Mixing Box Model MBE / MBP Description The mixing box type MBE/MBP consists of a housing with two round connection pipes and an integrated silencer unit for reducing flow generated noise. Two volumetric flow controllers are integrated, in order to allow the volumetric flow in ducts to be kept constant or variable or to be regulated using positive control Vmin, Vmax or "CLOSED". It is used in two-duct air-conditioning systems, in which control and mixing can be carried out electrically or pneumatically, as desired. The measuring sensor used in the cold-air connection pipe and in the silencer...
Open the catalog to page 3
Mixing Box Model MBE / MBP Regulation Mixing boxes are used in twin-duct air-conditioning systems. The unit mixes cold and hot air in such a way that the difference between the highest and the lowest temperature at the outlet of the device (low-pressure side) is less than 10%. Two control circuits independent of one another are formed, which allow the supply air to be controlled at a constant or variable flow rate. The differential pressure sensor for the cold air, with a measuring cross in the connection pipe (1), together with the cold air controller (2), forms a control circuit which is...
Open the catalog to page 4
Installation Installation information To avoid unnecessary controller errors, the min. distances according to the following table / drawings must be observed. For combinations of several connection pieces or pieces with fire dampers or silencers, the larger minimum distances must be observed. Distance to other connection pieces (e.g. branching piece, reduction piece, T-junction, etc.) Construction Housing - Galvanised sheet steel - abrasion-resistant up to a duct velocity of 20 m/s - Lined with mineral wool, perforated sheet cover. Damper leaf seal - made of PUR, silicone-free - for...
Open the catalog to page 5
Mixing Box Model MBE / MBP Models and dimensions Dimensions MBE Inspection opening Inspection opening Rivet nut M8 Version: 26.08.2016 No return possible!
Open the catalog to page 6
Mixing Box Model MBE / MBP Dimensions of accessories Acoustic cladding (-DS) and additional silencer (-ZS) Additional silencer Acoustic cladding Section A-A shown without connection frame Rubber lip seal (-GD) Detail X Section C-C shown without connection frame Version: 26.08.2016 No return possible!
Open the catalog to page 7
ICHAK#Mixing Box Model MBE / MBP Technical data Volumetric flow range for MBE (constant or min/max) Attention, the following specifications are important for programming the volumetric flow controllers: - This table merely specifies the complete measuring range of the controller (volumetric flow range) - If the customer wants a calibration curve different from 12 m/ s, it must be specified! - When the air volume drops below the Vmin shown in the tables, the correct functioning of the volumetric flow controller is no longer guaranteed! - If only one air volume is specified in the order (as...
Open the catalog to page 8
Mixing Box Model MBE / MBP Sound values MBE / MBP, without acoustic cladding Supply air Return air Supply air flow generated noise without silencer Supply air flow generated noise with silencer Radiated noise of supply air without acoustic cladding Radiated noise of supply air with acoustic cladding Flow generated noise in round duct for supply air Insertion loss as the difference of the sound power levels measured with and without the mixing box. Construction subject to change.
Open the catalog to page 9
Mixing Box Model MBE / MBP Flow generated noise with / without additional silencer (-ZS) NW Construction subject to change.
Open the catalog to page 10
Mixing Box Model MBE / MBPRadiated noise with / without acoustic cladding (-DS) Construction subject to change.
Open the catalog to page 11
Mixing Box Model MBE / MBP Technical data of the control components Measured value collection and control function The measured value collection is carried out via a flow-favouring double measuring cross. The measuring openings are distributed over the measuring cross according to the median line method. The pressure differential formed on the measuring cross is determined by means of a dynamic or static measuring sensor. The measured values are averaged to give an average value which represents a measuring quantity for the volumetric flow. The controller compares the actual value signal...
