RMS
1 /11Pages

RMS

RMS
1 /11Pages

Catalog excerpts

RMS-2

09/11 - 2 Construction subject to change. Version: 27.03.2019 No return possible!

 Open the catalog to page 2
RMS-3

Smoke detection system RMS Description Industrial property rights owned by SCHAKO: - Patent: DE 199 51 403 A1 - Registered utility model: 20023533.8 - Patent: EP 122 4641 - VdS Approval: G209206 External monitoring is done by the VdS Schadensverhütung GmbH Köln (VdS Damage Prevention Branch, Cologne) The SCHAKO smoke detection system consists of the smoke detector RMSII-L and the relay module RM V4.00 and is used in places where, at the earliest possible stage of a fire (upon occurrence of cold smoke of < 72°), triggering and switching operations are to be controlled automatically. It can be...

 Open the catalog to page 3
RMS-4

Smoke detection system RMS Installation arrangement and mounting The smoke detector must be fitted free of vibration if possible. When charged with steam, disinfectant, dust, soot (exhaust gases) or dew, an alarm or fault message is triggered. Assembly in ducts 1. Establish smoke detector position (not in the inspection opening of the fire damper), and mark the middle. 2. Cut out a hole of 120 mm in diameter. 3. Drill mounting holes (only when installed on site in the ventilation duct). 4. Insert the delivered insulating sleeves into the mounting holes. 5. Fit smoke detector with mounting frame...

 Open the catalog to page 4
RMS-5

Smoke detection system RMS Construction Smoke detector base - Polycarbonate Connecting cable - 2.0 m with 9-pin Sub D plug. The 9-pin Sub D terminal for the electric supply and trigger lines is located inside the base. Individual display - LED on duct exterior Mounting frame - Sheet steel, with seal Accessories Assembly part type EBT - for installation flush with the duct, made of galvanised sheet steel. - Housing leakage according to DIN EN 1751, class B, at a duct pressure of up to 1000 Pa. Assembly part (-REBT / -REBTF) - for installation in round ducts, made of galvanised sheet steel. - Housing...

 Open the catalog to page 5
RMS-6

Smoke detection system RMS Accessories with assembly part (-EBT), for fire damper installation - Installation in duct topside - Installation in duct side wall The dimension L depends on the height H (mm). The smoke detector must always be assembled in the assembly part type EBT on the operator side (trigger device, drive) (not in the inspection opening of the fire damper). Construction subject to change.

 Open the catalog to page 6
RMS-7

Smoke detection system RMS with assembly part (-REBT), for installation in round ducts with assembly part (-REBTF), for installation in round ducts - without flange, with rubber lip seal. - with flange on both sides, to EN 12220. Available sizes REBT / REBTF 1.) painted black matt on the inside Construction subject to change.

 Open the catalog to page 7
RMS-8

Smoke detection system RMS Technical dataSmoke detection system (-RMS) Operating voltage: Connection assignment of the 9-pin SUB-D plug: The relays drop off when an alarm / a fault or a power cut occurs. 09/11 - 8 Version: 27.03.2019 Construction subject to change.

 Open the catalog to page 8
RMS-9

Smoke detection system RMSCircuit diagram of relay module 1.) Smoke detectors 10.) AMP plug for 24V AC/DC actuators (max. 10 VA) 11.) Selector switch 1, e.g., actuator 12.) Selector switch 2, e.g., light 13.) Contact load of the selector switches 14.) Spring return actuator 24 V AC/DC for fire damper. SCHAKO product or external product (for the technical data, please refer to the motor data sheet) 15.) Spring return actuator 24 V AC/DC / 230 V AC SCHAKO product or external product (optional) (for the technical data, please refer to the motor data sheet) 16.) Magnetic clamp / pneumatic valve (optional)...

 Open the catalog to page 9
RMS-10

Smoke detection system RMS Maintenance / Inspection Maintenance of the smoke detection device for fire and smoke dampers must be carried out once a year or after a fault message, due to contamination. Note Installation and wiring must be carried out by authorised electricians only. The agreed regulations of the technic, safety and accident prevention regulations as well as the VDE guidelines, regulations of the local EVU's and the wiring instructions and connection plans of the manufacturer, must be adhered to when installing, wiring and commissioning. When wiring the junction boxes, make sure...

 Open the catalog to page 10
RMS-11

Smoke detection system RMS Order details Specification texts Smoke detection system Type RMSΙΙ-L Accessories: Assembly part for duct installation -EBT Relay module -RM incl. RST Assembly part for duct connection without flange with rubber lip seal -REBT with flange, on both sides according to EN 12220 -REBTF Order example RMSΙΙ-L-RM Unless stated otherwise, the thick-frame model will be delivered! Smoke detection system type RMS, with annual maintenance, for installation flush with the duct or fire damper installation with assembly part type EBT (extra charge), with maintenance cover. Consisting...

