Technical Documentation "Installation, Mounting and Operating In- SVA-FF Fire Damper Disc Valve PERFORMANCE DATA USABILITY CERTIFICATE • General building supervisory approval (abZ) • Preventing the transmission of fire from floor SPECIAL FEATURES CLASSIFICATION AND STANDARD Classification K90-18017 Application Ventilation systems in accordance with DIN 18017-3 Fire prevention Low pressure loss Low volume level Sheet steel design with epoxy resin powder coating (standard colour: RAL 9010 white; other RAL colours are possible upon request) A relatively high air inlet ring prevents soiled edges SCHAKO | Ferdinand Schad KG Phone +49 (0) 7463-980-0 D-78600 Kolbingen www.SCHAKO.de | info@SCHAKO.de
Open the catalog to page 1
Fire Damper Disc Valve SVA-FF Technical documentation Table of Contents Construction subject to change No return possible
Open the catalog to page 2
Fire Damper Disc Valve SVA-FF Technical documentation Description DESCRIPTION The fire damper poppet valve SVA-FF is designed for installation in ventilation systems in accordance with DIN 18017-3. Besides, the fire damper poppet valve can also be mounted into systems in accordance with DIN 18017-3, for which the supply air is introduced through ducts. Its usage has been regulated by the general building supervisory approval (abZ) no. Z-41.3-674. Proper installation prevents spreading fire across floors. The fire damper poppet valves have fire resistance class K90-18017. The valve disc...
Open the catalog to page 3
Fire Damper Disc Valve SVA-FF Technical documentation Models and dimensions Nominal size Table 2: Dimensions of mounting frames (-ER) Available sizes Table 1: Available sizes of SVA-FF Replacement fusible link 70°C, size-dependent model When ordering, please state the nominal size of SVA-FF. Construction subject to change No return possible
Open the catalog to page 4
Fire Damper Disc Valve SVA-FF Technical documentation Installation details INSTALLATION DETAILS Installation Installation of fire damper poppet valve type SVA-FF. The mounting frame is fastened on the duct or pipe by means of rivets or tapping screws. The valve is fastened in the mounting frame by rotating it in such a way that the valve becomes clamped in the mounting frame. To set the amount of air flow or change the gap width "s", (see Figure 1 page 4) rotate the valve disc. Installation of the air ducts with application of a ceiling mortar x ≤ 1.5 m Suspension, allowed tensile stress...
Open the catalog to page 5
Fire Damper Disc Valve SVA-FF Technical documentation Installation details F90: W = min. 40 mm Figure 4: Detail A F90: W = min. 40 mm F30: W = min. 24 mm Detail A alternatively Figure 7: Detail C F90: W = min. 40 mm Figure 5: Detail A alternatively Figure 8: Dimensioning of firestop boards Detail B AS øRD W = section = nominal size (NG) = wall thickness 1.) Spiral duct or flexible sheet steel duct 2.) The mounting frame is riveted from the inside to the standard spiral duct using steel rivets 3x6 3.) Mortar MG II-III or plaster mortar 4.) Non-fire-resistant suspended ceiling 5.) Shut-off...
Open the catalog to page 6
Fire Damper Disc Valve SVA-FF Technical documentation Installation details Installation in or outside of ventilation shafts x ≤ 1.5 m Suspension, allowed tensile stress max. 6 N/mm² Figure 9: Installation in or outside of ventilation shafts Detail E Construction subject to change No return possible = section = nominal size (NG) = wall thickness 1.) Spiral duct or flexible sheet steel duct 2.) The mounting frame is riveted from the inside to the standard spiral duct using steel rivets 3x6 3.) Mortar MG II-III or plaster mortar 4.) Non-fire-resistant suspended ceiling 5.) Shut-off damper 6.)...
