RM-O-3-D - 1

Smoke Detector Type RM-O-3-D for control of fire and smoke dampers General Building Approval TROX GmbH

Open the catalog to page 1
RM-O-3-D - 2

Contents · Application · Technical Data ______ Contents · Application · Technical Data _______________ Installation Instructions _________________________________ Functional Description ______________________________________ Circuit Diagrams ______________________________________ Maintenance ______________________________________________ ___________ Order Details ____________________________________ ቢ Smoke detector with mains adapter, smoke sensor and ባ ቤ ብ ቦ sensor electronics “Reset / Test” button Signal lamp - green - “System monitoring” Signal lamp - red - “Alarm condition” Signal lamp...

Open the catalog to page 2
RM-O-3-D - 3

Installation Instructions Installation instructions · The smoke detector must be installed on a vibration free surface, in an area of the duct to be monitored, having a uniform air flow over and into the smoke sensor to ensure the proper operation of the smoke alarm. · Stick the drilling template item ቨ on the ventilation duct item ቧ and drill holes (consider the orientation). · Using the fixing screws item ቩ, attach the casing to the ventilation duct item ቧ. · Loosen the cover fixing screws item 1.3 and remove the cover plate item 1.1 . · Connect the fire or smoke damper release mechanism....

Open the catalog to page 3
RM-O-3-D - 4

Functional Description Fire or smoke damper OPEN Operational status / Event Signal relay CLOSED Mains turned on – Functional status – Mains turned on Electronics defective No smoke sensor – Alarm situation, immediate release signal – Dust / Contamination > 70 % < 90 % Dust / Contamination > 90 % – Alarm situation, immediate release signal – Reset / Test – Inspection – Smoke 2) – Alarm situation, immediate release signal – indicator – Normal range – Warning range – Alarm range Alarm relay 2) The alarm situation, triggered by smoke (event or maintenance), can only be cancelled by pressing the...

Open the catalog to page 4
RM-O-3-D - 5

Circuit Diagrams The entire electrical system must be installed in accordance with VDE (or National equivalent) and the local Energy Supply Company regulations. Also current National Legal Standards related to the “Regulations on fire protection requirements for ventilation plants” must be complied with. Figure 1 Circuit diagram RM-O-3-D (Fire or smoke damper in CLOSED position) Figure 2 Installation with separate power supply for the release mechanism A on the system fire or smoke damper Reset / Test N (–) Reset / Test (extern) (external) Six-point terminal strip (L1) • Mains connection...

Open the catalog to page 5
RM-O-3-D - 6

Maintenance General Maintenance (annually during the inspection) The operator must comply with the basic maintenance requirements in accordance with DIN 31051 (Principles of maintenance) in conjunction with DIN EN 13306 (Maintenance concepts). Maintenance activities may only be carried out by qualified companies / specialist staff. The results of all maintenance activities must be documented. These documents should be held by the operator. Documentation should also include the General Building Approval. Inspection and maintenance must be carried out annually. Inspection (at commissioning...

Open the catalog to page 6
RM-O-3-D - 7

Order Details Order code Specification text Order example Smoke detector (smoke sensing using optical light scatter principle) to prevent transfer of smoke via the ventilation ducting in air conditioning systems. Suitable for control and release of fire and smoke dampers with General Building Approval equipped with electric or electro-pneumatic release mechanisms and working on the principle of power off to close. Manufacturer: TROX Type: RM - O - 3 - D Quantity: 5 Essential features · Granted General Building Approval Z-78.6-125 by the German Institute for Structural Engineering, Berlin ·...

Open the catalog to page 7

All TROX catalogs and technical brochures

  1. X-GRILLE Cover

    18 Pages

  2. ATVC-100

    8 Pages

  3. X-CUBE Compact

    12 Pages

  4. ARR

    2 Pages

  5. VMRK

    4 Pages

  6. VFR

    8 Pages

  7. Tunnel dampers

    20 Pages

  8. FKS-EU

    20 Pages

  9. CAK

    6 Pages

  10. Type NL

    8 Pages

  11. Type PKV

    7 Pages

  12. Type BID

    8 Pages

  13. Type QLI

    8 Pages

  14. LVC

    9 Pages

  15. RM-O-VS-D

    7 Pages

  16. FK-EU

    56 Pages

  17. EK-01

    14 Pages

  18. XSA

    12 Pages

  19. MSA

    12 Pages

  20. SCHOOLAIR-V

    12 Pages

  21. SCHOOLAIR-B

    12 Pages

  22. FSL-B-SEK

    4 Pages

  23. DID632

    20 Pages

  24. DID300B

    12 Pages

  25. DID312

    16 Pages

  26. AGW

    24 Pages

  27. AGS

    24 Pages

  28. DLQ-1...4-AK

    13 Pages

  29. DQ/ADQ

    9 Pages

  30. DLQ/ADLQ

    10 Pages

  31. DLK-Fb

    4 Pages

  32. VD

    10 Pages

  33. QSH · ISH

    8 Pages

  34. DLQL

    12 Pages

  35. X-CUBE

    16 Pages

  36. FV-K90

    12 Pages

  37. AK-Ex

    5 Pages

  38. JZ-RS

    5 Pages

  39. FKRS-EU

    28 Pages

  40. Star Climate

    16 Pages

  41. SD

    10 Pages

  42. AIRNAMIC

    12 Pages

  43. XARTO

    12 Pages

  44. X-CUBE COMPACT

    10 Pages

Archived catalogs

  1. Slot Diffuser

    11 Pages