TRISTAR 3G

TRISTAR 3G
1 / 10 PagesView full catalog

TRISTAR 3G

Product catalog summary
Overview: The TRISTAR 3G is a pressurized carbon steel boiler designed for outputs between 65 and 3000 kW. It supports fuels like natural gas, LPG, and light oil, with a minimum return temperature of 50°C.
Specifications: Available in various models, the TRISTAR 3G is certified under Dir. 92/42/EC and constructed with certified carbon steel, complying with EN 303 part 1 standards. It features patented smoke pipes and a floating furnace design.
Technical Features: The boilers have an oval or cylindrical shell with a fully wet cylindrical furnace. A special collector-distributor ensures optimal water circulation, reducing stratification and preventing condensation and corrosion.
Main Components: Key components include the furnace, smoke pipes with diverters, a door with a flame sight glass, a smoke chamber, body insulation, and a control panel. The door is reversible, and the boiler is insulated with mineral wool.
Operational Flexibility: The boilers support ON/OFF, two-stage, or modulating burners, maintaining a minimum thermal power of 60% of the furnace load. They are designed for easy handling and installation.
Performance and Efficiency: High efficiency is achieved at both full and part loads, with NOx emissions below 100 mg/kWh. The elliptic shape of models up to 840 kW facilitates easier access.
Installation and Maintenance: Designed for easy maintenance, the boilers have cleaning doors and flame sight glasses. They offer various connection options for central heating flow, return, expansion vessel, and chimney.
Dimensions and Weight: Detailed dimensions and weights are provided for each model, ensuring compatibility with standard doorways for easy installation.
Performance Metrics: The boilers achieve nominal load efficiencies between 93.9% and 95.9%, with minimal heat losses and specified flue gas temperatures and CO2 content.
Special Features: Patented "EASY STREAM Pipes" with aluminum multi-fin structures enhance efficiency. Electrical, hydraulic, and installation diagrams are available online.
Recommendations: Adherence to specified pressure drops and installation guidelines is recommended for optimal performance.
See more

Catalog excerpts

TRISTAR 3G-1

BREVETTO Unical PATENT smoke pipes PRESSURIZED CARBON STEEL BOILER WITH THREE REAL SMOKE PASS OUTPUT RANGE from 65 to 3000 kW OPERATION TEMPERATURE minimum return temperature 50°C Natural Gas or LPG fed pressure jet, two stage or modulating burners The models 2300 - 2650 - 3000 can be fed also with light oil SUPPLY MODELS ENERGETIC CLASS according to Dir. 92/42/EC Certified in OUTPUT RANGE Special patented smoke pipes with aluminium profiles - Floating furnace

 Open the catalog to page 1
TRISTAR 3G-2

Effective three pass boiler 2. Smoke pipes with smoke diverters 3. Door with flame sight glass 5. Body insulation 6. Panel board Heat output Heat input Efficiency at Efficiency at Boiler Water side Flue gas Max. boiler Flue gas Combustion Weight min/max min/max full load part load capacity pressure pressure operating temperature chamber MODEL (100%) (30%) drops drops pressure On special order the boilers from model TRISTAR 3G 2S 1100 to TRISTAR 3G 3000 can be manufactured for a max. working pressure up to 10 bar.

 Open the catalog to page 2
TRISTAR 3G-3

Effective three pass boiler ■ UTILISATION FLEXIBILITY thanks to the certification in ranged output ■ REDUCED NOx EMISSIONS: < 100 mg/kWh thanks to the reduction of the specific thermal load ■ ELLIPTIC SHAPE OF THE OUTER SHELL (up to mod. 840 kW): reduced width making easier access through the doors ■ OTTIMIZZAZIONE SCAMBIO TERMICO through driven and braked run of the water within the boiler ■ SMOKE PIPES EASY STREAM PIPE 0 1”1/2 ■ FLOATING CYLINDRICAL FURNACE without thermomechanical stresses from 500 kW to 3000 kW ■ FURNACE BOTTOM with stiffening and heat dissipating plates ■ FRONT DOOR with...

