1. Catalogs
  2. Thermafiber, Inc
  3. Sound Attenuation Fire Blankets (SAFB)
video corpo
cad

Sound Attenuation Fire Blankets (SAFB)

Sound Attenuation Fire Blankets (SAFB)
1 / 13 PagesView full catalog

Sound Attenuation Fire Blankets (SAFB)

Product catalog summary
Introduction
THERMAFIBER® Sound Attenuation Fire Blankets (SAFB) are designed for superior sound and fire performance in wall and ceiling assemblies. These mineral-fiber blankets are noncombustible, offering high sound attenuation and contributing to high fire ratings, ideal for multi-family residential projects, hotels, offices, and retail businesses.
System Performance
THERMAFIBER SAFBs are recognized for their high quality, offering more fire, sound, and thermal tests than other insulation products. They resist sagging due to high density and enhance fire protection in various assemblies, effectively reducing low-frequency sound levels.
Superior Sound Attenuation
THERMAFIBER SAFBs significantly improve sound attenuation ratings, outperforming glass fiber insulation. For instance, a 3-5/8" steel-framed wall with 5/8" gypsum panels achieved an STC of 49 with 3" THERMAFIBER SAFBs, compared to STC 47 with glass fiber insulation.
Superior Fire Resistance
THERMAFIBER products are noncombustible and withstand temperatures over 2,000 °F, maintaining integrity longer than glass fiber insulation in fire tests, making them highly effective in fire protection.
Environmental Benefits
THERMAFIBER SAFBs contain over 80% recycled content, contributing to LEED® credits and reducing greenhouse gas emissions by lowering energy needs for heating and cooling. They meet high standards for indoor air quality, being inorganic and resistant to mold and mildew.
Fire Performance Testing
THERMAFIBER SAFBs have been extensively tested for fire performance, demonstrating superior characteristics compared to glass fiber insulation. In tests, THERMAFIBER insulation remained intact significantly longer than glass fiber, which melted or fell away.
Sound and Fire-Rated SAFB Assemblies
Various assemblies using THERMAFIBER SAFBs have been tested for acoustical performance and fire ratings, including steel stud partitions with different configurations, achieving high STC ratings and fire resistance.
Technical Data and Good Design Practices
THERMAFIBER provides detailed technical data and design practices to optimize the use of SAFBs in construction projects, ensuring maximum performance in sound attenuation and fire resistance.
Conclusion
THERMAFIBER Sound Attenuation Fire Blankets offer unmatched performance in sound and fire protection, making them a valuable choice for various building applications.
Overview
This document provides technical specifications and guidelines for various non-load bearing and load-bearing wall and ceiling systems using SHEETROCK® Brand gypsum panels and THERMAFIBER Sound Attenuation Fire Blankets (SAFB). It includes details on sound transmission class (STC) ratings, fire ratings, and installation procedures.
Specifications
  • Steel Stud Chase Walls: Non-load bearing walls with specific STC ratings based on SHEETROCK® Brand gypsum panels.
  • Shaft Wall Systems: Non-load bearing with detailed STC and fire ratings.
  • Area Separation Walls: Designs and STC values provided for various configurations.
  • Demountable Partitions: Non-load bearing with specific installation guidelines.
Procedures
  • Installation of THERMAFIBER SAFB: Detailed steps for installing SAFB in stud cavities and joist cavities to achieve desired sound and fire ratings.
  • Creased THERMAFIBER SAFB: Special installation technique to enhance sound performance by compressing the blanket within the cavity.
Standards and Compliance
  • THERMAFIBER SAFB meets various ASTM standards and is approved for use in New York City.
  • Compliance with NFPA 101 for Class A interior finish rating.
Recommendations
  • Substitution of materials may compromise system performance; adherence to specified materials is crucial.
  • Proper application of acoustical sealant is essential to reduce sound transmission.
  • Vapor retarders should be placed on the warm side of the wall, as specified by a professional engineer.
Technical Data
  • THERMAFIBER SAFB is available in various densities and thicknesses, with specific R-values and flame spread ratings.
  • Creased SAFB is engineered for enhanced sound performance in specific assemblies.
Good Design Practices
  • Ensure adjacent assemblies have similar sound control performance.
  • Seal all wall penetrations and perimeters with acoustical sealant.
Safety and Liability
  • Follow safety and industrial hygiene practices during handling and installation.
  • Liability is limited to the replacement of defective goods, with claims to be made within 30 days.
See more