 Open the catalog to page 11

All SCHAKO KG catalogs and technical brochures

  1. CNVA

    32  Pages

  2. FKW (2025)

    28  Pages

  3. AUDIX

    2  Pages

  4. DISA

    4  Pages

  5. UC-OH²

    2  Pages

  6. IGA

    2  Pages

  7. CDD

    2  Pages

  8. FBS

    18  Pages

  9. PIL

    23  Pages

  10. MWS / MWK

    23  Pages

  11. ERK-SO

    43  Pages

  12. DSCXL

    17  Pages

  13. DSCPL

    16  Pages

  14. BKSYS

    18  Pages

  15. MINODSA

    6  Pages

  16. DKA

    6  Pages

  17. LAQ

    11  Pages

  18. VMPR/VMPQ

    29  Pages

  19. DSCU

    18  Pages

  20. DSCP

    15  Pages

  21. DQJP

    9  Pages

  22. BKA-EN

    79  Pages

  23. CPL

    15  Pages

  24. AUDIX®

    25  Pages

  25. VREX

    26  Pages

  26. VQEX

    17  Pages

  27. VPEX

    18  Pages

  28. SVA-FS

    11  Pages

  29. NRWG

    22  Pages

  30. COMBIDSC

    26  Pages

  31. DSC

    37  Pages

  32. DO

    10  Pages

  33. VRAQ

    46  Pages

  34. UEKU

    6  Pages

  35. UEK

    6  Pages

  36. SS-K

    6  Pages

  37. VOLKOM

    6  Pages

  38. STV

    8  Pages

  39. DQJ

    38  Pages

  40. ALAS-F 125

    6  Pages

  41. ALPETY

    16  Pages

  42. CTT

    23  Pages

  43. KWB

    19  Pages

  44. GREENKIT

    20  Pages

  45. SVA-FF

    15  Pages

  46. FKU

    31  Pages

  47. FKF

    29  Pages

  48. SGA

    5  Pages

  49. DBB

    27  Pages

  50. TVO

    8  Pages

  51. AL

    23  Pages

  52. NBS

    34  Pages

  53. MKAR_MKAQ

    13  Pages

  54. KF

    4  Pages

  55. JK

    16  Pages

  56. HK

    16  Pages

  57. FLAQ

    11  Pages

  58. FG

    14  Pages

  59. ERK-MB

    38  Pages

  60. DISA-H (2025)

    34  Pages

  61. DISA-360

    32  Pages

  62. DISA-300

    51  Pages

  63. CNV

    29  Pages

  64. BKA-UE

    35  Pages

  65. BAK-240

    16  Pages

  66. Aquaris-Silent

    38  Pages

  67. Aquaris_KWB

    20  Pages

  68. DISA-W

    43  Pages

  69. BDA

    11  Pages

  70. PILB/PILBR

    33  Pages

  71. DAV

    19  Pages

  72. 4DE

    18  Pages

  73. 4DF

    13  Pages

  74. DQC

    16  Pages

  75. DQDL

    16  Pages

  76. IDA

    21  Pages

  77. IKA

    23  Pages

  78. ZMD

    17  Pages

  79. DQF

    15  Pages

  80. DQJF

    12  Pages

  81. DQJA/DQJR

    10  Pages

  82. DQJSL

    17  Pages

  83. DQJSLC

    17  Pages

  84. DHV

    18  Pages

  85. COMBIDQJ

    11  Pages

  86. COMBIPIL

    11  Pages

  87. DSA

    15  Pages

  88. DSARR

    7  Pages

  89. QA

    30  Pages

  90. PUSH

    23  Pages

  91. WQA

    12  Pages

  92. DSX

    25  Pages

  93. DSX-XXL

    23  Pages

  94. AUDIX®-AW

    20  Pages

  95. AUDIX®-ÜSG

    13  Pages

  96. DSX-XXL-W

    25  Pages

  97. SIA

    7  Pages

  98. SAR/SAQ/SARP

    13  Pages

  99. WDA

    32  Pages

  100. BSG

    19  Pages

  101. KG

    19  Pages

  102. IB-Q

    21  Pages

  103. IB-R

    15  Pages

  104. LK

    12  Pages

  105. PA

    32  Pages

  106. DBBR

    6  Pages

  107. KGRR

    17  Pages

  108. DBBRR

    11  Pages

  109. WGARR

    7  Pages

  110. WGA

    29  Pages

  111. ALA

    4  Pages

  112. ALA-R

    4  Pages

  113. ALA-SO

    4  Pages

  114. ALAS

    10  Pages

  115. ALAS-P

    5  Pages

  116. DKAPPs

    6  Pages

  117. EBE/EBP

    52  Pages

  118. DKG

    6  Pages

  119. MBE/MBP

    27  Pages

  120. PIANO

    27  Pages

  121. VAS

    26  Pages

  122. VAQS

    19  Pages

  123. VARS

    26  Pages

  124. VRAPPs

    20  Pages

  125. VRAR

    52  Pages

  126. MAK

    15  Pages

  127. RS-F

    7  Pages

  128. RS

    15  Pages

  129. EasyBus

    24  Pages

  130. DISA-Family

    4  Pages

  131. TSR

    5  Pages

  132. VLV

    31  Pages

  133. MBM

    10  Pages

  134. LL

    7  Pages

  135. RR-Complete

    41  Pages

  136. MINODSX

    6  Pages

  137. SPB

    10  Pages

  138. DISA-H

    34  Pages

  139. AQUARIS SILENT

    38  Pages

  140. NBS

    24  Pages

  141. JK-LP/JK-LU

    15  Pages

  142. HKP / HKU

    16  Pages

  143. FKW

    16  Pages

  144. FLARE

    13  Pages

  145. RF

    7  Pages

  146. KGF

    9  Pages

  147. SVA-FF

    8  Pages

  148. BKA-Ü

    35  Pages

  149. BSK-RPR

    60  Pages

  150. BKP-EN

    40  Pages

  151. BAK-240

    6  Pages

  152. BAK-250

    14  Pages

Archived catalogs

  1. DISA-B

    32  Pages

  2. DISA-601

    41  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.