Gamma instabus
14Pages

{{requestButtons}}

Catalog excerpts

Gamma instabus - 1

Gamma instabus Technical product information Switching Actuators N 530, 6 AX Switching Actuators N 532, 10 AX Switching Actuators N 534, 16/20 AX Switching Actuators N 535, 16/20 AX • For switching capacitive, inductive and resistive loads • Maintenance-free terminals for connecting and looping through solid, stranded and fine-stranded conductors with conductor cross-sections from 0.5 to 2.5 mm2 • Switching status display with operating capability for each output to test for correct installation Functions with configuration with ETS • Control functions: o Switching with status message, logic gate, central switching, timed switching, night mode o Control value input for analogous values can be configured as an alternative to the switching input o Integrated 8-bit scene control and assign of each output to up to 8 scenes • Override functions: Manual ON, permanent OFF, locks, central override, forced control • Diagnostic functions: Counting of switching cycles with threshold monitoring of switching cycles, counting of operating hours with threshold monitoring of operating hours, status messages • Only for type N 535: load detection with load check threshold monitoring

Open the catalog to page 1
Gamma instabus - 2

Type overview Type Article number Characteristics Switching actuators N 530D31, N 532D31 und N 534D31 can switch four mutually independent groups of electrical consumers via four potential-free outputs. Switching actuators N 530D51, N 532D51, 534D51 und N 535D51 can switch eight mutually independent groups of electrical consumers via eight potential-free outputs. Switching actuators N 530D61, N 532D61 und N 534D61 can switch twelve mutually independent groups of electrical consumers via twelve potential-free outputs. The switching actuators can switch resistive loads (e.g. electric heater,...

Open the catalog to page 2
Gamma instabus - 3

The device is a rail-mounted device in N dimension for installation in arrangements and is installed on 35 mm rails as per standard IEC 60715. The switching actuator is connected to the bus connection with a bus terminal block. The power supply is supplied via the bus voltage (no additional power voltage is required). Every actuator output has a potential-free relay with switch position display. Via the relay, the switch position can be changed with a tool. Every actuator output has one terminal each for the supply voltage (rated operating voltage AC 230 V) and the switched load. The...

Open the catalog to page 3
Gamma instabus - 4

Position and function of the operating and display elements Example graphic: 8 load outputs *The description of positions 2 and 3 applies analogously for the corresponding contacts and switches of the other channels. Siemens Switzerland Ltd Building Technologies Division International Headquarters Theilerstrasse 1a CH-6300 Zug Update: http://www.siemens.com/gamma-td © Siemens Switzerland Ltd 2019 Subject to change

Open the catalog to page 4
Gamma instabus - 5

The following connection example shows the connection of loads, e.g. lamps, for switching on/off via the switch contacts of channels A, B, C, D, E and H. Maximum current via the load terminals < 20 A Example graphic: 8 load outputs Siemens Switzerland Ltd Building Technologies Division International Headquarters Theilerstrasse 1a CH-6300 Zug Update: http://www.siemens.com/gamma-td © Siemens Switzerland Ltd 2019 Subject to change

Open the catalog to page 5
Gamma instabus - 6

Siemens Switzerland Ltd Building Technologies Division International Headquarters Theilerstrasse 1a CH-6300 Zug © Siemens Switzerland Ltd 2019 Subject to change Update: http://www.siemens.com/gamma-td

Open the catalog to page 6
Gamma instabus - 7

Load detection (load check) (only type N 535) Environmental conditions Protection settings Siemens Switzerland Ltd Building Technologies Division International Headquarters Theilerstrasse 1a CH-6300 Zug © Siemens Switzerland Ltd 2019 Subject to change Update: http://www.siemens.com/gamma-td

Open the catalog to page 7
Gamma instabus - 8

Behavior with bus voltage failure/recovery In case of bus voltage failure, the current switch status and other values for each output are permanently stored. On bus voltage recovery, these values are restored. For each channel, the configured actions are also executed and, if applicable, new status values are reported. Behavior on unloading the application program After "unloading" the application program with the ETS, the unloaded device has no functions. Timer functions When configuring the device with ETS, one timer and night mode can be programmed. It is possible to set delayed...

Open the catalog to page 8
Gamma instabus - 9

Switch cycle and operating hours count To monitor use, with the right configuration it is possible to count and display the switch cycles and operating hours of the device. For switching actuators of type N 535, the counting of operating hours can be configured so that operating hours are only counted when there is an active current flow. Load current monitoring (only type N 535) For switching actuators of type N 535, the load check can optionally be measured and the status can be sent via the bus. The load check can also be monitored with regard to exceedance or falling short of load check...

Open the catalog to page 9
Gamma instabus - 10

Schematic design of a switching actuator channel The following diagram shows an example of the functions of the switching actuator or switching actuator with load detection in a logical context. Send status value Control value Switching Control value input Control functions Central switching Normal mode/ flashing Normal mode/flashing 8-bit scene control Flashing Night mode Timer period day mode Normal mode Timer (day) Timer (night) Timer period night mode Override functions Relay mode Normally closed/open Diagnostic functions Status switching Number of switch cycles Status number of...

Open the catalog to page 10
Gamma instabus - 11

Safety WARNING • The switching actuator should only be installed and put into operation by a certified electrician. • Ensure that the switching actuator can be activated. • Do not open the casing of the switching actuators. • For planning and construction of electric installations, the relevant guidelines, regulations and standards of the respective country are to be considered. Note on installation The switching actuators can be used for fixed installations in interior spaces, for installations in dry locations, within distribution boards or small casings with DIN rails EN 60715-TH35. Note...

Open the catalog to page 11

All SIEMENS Building Technology catalogs and technical brochures

  1. RDS110

    22 Pages

  2. PXC5.E003

    12 Pages

  3. PXC4.M16

    16 Pages

  4. QAF63.2-J

    8 Pages

  5. PXM30-1

    10 Pages

  6. PXC4.E16

    14 Pages

  7. A6V10575277

    16 Pages

  8. RRV934

    12 Pages

  9. WRI982

    12 Pages

  10. Catalog LV 51

    150 Pages

Archived catalogs