Technical Documentation "Installation, Mounting and Operating Instructions" BAK-250 Fire protection unit General building supervisory approval Z-41.3-542 SCHAKO | Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen
Open the catalog to page 1
vchAko Fire protection unit BAK-250 Technical documentation Description VENTILATION FITTINGS Exhaust air: DQJA-SR-A DQJA-SQ-A 4-DE-A DQD-L 4-DF Weight of the fire protection unit Exposed ceiling constructions can loose their strength prematurely. To avoid this ceiling constructions are protected with fire resistant suspended ceilings. Openings in the suspended ceiling, for example for air diffusers, are only permitted if they can be closed in case of fire with suitable fire protection equipment, for example with the fire protection unit type BAK-250. Fire protection unit type BAK-250 with...
Open the catalog to page 2
Fire protection unit BAK-250 Technical documentation Description CONNECTION OF VENTILATION DUCTS The fire protection unit type BAK-250 must only be connected to ventilation ducts made of non-flammable materials (Construction class A to DIN 4102). The ventilation ducts used must not exert substantial forces on the fire protection unit or the suspended ceiling in case of fire. The required bellow expansion joints (flexible connection pieces) must be designed as flammable, elastic connection pieces made of at least normally inflammable building materials (EN 13501-1) and must be installed...
Open the catalog to page 3
Fire protection unit BAK-250 Technical documentation Models and dimensions MODELS AND DIMENSIONSDimensions 1 Housing 2 Shut-off damper 3 Snap-in locking device 4 Shut-off damper housing 5 Trigger device 6 Suspension lug 7 Drive (optional) 8 Fusible link cover 9 Available starting from nominal size 500 Nominal size Table 2: Available sizes Trigger device The fire protection unit is supplied as standard with an inside and an outside trigger device (fusible link with 72°C trigger temperature)! Thus, during a fire, the trigger and closing motions of the damper leaf occur independently of...
Open the catalog to page 4
Fire protection unit BAK-250 Technical documentation Installation details INSTALLATION DETAILS Installation The fire protection unit type BAK-250 is connected to the the ceiling with four suspensions. This is followed by mounting the suspended ceiling. Then the air diffuser is connected to the suspended ceiling or to the plenum box using a screw connection (SM mounting). The tension rod dimensions are calculated from the loads of their own weight, of the connected ducts and of the air diffuser. Installation Instructions Inserted ceiling area Fire-resistant ceiling Supply air Exhaust air...
Open the catalog to page 5
Fire protection unit BAK-250 Technical documentation Accessories ACCESSORIES Available at an extra charge Limit switch type ES 1 A Electric spring return actuator ELD-I-B - BFG24-T-ST SO (24 V AC/DC) - BFG230-T SO (230 V AC) Limit switch type ES 1 A Electric limit switch for position indication. Switching element including one NC and one NO contact each, 4 connections for M3.5 screw terminals for max. 2 mm². 250 V AC, Ie 6A, IP67 using suitable cable glands M20 (on-site). Figure 8: Circuit diagram limit switch type ES 1 A BAK-250 with electric spring return actuator type LD-I-B electric...
Open the catalog to page 6
Fire protection unit BAK-250 Technical documentation Specification texts Fire protection unit with resistance class K 90 U according to the general building supervisory approval Z-41.3-542 suitable for installation in suspended ceilings designed as panelled ceilings in screw-type and spatulated design that meet the requirements of an independent component of being fire-resistant for 90 minutes in the event of a fire from top or bottom and are classified in fire resistance class F90-A. Metal-cased damper leaf and visible screw connection of the air diffuser. Damper blade is triggered by an...
Open the catalog to page 7
Fire protection unit BAK-250 Technical documentation Maintenance or functional test MAINTENANCE OR FUNCTIONAL TEST Polluted and damp air can impair the continuous operational safety. This is why, after commissioning the ventilation installation, all shut-off devices must be subjected to a functional test at a six-month interval according to section 5 of the general building supervisory approval Z-41.3-574. If two consecutive functional tests show no defects, the shut-off devices only have to be tested at a yearly interval. If maintenance agreements are made for ventilation installations, it...
Open the catalog to page 8
Fire protection unit BAK-250 Technical documentation Maintenance or functional test 1.2.2 Trigger device with electric spring return actuator ELD-I-B Electric system check Actuate the electric pushbutton (on-site), this interrupts the power supply to the spring return actuator (pos.20); as a result, the shut-off damper must close automatically. Press the on-site electric pushbutton again which restores the power supply to the electric spring return actuator; as a result, the adjusting mechanism moves the shut-off damper to the OPEN position again. The pushbutton (pos.21) is pressed on the...
Open the catalog to page 9
Fire protection unit BAK-250 Technical documentation Maintenance or functional test SAMPLE TEMPLATES SAMPLE OF FUNCTIONAL TEST PROTOCOL SCHAKO Ferdinand Schad KG Steigstrasse 25-27 D-78600 Kolbingen Phone: +49- (0)7463 / 980-0 Fax: +49- (0)7463 / 980-200 E-mail: info@schako.de Web: www.schako.de Sample Functional test protocol for____________________ Cons. No. ____________________ Usability certificate: Series: Release device: The following function steps have been carried out according to the documents Installation, mounting and operating instructions External check: System:...