Catalog excerpts

Sound Attenuation Fire Blankets (SAFB)-1

THERMAFIBER® Sound Attenuation Fire Blankets (SAFB) For unsurpassed sound and fire performance for walls and ceilings

 Open the catalog to page 1
Sound Attenuation Fire Blankets (SAFB)-2

3 System Performance Superior Sound Attenuation Superior Fire Resistance 4 Fire Performance Testing 5 Sound and Fire-Rated SAFB Assemblies 10 Technical Data 11 Good Design Practices 11 Architectural Specifications Contents

 Open the catalog to page 2
Sound Attenuation Fire Blankets (SAFB)-3

THERMAFIBER® Sound Attenuation Fire Blankets (SAFB) are the best way to stop sound in wall and ceiling assemblies. The noncombustible mineral-fiber composition of this product not only gives it high sound attenuation characteristics, but also enables it to contribute to high fire ratings in many assemblies. The tests prove that THERMAFIBER SAFBs are the best performance value for multi-family residential projects, hotels and motels, offices and retail businesses. A few of the innumerable tests of assemblies utilizing THERMAFIBER SAFBs for sound and fire performance are shown on pages 5-9. For...

 Open the catalog to page 3
Sound Attenuation Fire Blankets (SAFB)-4

Fire Performance Effective performance for both high sound and fire ratings is the unique characteristic of THERMAFIBER Sound Attenuation Fire Testing Blankets. Glass fiber insulation simply doesn’t compare. Glass fiber’s lower density means lower sound performance, according to sound tests conducted by USG. Evaluations of various densities and thicknesses showed that the best acoustical performance in mid- and high-frequency sound (typical in offices and between hotel rooms) was with insulations of a nominal density of 2.5 lb./cu. ft. Densities above 2.5 lb./cu. ft. performed better at higher...

 Open the catalog to page 4
Sound Attenuation Fire Blankets (SAFB)-5

Sound & Fire Tests The following are typical assemblies containing THERMAFIBER Sound Attenuation Fire Blankets (SAFBs). Each has been tested for acoustical performance and each has a fire rating or estimated fire rating. The Sound Transmission Class (STC), Impact Insulation Class (IIC), Ceiling Attenuation Class (CAC) and Field Sound Transmission Class (FSTC) are listed first and assemblies of each type are listed in order with highest sound performance first. UL design or other fire test or sound test information are identified at the end of the assembly description. A wide variety of systems...

 Open the catalog to page 5
Sound Attenuation Fire Blankets (SAFB)-6

54 STC* 1-hr. partition, single-layer, resilient channel— 39 THERMAFIBER SAFB in stud cavity—5/89 gypsum wallboard Type C core—3-5/89 20 ga steel studs 249 o.c.—RC-1 chan or equivalent one side spaced 249o.c. screw-att to studs—gypsum panels screwatt to studs & RC-1 channels—joints stag and fin— perimeter caulked—UL Des U419 or U451 rating also applies with IMPERIAL Brand gypsum base, FIRECODE C core, and veneer finish surface— RAL-TL-83-216 A-14 50 STC 2-hr. partition, single-layer—39 THERMAFIBER SAFB in stud cavity—3/49 SHEETROCK Brand gypsum Panels, ULTRACODE core, ea side—min. 3-1/29 25 ga...

