OpenAir™ VAV Compact Controller KNX / PL-Link G..B181.1E/KN VAV Compact Controller 5 / 10 Nm with KNX communication • GDB181.1E/KN with 5 Nm nominal torque • GLB181.1E/KN with 10 Nm nominal torque • Operating voltage AC 24 V • Supports KNX S-Mode, LTE-Mode, and PL-Link • For plants with variable or constant air-volume flow Siemens Building Technologies
Open the catalog to page 1For a detailed description of specific functions please refer to the product documentation P3547. Siemens Building Technologies
Open the catalog to page 2LED colors and patterns Color 2) Function or part of the function available in PL-Link operation only Addressing and bus test with push button The VAV compact controllers can be set into addressing/programming mode by push-button: ■ Press push button (>0.1s and <1s) ■ KNX bus wiring OK ^ LED turns red until addressing/programming is finished ■ KNX bus wiring not OK ^ LED stays dark Reset with push button The VAV compact controllers can be reset by push-button: ■ Press push button > 20s ■ Device restarts All parameters which can be set by the OEM are reset to the OEM default values. Siemens Building...
Open the catalog to page 3Parameterization of the VAV application The OEM generally provides the basic configuration to VAV compact controllers, especially the parameters for nominal flow (Vnom), the opening direction, and the box coefficient (Vn). The setting of all other parameters depends on the actual application and is usually defined by the ventilation planner or the systems integrator. The following parameters must be checked or set prior to commissioning: 3) Value used for displaying / not used for volume flow control loop Operating mode “Volume flow control” Variable air volume (VAV) control The operating point...
Open the catalog to page 4The following parameters are usually checked and set by the systems integrator to achieve the right level of bus traffic generated by the actuator or to define the behavior in case of communication interruption. Parameters in the group “advanced” can be left unchanged unless a special configuration is required. Parameter group “Standard”: Parameter group “Advanced”: Siemens Building Technologies
Open the catalog to page 5Notes Safety Caution National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage. ● Observe national provisions and comply with the appropriate safety regulations. Mounting ● Do not open the damper actuators ● Do not use the accessory mounting holes for fixation of the damper actuators Mounting positions IP54 protection in following mounting positions Accessory mounting holes Not to be used for fixation of the actuator, use anti-rotation-bracket instead. Maintenance The damper actuators are maintenance-free. Disconnect the electrical...
Open the catalog to page 6Object function Data point type KNX Fault information [0...255 ] = Log Nr. [0...2] = Alarm priority [0...14] = Application area [0...4] = Error class [0...7] = Attributes [0...7] = Alarm status Fault state Fault transmission Damper position Volume flow 5) relative Balancing mode Opening direction Diff. pressure Volume flow 5) absolute For technical reasons, values for Vmin / Vmax need to be entered with two trailing “0” in ETS5, i.e. to get Vmin = 5%, enter “500%” in ETS5. The same applies for read-back values. For some group objects, alternative data point types (DPT) can be selected in ETS....
Open the catalog to page 7Siemens Building Technologies Power supply Function data Connection cables
Open the catalog to page 811 The documents can be downloaded from http://siemens.com/bt/download Siemens Building Technologies
Open the catalog to page 9Internal diagrams The VAV compact controller is supplied with two prewired connecting and communication cables. All interconnected devices must be connected to the same G0. G..B181.1E/KN The operating voltage at terminals G and G0 must comply with the requirements under SELV or PELV. Safety transformers with twofold insulation as per EN 61558 required; they must be designed to be on 100 % of the time. Siemens Building Technologies
Open the catalog to page 10Siemens Building Technologies
Open the catalog to page 1112 Pages
18 Pages
10 Pages
8 Pages
10 Pages
14 Pages
12 Pages
12 Pages
150 Pages
22 Pages
39 Pages
649 Pages
399 Pages
411 Pages
4 Pages
14 Pages
3 Pages
14 Pages
12 Pages
16 Pages
8 Pages
22 Pages
16 Pages
191 Pages
10 Pages
16 Pages
224 Pages
5 Pages