Open the catalog to page 7
Fire Damper Disc Valve SVA-FF Technical documentation Technical data TECHNICAL DATA Pressure loss and noise level SVA-FF 100 Diagram 1: Pressure loss and noise level of SVA-FF 100 Diagram 3: Pressure loss and noise level of SVA-FF 150/160 Diagram 2: Pressure loss and noise level of SVA-FF 125 Diagram 4: Pressure loss and noise level of SVA-FF 200 Construction subject to change No return possible
Open the catalog to page 8
Sound power level Table 4: Insertion loss The average values of the insertion from the duct to the room for ceiling installation are shown in the above table. Construction subject to change No return possible
Open the catalog to page 9
Fire Damper Disc Valve SVA-FF Technical documentation Order code ORDER CODE OF SVA-FF EXAMPLE SVAFF-200-9010 Fire damper poppet valve type SVA-FF | Nominal size = 200 mm | 9010 = coating RAL 9010 ORDER DETAILS 01 - TYPE SVAFF = Fire damper poppet valve SVA-FF 02 - NOMINAL SIZE 100 - 125 - 150 - 160 - 200 in mm - always three digits 03 - PAINT 9010 = RAL colour white (standard) xxxx = RAL colour on request (always with 4 digits) SPECIFICATION TEXTS Fire damper poppet valve for mounting into ventilation systems in accordance with DIN 18017-3, or ventilation systems according to DIN 18017-3,...
Open the catalog to page 10
Fire Damper Disc Valve SVA-FF Technical documentation Service SERVICE Checking the function, cleaning, repair Polluted and damp air can impair the continuous operational safety. This is why, after commissioning the ventilation installation, all shut-off devices must be subjected to a functional test at a six-month interval according to section 5 of the general building supervisory approval Z-41.3-674. If two consecutive functional tests show no defects, the shut-off devices only have to be tested at a yearly interval. • Check connection opening and mounting frame (pos. 1) for soiling and...
Open the catalog to page 11
Fire Damper Disc Valve SVA-FF Technical documentation Service SCHAKO Ferdinand Schad KG Steigstrasse 25-27 D-78600 Kolbingen Phone: +49- (0)7463 / 980-0 Fax: +49- (0)7463 / 980-200 E-Mail: info@schako.de Sample Web: www.schako.de Functional test protocol for______________ _ Cons. No. Usability certificate: Series: _ Release device: Construction subject to change No return possible
Open the catalog to page 12
Fire Damper Disc Valve SVA-FF Technical documentation Service SCHAKO Ferdinand Schad KG Steigstrasse 25-27 D-78600 Kolbingen Phone: +49- (0)7463 / 980-0 Fax: +49- (0)7463 / 980-200 E-mail: info@schako.de Web: www.schako.de Sample Functional test protocol for____________________ Cons. No. ____________________ Defects found during the test on: Defects found during the test on: Defects found during the test on: Defects found during the test on: Construction subject to change No return possible
Open the catalog to page 13All SCHAKO KG catalogs and technical brochures