 Open the catalog to page 6
Sound Attenuation Fire Blankets (SAFB)-7

57 STC** 2-hr. partition, double-layer chase wall—3-1/2" THERMAFIBER SAFB on one side in stud cavity— 2 layers 5/8" gypsum wallboard Type X ,ea side— 1-5/8" 25 ga steel studs 24" o.c. in 2 rows spaced 6-1/4" apart—5/8" gypsum panel gussets or steel run braces spanning chase screw-att to studs— panels appl screw att—joints stag & fin—UL Des U420—TL-76-156 52 STC** 1-hr. partition, single-layer chase wall—3-1/2" THERMAFIBER SAFB on one side in stud cavity—5/8" gypsum wallboard Type X, ea side—1-5/8" 25 ga steel studs 24" o.c. in 2 rows spaced 6-1/4" apart— 5/8" gypsum panel gussets or steel run...

 Open the catalog to page 7
Sound Attenuation Fire Blankets (SAFB)-8

59 STC* 2-hr. partition—double-layer, resilient channel— 29 THERMAFIBER SAFB in stud cavity—2 layers 5/89 gypsum wallboard Type C core, each side—2 x 4 169 o.c.—RC-1 channel or equivalent one side, spaced 249 o.c.—resilient side screw att—opp side nail att—both base layers appl vert and face layers appl horiz—resilient layers perimeter caulked—joints fin—UL Des U334—TL-67-239 50 STC* and **** 1-hr. partition—single-layer—3" THERMAFIBER SAFB in stud cavity—1/2" Cemetitious Backer Board (cement board) and 1/4" ceramic tile one side—5/8" gypsum wallboard Type C, one side—3-5/8" 20 ga steel studs...

 Open the catalog to page 8
Sound Attenuation Fire Blankets (SAFB)-9

Cement Board/Wood Stud Partitions (Load Bearing) 40 STC* and **** 1-hr. partition—single-layer—3-1/2" THERMAFIBER SAFB in stud cavity—1/2" Cemetitious Backer Board (cement board) and 1/4" ceramic tile one side—2 x 4 studs 16" o.c.—board att with 1-5/8" TYPE S-12 corrosion resistant wafer-head steel screws or 1-1/2" hot-dipped galv nails 8" o.c.—5/8" gypsum wallboard Type C core other side—joints taped—UL Des U329—USG-840314 A-114 Mineral Fiber Overlay on Acoustical Ceiling System Wood Joist Ceiling Systems (Unrestrained Assemblies) 47 STC/40 IIC* 1-hr. ceiling—single-layer— 1" FIRESPAN 90 laid...

 Open the catalog to page 9
Sound Attenuation Fire Blankets (SAFB)-10

Technical Data THERMAFIBER Sound Attenuation Fire Blankets are available in two densities and nine thicknesses to meet a variety of sound and fire performance needs. Also, Creased THERMAFIBER SAFB, a specially engineered product, is available for certain high-performance sound-rated assemblies. The table below shows the R-values and densities available for various thicknesses of THERMAFIBER SAFBs, as well as “k” values, sizes, flame spread and smoke developed ratings and density tolerances. THERMAFIBER SAFB insulation in a typical partition assembly. Creased This specially engineered SAFB insulation...

 Open the catalog to page 10
Sound Attenuation Fire Blankets (SAFB)-11

Specification Compliance THERMAFIBER Sound Attenuation Fire Blankets meet the following: 1. Class A interior finish rating per NFPA 101, life safety code. 2. ASTM C665, Type 1, per Federal Specification HH-I-521F. 3. ASTM C553 (SAFB Blankets absorb less than 1% moisture by weight and volume). 4. ASTM C612, Type 1, per Federal Specification HH-I-558B. 5. ASTM E136 (rated noncombustible as defined by NFPA Standard 220 when tested according to ASTM E136). 6. Accepted by New York City Department of Buildings (MEA-207-82M). Approved by the New York City Board of Standards & Appeals for use in New...

 Open the catalog to page 11