Technical Documentation "Installation, Mounting and Operating Instructions" BKP-EN Fire damper Fig.: BKA-EN with B10 drive USABILITY CERTIFICATES PERFORMANCE DATA • Performance Reliability Certificate according to EU-Bau PVO 0761 - CPR - 0350 • Declaration of Performance 09-23-DoP-BKP-EN-2013-11-01 • For automatic locking of fire lobbies • For use or connection of a smoke release device with abZ (e.g. SCHAKO smoke detection system RMS) in connection with suitable release devices (e.g. spring return actuator) • Classification according to EN 13501-3, depending on the mounting situation EI 90(120) (ve, ho iOo) S • Product standard EN 15650 • Test standard EN 1366-2 ATEX version available (at an extra charge) Extensive uses and applications Large free cross-sections For optimum integration into the building control system via the SCHAKO EasyBus signalling and switching bus system or the SCHAKO BKSYS fire damper mini-controller SCHAKO | Ferdinand Schad KG Phone +49 (0) 7463-980-0 D-78600 Kolbingen www.SCHAKO.de | info@SCHAKO.de
Open the catalog to page 1
Fire Damper Model BKP-EN Technical documentation Table of Contents Construction subject to change. No return possible!
Open the catalog to page 2
Fire Damper Model BKP-EN Technical documentation Description DESCRIPTION Fire dampers built into ventilation ducts (air-conditioning systems) are used for the automatic locking of fire lobbies. The fire damper BKP-EN conforms to EN 15650, EN 13501-3 and EN 1366-2. The BKP-EN has been tested according to EN 1366-2 in compliance with Declaration of Performance no. 09-23-DoP-BKPEN-2013-11-01. It has the Performance Reliability Certificate according to EU-Bau PVO 0761-CPR-0350. Its category according to EN 13501-3 is depending on the mounting situation EI 90(120) (ve, ho i↔o) S. According to...
Open the catalog to page 3
Fire Damper Model BKP-EN Technical documentation Models and dimensions MODELS AND DIMENSIONSDimensions 1 Housing 2 Damper blade 3 Hand lever 4 Locking profile 5 Trigger device 6 Fusible link 7 Inspection opening (arranged at bottom) from B > 200, for B < 200 no inspection opening possible. x = B/2 200 > B < 600 or x ~ 125 mm ^ B > 600 y ~ 100 mm from the connection flange 8 Drive unit 9 Profile CW 50/50/0.6 (with wall thickness = 100 mm, for larger wall thicknesses, the profiles must be adapted accordingly). 10 Profile UW 50/40/0.6 (with wall thickness = 100 mm, for larger wall thicknesses,...
Open the catalog to page 4
Fire Damper Model BKP-EN Technical documentation Models and dimensions • Housing length L = 330 mm. • All heights and widths which can be combined are available! • Trigger device always on H side • Inspection opening always on B side (bottom) • Intermediate sizes on request "a" = 50 mm: Minimum distance between the front edge of the open damper blade and the finishing protective grating (ASG), the flexible spigot (FS) or the duct connection spigot (RS). SCHAKO ASG/VT/FS/RS: Flange holes suitable for The fire damper type BKP-EN is supplied with front side fitted corner long holes for M8...
Open the catalog to page 5
Fire Damper Model BKP-EN Technical documentation Models and dimensions Use be exposed to direct effects of the weather and must not be stored below -40 °C or above 50 °C. The fire damper type BKP-EN can be fitted as shown in the following table. The BKP-EN may also be installed in walls or ceilings of a lower fire resistance class. In this case, the BKP-EN has the same fire resistance class as the wall or ceiling. 1) Installation only in connection with a concrete base still to be made on site. Tab. 3: Usability • During mounting or installation, there is a risk of injuries. To avoid any...
