panel: Voltage Power consumption Water Temperature Maximum water volume Water connector heat exchanger Operation pressure heat 10 bar exchanger Pressure loss heat exchanger Cooling media Water (optional Glycol mixture) Steel ventilation panel conductive, powder coated; Heat exchanger Aluminum / Coppper; Fan drawing or pushing direction Weiss Doppelbodensysteme GmbH Baenglesaecker 6 + 9 73527 Schwaebisch Gmuend Tel: +49 (0) 7171 – 97601-0 Fax: +49 (0) 7171 – 97601-8 e-mail: [email protected] Breaking load Flammability...

 Open the catalog to page 3