 Open the catalog to page 3
TRISTAR 3G-4

Effective three pass boiler DIMENSIONS TRISTAR 3G 2S 65-85 1 Panel board 2 Smoke chamber cleaning door 3 Flame sight glass T1 Central Heating flow T2 Central Heating return T3 Expansion vessel connection T4 Boiler drain T5 Chimney connection T6 Burner connection T7 Condensation drain ABCDEFGH I LMNOPQ*R* (*) Minimum dimensions for boiler room access. (**) Pressure drops corresponding to a thermal drop of 15K.

 Open the catalog to page 4
TRISTAR 3G-5

Effective three pass boiler 1 Panel board 2 Smoke chamber cleaning door 3 Flame sight glass T1 Central Heating flow T2 Central Heating return T3 Expansion vessel connection T4 Boiler drain T5 Chimney connection T6 Burner connection T7 Condensation drain TRISTAR ABCDEFGH I LM*NOPQ*R*S (*) Minimum dimensions for boiler room access. (**) Pressure drops corresponding to a thermal drop of 15K.

 Open the catalog to page 5
TRISTAR 3G-6

Effective three pass boiler DIMENSIONS TRISTAR 3G 2S 500^730 - 840 1 Panel board 2 Smoke chamber cleaning door 3 Flame sight glass T1 Central Heating flow T2 Central Heating return T3 Expansion vessel connection T4 Boiler drain T5 Chimney connection T6 Burner connection T7 Condensation drain TRISTAR ABCDE FGHM*NOPQ*R*S* (*) Minimum dimensions for boiler room access. (**) Pressure drops corresponding to a thermal drop of 15K.

 Open the catalog to page 6
TRISTAR 3G-7

Effective three pass boiler "(5 1 Panel board 2 Smoke chamber cleaning door 3 Flame sight glass T1 Central Heating flow T2 Central Heating return T3 Expansion vessel connection T4 Boiler drain T5 Chimney connection T6 Burner connection T7 Condensation drain TRISTAR ABCD E FGHM*NOPQ*R* (*) Minimum dimensions for boiler room access. (**) Pressure drops corresponding to a thermal drop of 15K. On special order the boilers from model 1100 to 3000 can be manufactured for a max. working pressure up to 10 bar.

 Open the catalog to page 7
TRISTAR 3G-8

Effective three pass boiler DIMENSIONS TRISTAR 3G 2300-3000 1 Panel board 2 Burner connection flange 3 Smoke chamber cleaning door 4 Flame control warming light T3 Expansion vessel connection T7 Condensation drain (*) Minimum dimensions for boiler room access. (**) Pressure drops corresponding to a thermal drop of 15K. On special order the boilers from model 1100 to 3000 can be manufactured for a max. working pressure up to 10 bar.

 Open the catalog to page 8
TRISTAR 3G-9

Effective three pass boiler The pipes of the third smoke pass are decisive for the attainment of the maximum efficiency. The new patented technology has allowed to insert special aluminium multi-fin structures inside the thick steel pipes. In this way are born the new “EASY STREAM Pipes” of 1 1/2” diameter.

 Open the catalog to page 9
TRISTAR 3G-10

Effective three pass boiler TECHNICAL DATA ELECTRICAL, HYDRAULIC, INSTALLATION DIAGRAMS AND CONTROLLERS can be unloaded from the web site www.unical.eu at the page of the product

 Open the catalog to page 10

All UNICAL AG S.p.A. catalogs and technical brochures

  1. T.IT K

    2  Pages

  2. HP 230

    2  Pages

  3. HP 110

    2  Pages

  4. HP_QOR

    2  Pages

  5. FOKOLUS

    8  Pages

  6. EXOCELL

    4  Pages

  7. AIREX 150-200

    2  Pages

  8. RECAL

    2  Pages

  9. !DEA

    8  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.