Open the catalog to page 6
Fire Damper Model BKP-EN Technical documentation Installation details INSTALLATION DETAILS Installation positions Installation in solid walls Installation in solid walls (shaft walls, shafts, ducts and fire walls) made of, for example, concrete, masonry according to EN 1996 or DIN 1053; solid plaster wall boards according to EN 12859 or DIN 18163; apparent density ≥ 450 kg/m³ and wall thickness W ≥ 100 mm. On the non-operating side, fastening materials (e.g. screws, press-in nuts, etc.) must be provided for mounting duct components prior to installation of the BKP-EN. Alternatively,...
Open the catalog to page 7
Fire Damper Model BKP-EN Technical documentation Installation details Installation in solid ceilings Installation in solid ceilings made, for example, of concrete, aerated concrete, apparent density ≥ 500 kg/m³ and ceiling thickness D ≥ 125 mm. On the non-operating side, fastening materials (e.g. screws, press-in nuts, etc.) must be provided for mounting duct components prior to installation of the BKP-EN. Alternatively, extension pieces (on site or as accessories, e.g. SCHAKO type VT) can be mounted. Installation with complete mortar lining (the circumferential gaps "s" must be...
Open the catalog to page 8
Fire Damper Model BKP-EN Technical documentation Installation details Installation with vertical concrete base on solid ceilings Vertical installation on solid ceilings made, for example, of concrete, aerated concrete, apparent density ≥ 500 kg/m³ and ceiling thickness D ≥ 125 mm. Construction of a circumferential, straight reinforced concrete base (concrete grade: C20/25; concrete cover ≥ 35 mm; reinforcement: concrete steel BSt500S concrete steel mats B500A). The base must be constructed circumferentially with a wall thickness of at least 100 mm, measured from the housing of the fire...
Open the catalog to page 9
Fire Damper Model BKP-EN Technical documentation Installation details Installation in lightweight partition walls with metal posts and panelling on both sides Installation in lightweight partition walls with metal posts and panelling on both sides (gypsum-bonded wall boards; wall thickness W≥ 100 mm) as classified according to EN 13501-2 or comparable national standards. On the non-operating side, fastening materials (e.g. screws, press-in nuts, etc.) must be provided for mounting duct components prior to installation of the BKP-EN. Alternatively, extension pieces (on site or as...
Open the catalog to page 10All SCHAKO KG catalogs and technical brochures
-
CNVA
32 Pages
-
KGF Compact Filter Grille
9 Pages
-
AUDIX
2 Pages
-
DISA
4 Pages
-
UC-OH²
2 Pages
-
IGA
2 Pages
-
CDD
2 Pages
-
FBS
18 Pages
-
MINOPAB