Open the catalog to page 12
MP bus activation with integrated switch Circuit diagrams Circuit diagram standard controller Compact controller Belimo make LMV-D3-MP VAV with analogue command signal VAV with lock (CLOSED) Mode 2-10V DC _MP / actual value signal 0...10V / 2...10V -1 VAV command signal "0...10V Switchover CLOSED / -VAV operation MP / actual value sig-0...10V / 2...10V Lock mode (CLOSED) In the 2 - 10 V mode, the following function can be carried with a 0 - 10 V signal: **Attention: Controller/DDC must be able to pull the command signal to 0 V. Cable designations Version: 26.08.2016 Construction subject to...
Open the catalog to page 13
CAV operation / positive contacts CAV function for MV-D3-MP CAV - V Mode setting Signal Function Damper CLOSED Vmin...Vmax CAV - Vmin Damper OPEN Contact closed, function active Contact closed, function active, in mode 2 ...10 V only Contact open * not available for DC 24 V supply Note: Please ensure mutual locking Construction subject to change.
Open the catalog to page 14
Mixing Box Model MBE / MBPLED table of functions for LMV-D3-MP Application Description / action LED pattern Adaptation Address Status display - 24V power supply o.k. - VAV-Compact ready for operation Synchronisation started by: a) Operating / service unit b) Manual trigger device at the VAV-Compact c) Power ON behaviour Adaptation started by: a) Operating / service unit b) Key on the VAV-Compact a) Press both keys «Adaptation» & «Address» simultaneously b) VAV service will be activated: - until 24V supply is switched off - until both keys are pressed again - after 2 hours have passed Damper...
Open the catalog to page 15
Two-stage volumetric flow rate control Universal controller Belimo make VRD3-SO Connection diagram VRD3-SO Positive control VRD3-SO Two-stage volumetric flow rate control VRD3-SO i AC 24 V - ■■ DC 24 V Overview control signals / functions Signal terminal / Function *) requires AC 24 V power supply 08/20 - 16 Version: 26.08.2016 Construction subject to change. No return possible!
Open the catalog to page 16All SCHAKO KG catalogs and technical brochures
-
CNVA
32 Pages
-
KGF Compact Filter Grille
9 Pages
-
AUDIX
2 Pages
-
DISA
4 Pages
-
UC-OH²
2 Pages
-
IGA
2 Pages
-
CDD
2 Pages
-
FBS
18 Pages
-
MINOPAB
6 Pages
-
PIL
23 Pages
-
MWS / MWK
23 Pages
-
ERK-SO
43 Pages
-
BKSYS
18 Pages
-
MINODSA
6 Pages
-
DKA
6 Pages
-
LAQ
11 Pages
-
VMPR/VMPQ
29 Pages
-
BKA-EN
79 Pages
-
CPL
15 Pages
-
AUDIX®
25 Pages
-
VREX
26 Pages
-
VQEX
