RM-O-VS-D-1

Smoke detector Type RM-O-VS-D with air flow monitor for control of fire and smoke dampers General building approval

 Open the catalog to page 1
RM-O-VS-D-2

Contents · Applications · Technical Data ______ Applications · Technical Data _______________________ Installation instructions _________________________________ Functional description ______________________________________ Circuit diagrams _______________________________________ Maintenance ______________________________________________ ___________ Order details ____________________________________ ቢ Smoke detector with mains adapter, ባ ቤ ብ ቦ ቧ sensor electronics, smoke sensor and air flow monitor unit “Reset / Test” button Signal lamp - green - “System monitoring” Signal lamp - red “Alarm condition”...

 Open the catalog to page 2
RM-O-VS-D-3

Installation instructions Installation instructions · The smoke detector must be installed on a vibration free surface, in an area of the duct to be monitored, having a uniform air flow over and into the smoke sensor to ensure the proper operation of the smoke alarm. · Locate the drilling jig ቮ on the duct ቭ and drill holes (note arrangement and desired installation orientation). · Using the assembly fixing screws ቯ, attach the casing to the duct ቭ. · Loosen cover fixing screws 1.3 and open the sealed cover 1.1 of the casing. · Connect fire or smoke damper release mechanism (terminal block L3)....

 Open the catalog to page 3
RM-O-VS-D-4

Functional description 2) The blue LED goes out at air velocity < 2 m/s or after the fire or smoke damper closes. 3) The alarm situation, triggered by smoke (event or maintenance), can only be cancelled by pressing the button after the smoke sensor head is again free of smoke.

 Open the catalog to page 4
RM-O-VS-D-5

Circuit diagrams The entire electrical system must be installed in accordance with VDE (or National equivalent) and the local Energy Supply Company regulations. Also current National Legal Standards related to the “Regulations on fire protection requirements for ventilation plants” must be complied with. Figure 1 Circuit diagram RM-O-VS-D (Fire or smoke damper in CLOSED position) Figure 2 Installation with separate power supply for the control device A on the system fire or smoke damper Reset (external) Mains connection 230 V, 50/60 Hz Manual release Terminal 1-2 X3 Connection for smoke detector...

 Open the catalog to page 5
RM-O-VS-D-6

Maintenance General Maintenance (annually during the inspection) The operator must comply with the basic maintenance requirements in accordance with DIN 31051 (Principles of maintenance) in conjunction with DIN EN 13306 (Maintenance concepts). Maintenance activities may only be carried out by qualified companies / specialist staff. The results of all maintenance activities must be documented. These documents should be held by the operator. Documentation should also include general building approval. Inspection and maintenance must be carried out annually. Inspection (at commissioning phase and...

 Open the catalog to page 6
RM-O-VS-D-7

Order code Specification text Order example Smoke detector (smoke sensing using optical light scatter Manufacturer: TROX principle) to prevent transfer of smoke via the ventilation Type: RM-O-VS-D_ ducting in air conditioning systems. Quantity: 5_ Suitable for control and release of fire and smoke dampers with General Building Approval equipped with electric or electro-pneumatic release mechanisms and working on the principle of power off to close. Essential features • With integral mains adapter (supply voltage 230 V, • Zero potential signal relay • Integral signal lamps • Sealed cover connected...

 Open the catalog to page 7

All TROX catalogs and technical brochures

  1. Retrofit kits

    6  Pages

  2. X-GRILLE Cover

    18  Pages

  3. ATVC-100

    8  Pages

  4. X-CUBE Compact

    12  Pages

  5. ARR

    2  Pages

  6. VMRK

    4  Pages

  7. VFR

    8  Pages

  8. Tunnel dampers

    20  Pages

  9. FKS-EU

    20  Pages

  10. CAK

    6  Pages

  11. Type ST · XT

    8  Pages

  12. Type NL

    8  Pages

  13. Type PKV

    7  Pages

  14. Type BID

    8  Pages

  15. Type QLI

    8  Pages

  16. LVC

    9  Pages

  17. RM-O-3-D

    7  Pages

  18. FK-EU

    56  Pages

  19. EK-01

    14  Pages

  20. XSA

    12  Pages

  21. MSA

    12  Pages

  22. SCHOOLAIR-V

    12  Pages

  23. SCHOOLAIR-B

    12  Pages

  24. FSL-B-SEK

    4  Pages

  25. DID632

    20  Pages

  26. DID300B

    12  Pages

  27. DID312

    16  Pages

  28. AGW

    24  Pages

  29. AGS

    24  Pages

  30. DLQ-1...4-AK

    13  Pages

  31. DQ/ADQ

    9  Pages

  32. DLQ/ADLQ

    10  Pages

  33. DLK-Fb

    4  Pages

  34. VD

    10  Pages

  35. QSH · ISH

    8  Pages

  36. DLQL

    12  Pages

  37. X-CUBE

    16  Pages

  38. FV-K90

    12  Pages

  39. AK-Ex

    5  Pages

  40. JZ-RS

    5  Pages

  41. FKRS-EU

    28  Pages

  42. Star Climate

    16  Pages

  43. SD

    10  Pages

  44. AIRNAMIC

    12  Pages

  45. XARTO

    12  Pages

  46. X-CUBE COMPACT

    10  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.