6 Pages
-
PIL
23 Pages
-
MWS / MWK
23 Pages
-
ERK-SO
43 Pages
-
BKSYS
18 Pages
-
MINODSA
6 Pages
-
DKA
6 Pages
-
LAQ
11 Pages
-
VMPR/VMPQ
29 Pages
-
BKA-EN
79 Pages
-
CPL
15 Pages
-
AUDIX®
25 Pages
-
VREX
26 Pages
-
VQEX
17 Pages
-
VPEX
18 Pages
-
SVA-FS
11 Pages
-
NRWG
22 Pages
-
COMBIDSC
26 Pages
-
DSCXL
17 Pages
-
DSCU
18 Pages
-
DSCPL
16 Pages
-
DSCP
15 Pages
-
DSC
37 Pages
-
DO
10 Pages
-
VRAQ
46 Pages
-
UEKU
6 Pages
-
UEK
6 Pages
-
SS-K
6 Pages
-
DQJP
9 Pages
-
VOLKOM
6 Pages
-
DQJ
38 Pages
-
ALPETY
16 Pages
-
CTT
23 Pages
-
STV
8 Pages
-
KWB
19 Pages
-
GREENKIT
20 Pages
-
FKU
31 Pages
-
FKF
29 Pages
-
SGA
5 Pages
-
DBB
27 Pages
-
TVO
8 Pages
-
AL
23 Pages
-
SVA-FF
15 Pages
-
RF Return air filter grille
7 Pages
-
NBS
34 Pages
-
MKAR_MKAQ
13 Pages
-
KF
4 Pages
-
JK
16 Pages
-
HK
16 Pages
-
Lint Separator FLARE
13 Pages
-
FLAQ
11 Pages
-
FKW
28 Pages
-
FG
14 Pages
-
ERK-MB
38 Pages
-
DISA-H
34 Pages
-
DISA-360
32 Pages
-
DISA-300
51 Pages
-
CNV
29 Pages
-
BKA-UE
35 Pages
-
BAK-250 Fire protection unit
17 Pages
-
BAK-240
16 Pages
-
Aquaris-Silent
38 Pages
-
Aquaris_KWB
20 Pages
-
DISA-W
43 Pages
-
PILB/PILBR
33 Pages
-
DAV
19 Pages
-
4DE
18 Pages
-
4DF
13 Pages
-
DQC
16 Pages
-
DQDL
16 Pages
-
IDA
21 Pages
-
IKA
23 Pages
-
ZMD
17 Pages
-
DQF
15 Pages
-
DQJF
12 Pages
-
DQJA/DQJR
10 Pages
-
DQJSL
17 Pages
-
DQJSLC
17 Pages
-
DHV
18 Pages
-
DSARR
7 Pages
-
QA
30 Pages
-
PUSH
23 Pages
-
WQA
12 Pages
-
DSX-XXL
23 Pages
-
AUDIX®-ÜSG
13 Pages
-
SIA
7 Pages
-
SAR/SAQ/SARP
13 Pages
-
WDA
32 Pages
-
KGRR
17 Pages
-
DBBRR
11 Pages
-
WGARR
7 Pages
-
WGA
29 Pages
-
DKAPPs
6 Pages
-
EBE/EBP
52 Pages
-
VRAPPs
20 Pages
-
VRAR
52 Pages
-
MAK
15 Pages
-
DISA-Family
4 Pages
-
RMS
11 Pages
-
EasyBus
24 Pages
-
TSR
5 Pages
-
RS-F
7 Pages
-
RS
15 Pages
-
VLV
31 Pages
-
VARS
26 Pages
-
VAQS
19 Pages
-
VAS
26 Pages
-
PIANO
27 Pages
-
MBM
10 Pages
-
MBE/MBP
27 Pages
-
DKG
6 Pages
-
ALAS-P
5 Pages
-
ALAS-F 125
6 Pages
-
ALAS
10 Pages
-
ALA-SO
4 Pages
-
ALA-R
4 Pages
-
ALA
4 Pages
-
LL
7 Pages
-
RR-Complete
41 Pages
-
DBBR
6 Pages
-
PA
32 Pages
-
LK
12 Pages
-
IB-R
15 Pages
-
IB-Q
21 Pages
-
KG
19 Pages
-
BSG
19 Pages
-
DSX-XXL-W
25 Pages
-
AUDIX®-AW
20 Pages
-
DSX
25 Pages
-
MINODSX
6 Pages
-
MINODSA
6 Pages
-
DSA
15 Pages
-
COMBIPIL
11 Pages
-
COMBIDQJ
11 Pages
-
MINOPAB
6 Pages
-
BDA
11 Pages
-
SPB
10 Pages
-
CULTRA-Studioline
24 Pages
-
DISA-H
34 Pages
-
DISA-360
32 Pages
-
DISA-300
51 Pages
-
AQUARIS SILENT
38 Pages
-
NBS
24 Pages
-
CNV
29 Pages
-
CNVA
32 Pages
-
JK-LP/JK-LU
15 Pages
-
HKP / HKU
16 Pages
-
FKW
16 Pages
-
FLARE
13 Pages
-
RF
7 Pages
-
KGF
9 Pages
-
SVA-FF
8 Pages
-
BKA-Ü
35 Pages
-
BSK-RPR
60 Pages
-
BKP-EN
40 Pages
-
BAK-240
6 Pages
-
BAK-250
14 Pages
-
KF
4 Pages