17 Pages
-
VPEX
18 Pages
-
SVA-FS
11 Pages
-
NRWG
22 Pages
-
COMBIDSC
26 Pages
-
DSCXL
17 Pages
-
DSCU
18 Pages
-
DSCPL
16 Pages
-
DSCP
15 Pages
-
DSC
37 Pages
-
DO
10 Pages
-
VRAQ
46 Pages
-
UEKU
6 Pages
-
UEK
6 Pages
-
SS-K
6 Pages
-
DQJP
9 Pages
-
VOLKOM
6 Pages
-
DQJ
38 Pages
-
ALPETY
16 Pages
-
CTT
23 Pages
-
STV
8 Pages
-
KWB
19 Pages
-
GREENKIT
20 Pages
-
FKU
31 Pages
-
FKF
29 Pages
-
SGA
5 Pages
-
DBB
27 Pages
-
TVO
8 Pages
-
AL
23 Pages
-
SVA-FF
15 Pages
-
RF Return air filter grille
7 Pages
-
NBS
34 Pages
-
MKAR_MKAQ
13 Pages
-
KF
4 Pages
-
JK
16 Pages
-
HK
16 Pages
-
Lint Separator FLARE
13 Pages
-
FLAQ
11 Pages
-
FKW
28 Pages
-
FG
14 Pages
-
ERK-MB
38 Pages
-
DISA-H
34 Pages
-
DISA-360
32 Pages
-
DISA-300
51 Pages
-
CNV
29 Pages
-
BKP-EN Fire damper
40 Pages
-
BKA-UE
35 Pages
-
BAK-250 Fire protection unit
17 Pages
-
BAK-240
16 Pages
-
Aquaris-Silent
38 Pages
-
Aquaris_KWB
20 Pages
-
DISA-W
43 Pages
-
PILB/PILBR
33 Pages
-
DAV
19 Pages
-
4DE
18 Pages
-
4DF
13 Pages
-
DQC
16 Pages
-
DQDL
16 Pages
-
IDA
21 Pages
-
IKA
23 Pages
-
ZMD
17 Pages
-
DQF
15 Pages
-
DQJF
12 Pages
-
DQJA/DQJR
10 Pages
-
DQJSL
17 Pages
-
DQJSLC
17 Pages
-
DHV
18 Pages
-
DSARR
7 Pages
-
QA
30 Pages
-
PUSH
23 Pages
-
WQA
12 Pages
-
DSX-XXL
23 Pages
-
AUDIX®-ÜSG
13 Pages
-
SIA
7 Pages
-
SAR/SAQ/SARP
13 Pages
-
WDA
32 Pages
-
KGRR
17 Pages
-
DBBRR
11 Pages
-
WGARR
7 Pages
-
WGA
29 Pages
-
DKAPPs
6 Pages
-
EBE/EBP
52 Pages
-
VRAPPs
20 Pages
-
VRAR
52 Pages
-
MAK
15 Pages
-
DISA-Family
4 Pages
-
RMS
11 Pages
-
EasyBus
24 Pages
-
TSR
5 Pages
-
RS-F
7 Pages
-
RS
15 Pages
-
VLV
31 Pages
-
VARS
26 Pages
-
VAQS
19 Pages
-
VAS
26 Pages
-
PIANO
27 Pages
-
MBM
10 Pages
-
DKG
6 Pages
-
ALAS-P
5 Pages
-
ALAS-F 125
6 Pages
-
ALAS
10 Pages
-
ALA-SO
4 Pages
-
ALA-R
4 Pages
-
ALA
4 Pages
-
LL
7 Pages
-
RR-Complete
41 Pages
-
DBBR
6 Pages
-
PA
32 Pages
-
LK
12 Pages
-
IB-R
15 Pages
-
IB-Q
21 Pages
-
KG
19 Pages
-
BSG
19 Pages
-
DSX-XXL-W
25 Pages
-
AUDIX®-AW
20 Pages
-
DSX
25 Pages
-
MINODSX
6 Pages
-
MINODSA
6 Pages
-
DSA
15 Pages
-
COMBIPIL
11 Pages
-
COMBIDQJ
11 Pages
-
MINOPAB
6 Pages
-
BDA
11 Pages
-
SPB
10 Pages
-
CULTRA-Studioline
24 Pages
-
DISA-H
34 Pages
-
DISA-360
32 Pages
-
DISA-300
51 Pages
-
AQUARIS SILENT
38 Pages
-
NBS
24 Pages
-
CNV
29 Pages
-
CNVA
32 Pages
-
JK-LP/JK-LU
15 Pages
-
HKP / HKU
16 Pages
-
FKW
16 Pages
-
FLARE
13 Pages
-
RF
7 Pages
-
KGF
9 Pages
-
SVA-FF
8 Pages
-
BKA-Ü
35 Pages
-
BSK-RPR
60 Pages
-
BKP-EN
40 Pages
-
BAK-240
6 Pages
-
BAK-250
14 Pages
-
KF
4 Pages