Overview: This document provides detailed specifications and operational guidelines for various Sentinel D-Box sensors and controls, which are exclusive to Sentinel products and not compatible with other systems.
Ambient Response Humidity Sensor: This sensor maintains humidity control between 72-75% RH and includes a night-time setback function to prevent false alarms. It features a manual override via a pullcord and can operate in On/Off or Trickle/Boost modes. The operating range is 30%-90% RH, with a temperature range of +5°C to +40°C. Dimensions are 87 x 87 x 33mm.
Ecotronic Humidity Sensor: Automatically controls humidity between 65-90% RH with a manual override option. It supports On/Off or Trickle/Boost operations and has an adjustable set point. The maximum switching load is 1 amp inductive, and it operates within 0°C to +40°C. Dimensions are 87 x 87 x 33mm.
Vent-Axia ThermoSwitch®: This device activates fans based on temperature changes, suitable for Trickle/Boost operations. The setting range is +6°C to +30°C, with IP20 rating and dimensions of 80 x 104 x 36mm.
Air Quality Sensor (AQS): Designed to detect air quality deterioration, it adjusts ventilation in response to tobacco smoke and odors. It should not be used for combustible gas detection. The operating temperature range is 0°C to +50°C, with dimensions of 87 x 157 x 47mm.
Vent-Axia Visionex PIR: A presence detector for wall or ceiling installation, with a detection range up to 10 meters. It features an adjustable timer and operates within 0°C to +50°C. Dimensions are 104 x 74 x 52mm.
7 Day TimeSwitch: Provides scheduled switching for various applications, with twelve On/Off positions per day. It operates within -20°C to +85°C and dimensions are 104 x 74 x 52mm.
Remote Speed Control: Offers variable fan speed control without On/Off switching. It operates within -5°C to +40°C and dimensions are 84 x 84 x 30mm.
CO2 Duct Probe: Monitors CO2 levels in ducts, enhancing air quality by adjusting extraction rates. It operates within 0-2000ppm CO2 range and dimensions are 100 x 84 x 25mm.
CO2 + Temp Room Sensor: Monitors CO2 and temperature for ventilation control, operating within 0-2000ppm CO2 and 0-50°C. Dimensions are 100 x 84 x 25mm.
Remote Fan Status Indicator: Displays fan status and condition, suitable for all Sentinel modes. It operates within -5°C to +50°C and dimensions are 86 x 86 x 28mm.
Constant Pressure System Accessories PIR Grille: Features a PIR sensor and auto-humidity control damper, suitable for bathrooms and WCs. It operates within 0-50°C and dimensions are 158 x 150 x 35mm.
Dampers: Available in MM and PC types, these dampers adjust airflow based on sensor control. Duct sizes range from 100 to 315mm.
Power Supply: Provides a 24V DC SELV supply with a 24W output capacity, necessary for certain installations.
See more

Catalog excerpts

Sentinel D-Box Sensors & Controls-1

Ambient Response Humidity Sensor* Humidity Sensor control is fixed at 72 - 75%RH. Incorporates a night time 'set back' function to avoid nuisance tripping as the humidity level rises when the air cools. An integral pullcord provides a manual override function if required. Can be wired for either On/Off or Trickle/Boost operation. Pullcord override and neon indicator. Changeover relay switch. Operating range: 30% - 90%RH. Ambient operating temperature +5°C to +40°C. 24V DC SELV. Dimensions:87 x 87 x 33mm (H x W x D). Will fit single gang box for surface mounting. Stock Ref 432945 rings are included to allow setting within a limited temperature range or locking at a fixed set-point. IP20 rated. Sealed sensing mechanism. Mounting direct on surface only. Dimensions: 80 x 104 x 36mm (H x W x D). Volt free switch connection to Sentinel. Stock Ref 563502 Air Quality Sensor (AQS) * Automatically reacts to the deterioration of air quality, sensing tobacco smoke, smells and toilet odours to regulate mechanically ventilated areas, such as cinemas, pubs, clubs, restaurants, kitchens, toilets and conference rooms. Ecotronic Humidity Sensor* Humidity Control is automatic and can be set to switch between 65 and 90%RH. An integral pullcord provides a manual override function if required. Can be wired for either ON/OFF or Trickle/Boost operation. Set point adjustable. Maximum switching load 1 amp inductive. Pullcord override indicator. Ambient operating temperature 0°C to +40°C. Dimensions:87 x 87 x 33mm (H x W x D). Supply voltage 24V DC SELV. Humidity sensors should be sited approx. 100mm below ceiling level and not above cupboards, refer to siting details in fitting and wiring instructions supplied with product. Stock Ref 432949 Vent-Axia ThermoSwitch® Automatically switches on fans on either a rise or fall in air temperature. Can be used for Trickle/ Boost operation on either intake or extract systems. Setting range: +6°C to +30°C. Two internal range limit/locking The sensor switches when the air quality declines below an adjustable preset level. This is registered by a self-cleaning ceramic sensing head. The air quality sensor should not be used for the detection of combustible gases. Ambient operating temperature range 0°C to +50°C. MIN -MAX mode or direct Damper control. Dimensions:87 x 157 x 47mm (H x W x D) Surface mounted. 1 - 25 min O/R timer. Supply voltage Vent-Axia Visionex PIR* A wall or ceiling person presence detector for use with Sentinel. Can be used in MIN - MAX mode or for direct damper control. Fits any UK single gang mounting box. Adjustable timer overrun (5-25 minutes). Range of detection up to 10 metres. Designed to meet IP43. Ambient operating temperature range 0°C to +50°C. Supply voltage 24V DC SELV. Stock Ref PLEASE NOTE: These sensors/controls are unique to Sentinel and CANNOT be used with any other product.

 Open the catalog to page 1
Sentinel D-Box Sensors & Controls-2

7 Day TimeSwitch For applications where regular switching is required at fixed periods or at different times on different days of the week, eg:offices, shops, pubs and restaurants. The 7 Day TimeSwitch gives twelve On or Off positions per day and can be set for 7 days. The cycle will repeat until changed. Volt free switch connection to Sentinel. Analogue clock display and integral time switches for ease of setting. Manual override. Removable clear plastic cover protects timeswitch face. Time base: 7 days. Shortest switching time: 2 hours. Ambient operating temperature range -20°C to +85°C. Dimensions:...