-
CNVA
32 Pages
-
KGF Compact Filter Grille
9 Pages
-
AUDIX
2 Pages
-
DISA
4 Pages
-
UC-OH²
2 Pages
-
IGA
2 Pages
-
CDD
2 Pages
-
FBS
18 Pages
-
MINOPAB
6 Pages
-
PIL
23 Pages
-
MWS / MWK
23 Pages
-
ERK-SO
43 Pages
-
BKSYS
18 Pages
-
MINODSA
6 Pages
-
DKA
6 Pages
-
LAQ
11 Pages
-
VMPR/VMPQ
29 Pages
-
BKA-EN
79 Pages
-
CPL
15 Pages
-
AUDIX®
25 Pages
-
VREX
26 Pages
-
VQEX
17 Pages
-
VPEX
18 Pages
-
SVA-FS
11 Pages
-
NRWG
22 Pages
-
COMBIDSC
26 Pages
-
DSCXL
17 Pages
-
DSCU
18 Pages
-
DSCPL
16 Pages
-
DSCP
15 Pages
-
DSC
37 Pages
-
DO
10 Pages
-
VRAQ
46 Pages
-
UEKU
6 Pages
-
UEK
6 Pages
-
SS-K
6 Pages
-
DQJP
9 Pages
-
VOLKOM
6 Pages
-
DQJ
38 Pages
-
ALPETY
16 Pages
-
CTT
23 Pages
-
STV
8 Pages
-
KWB
19 Pages
-
GREENKIT
20 Pages
-
FKU
31 Pages
-
FKF
29 Pages
-
SGA
5 Pages
-
DBB
27 Pages
-
TVO
8 Pages
-
AL
23 Pages
-
RF Return air filter grille
7 Pages
-
NBS
34 Pages
-
MKAR_MKAQ
13 Pages
-
KF
4 Pages
-
JK
16 Pages
-
HK
16 Pages
-
Lint Separator FLARE
13 Pages
-
FLAQ
11 Pages
-
FKW
28 Pages
-
FG
14 Pages
-
ERK-MB
38 Pages
-
DISA-H
34 Pages
-
DISA-360
32 Pages
-
DISA-300
51 Pages
-
CNV
29 Pages
-
BKP-EN Fire damper
40 Pages
-
BKA-UE
35 Pages
-
BAK-250 Fire protection unit
17 Pages
-
BAK-240
16 Pages
-
Aquaris-Silent
38 Pages
-
Aquaris_KWB
20 Pages
-
DISA-W
43 Pages
-
PILB/PILBR
33 Pages
-
DAV
19 Pages
-
4DE
18 Pages
-
4DF
13 Pages
-
DQC
16 Pages
-
DQDL
16 Pages
-
IDA
21 Pages
-
IKA
23 Pages
-
ZMD
17 Pages
-
DQF
15 Pages
-
DQJF
12 Pages
-
DQJA/DQJR
10 Pages
-
DQJSL
17 Pages
-
DQJSLC
17 Pages
-
DHV
18 Pages
-
DSARR
7 Pages
-
QA
30 Pages
-
PUSH
23 Pages
-
WQA
12 Pages
-
DSX-XXL
23 Pages
-
AUDIX®-ÜSG
13 Pages
-
SIA
7 Pages
-
SAR/SAQ/SARP
13 Pages
-
WDA
32 Pages
-
KGRR
17 Pages
-
DBBRR
11 Pages
-
WGARR
7 Pages
-
WGA
29 Pages
-
DKAPPs
6 Pages
-
EBE/EBP
52 Pages
-
VRAPPs
20 Pages
-
VRAR
52 Pages
-
MAK
15 Pages
-
DISA-Family
4 Pages
-
RMS
11 Pages
-
EasyBus
24 Pages
-
TSR
5 Pages
-
RS-F
7 Pages
-
RS
15 Pages
-
VLV
31 Pages
-
VARS
26 Pages
-
VAQS
19 Pages
-
VAS
26 Pages
-
PIANO
27 Pages
-
MBM
10 Pages
-
MBE/MBP
27 Pages
-
DKG
6 Pages
-
ALAS-P
5 Pages
-
ALAS-F 125
6 Pages
-
ALAS
10 Pages
-
ALA-SO
4 Pages
-
ALA-R
4 Pages
-
ALA
4 Pages
-
LL
7 Pages
-
RR-Complete
41 Pages
-
DBBR
6 Pages
-
PA
32 Pages
-
LK
12 Pages
-
IB-R
15 Pages
-
IB-Q
21 Pages
-
KG
19 Pages
-
BSG
19 Pages
-
DSX-XXL-W
25 Pages
-
AUDIX®-AW
20 Pages
-
DSX
25 Pages
-
MINODSX
6 Pages
-
MINODSA
6 Pages
-
DSA
15 Pages
-
COMBIPIL
11 Pages
-
COMBIDQJ
11 Pages
-
MINOPAB
6 Pages
-
BDA
11 Pages
-
SPB
10 Pages
-
CULTRA-Studioline
24 Pages
-
DISA-H
34 Pages
-
DISA-360
32 Pages
-
DISA-300
51 Pages
-
AQUARIS SILENT
38 Pages
-
NBS
24 Pages
-
CNV
29 Pages
-
CNVA
32 Pages
-
JK-LP/JK-LU
15 Pages
-
HKP / HKU
16 Pages
-
FKW
16 Pages
-
FLARE
13 Pages
-
RF
7 Pages
-
KGF
9 Pages
-
SVA-FF
8 Pages
-
BKA-Ü
35 Pages
-
BSK-RPR
60 Pages
-
BKP-EN
40 Pages
-
BAK-240
6 Pages
-
BAK-250
14 Pages
-
KF
4 Pages