Open the catalog to page 10
Fire protection unit BAK-250 Technical documentation Maintenance or functional test SCHAKO Ferdinand Schad KG Steigstrasse 25-27 D-78600 Kolbingen Phone: +49- (0)7463 / 980-0 Fax: +49- (0)7463 / 980-200 E-mail: infoschako.de Web: www.schako.de Sample Functional test protocol for____________________ Cons. No. ____________________ Defects found during the test on: Defects found during the test on: Defects found during the test on: Defects found during the test on: Construction subject to change No return possible Version: 2015-08-01 | Document: 09/14 | Page 11
Open the catalog to page 11All SCHAKO KG catalogs and technical brochures
-
CNVA
32 Pages
-
KGF Compact Filter Grille
9 Pages
-
AUDIX
2 Pages
-
DISA
4 Pages
-
UC-OH²
2 Pages
-
IGA
2 Pages
-
CDD
2 Pages
-
FBS
18 Pages
-
MINOPAB
6 Pages
-
PIL
23 Pages
-
MWS / MWK
23 Pages
-
ERK-SO
43 Pages
-
BKSYS
18 Pages
-
MINODSA
6 Pages
-
DKA
6 Pages
-
LAQ
11 Pages
-
VMPR/VMPQ
29 Pages
-
BKA-EN
79 Pages
-
CPL
15 Pages
-
AUDIX®
25 Pages
-
VREX
26 Pages
-
VQEX
17 Pages
-
VPEX
18 Pages
-
SVA-FS
11 Pages
-
NRWG
22 Pages
-
COMBIDSC
26 Pages
-
DSCXL
17 Pages
-
DSCU
18 Pages
-
DSCPL
16 Pages
-
DSCP
15 Pages
-
DSC
37 Pages
-
DO
10 Pages
-
VRAQ
46 Pages
-
UEKU
6 Pages
-
UEK
6 Pages
-
SS-K
6 Pages
-
DQJP
9 Pages
-
VOLKOM
6 Pages
-
DQJ
38 Pages
-
ALPETY
16 Pages
-
CTT
23 Pages
-
STV
8 Pages
-
KWB
19 Pages
-
GREENKIT
20 Pages
-
FKU
31 Pages
-
FKF
29 Pages
-
SGA
5 Pages
-
DBB
27 Pages
-
TVO
8 Pages
-
AL
23 Pages
-
SVA-FF
15 Pages
-
RF Return air filter grille
7 Pages
-
NBS
34 Pages
-
MKAR_MKAQ
13 Pages
-
KF
4 Pages
-
JK
16 Pages
-
HK
16 Pages
-
Lint Separator FLARE
13 Pages
-
FLAQ
11 Pages
-
FKW
28 Pages
-
FG
14 Pages
-
ERK-MB
38 Pages
-
DISA-H
34 Pages
-
DISA-360
32 Pages
-
DISA-300
51 Pages
-
CNV
29 Pages
-
BKP-EN Fire damper
40 Pages
-
BKA-UE
35 Pages
-
BAK-250 Fire protection unit
17 Pages
-
BAK-240
16 Pages
-
Aquaris-Silent
38 Pages
-
Aquaris_KWB
20 Pages
-
DISA-W
43 Pages
-
PILB/PILBR
33 Pages
-
DAV
19 Pages
-
4DE
18 Pages
-
4DF
13 Pages
-
DQC
16 Pages
-
DQDL
16 Pages
-
IDA
21 Pages
-
IKA
23 Pages
-
ZMD
17 Pages
-
DQF
15 Pages
-
DQJF
12 Pages
-
DQJA/DQJR
10 Pages
-
DQJSL
17 Pages
-
DQJSLC
17 Pages
-
DHV
18 Pages
-
DSARR
7 Pages
-
QA
30 Pages
-
PUSH
23 Pages
-
WQA
12 Pages
-
DSX-XXL
23 Pages
-
AUDIX®-ÜSG
13 Pages
-
SIA
7 Pages
-
SAR/SAQ/SARP
13 Pages
-
WDA
32 Pages
-
KGRR
17 Pages
-
DBBRR
11 Pages
-
WGARR
7 Pages
-
WGA
29 Pages
-
DKAPPs
6 Pages
-
EBE/EBP
52 Pages
-
VRAPPs
20 Pages
-
VRAR
52 Pages
-
MAK
15 Pages
-
DISA-Family
4 Pages
-
RMS
11 Pages
-
EasyBus
24 Pages
-
TSR
5 Pages
-
RS-F
7 Pages
-
RS
15 Pages
-
VLV
31 Pages
-
VARS
26 Pages
-
VAQS
19 Pages
-
VAS
26 Pages
-
PIANO
27 Pages
-
MBM
10 Pages
-
MBE/MBP
27 Pages
-
DKG
6 Pages
-
ALAS-P
5 Pages
-
ALAS-F 125
6 Pages
-
ALAS
10 Pages
-
ALA-SO
4 Pages
-
ALA-R
4 Pages
-
ALA
4 Pages
-
LL
7 Pages
-
RR-Complete
41 Pages
-
DBBR
6 Pages
-
PA
32 Pages
-
LK
12 Pages
-
IB-R
15 Pages
-
IB-Q
21 Pages
-
KG
19 Pages
-
BSG
19 Pages
-
DSX-XXL-W
25 Pages
-
AUDIX®-AW
20 Pages
-
DSX
25 Pages
-
MINODSX
6 Pages
-
MINODSA
6 Pages
-
DSA
15 Pages
-
COMBIPIL
11 Pages
-
COMBIDQJ
11 Pages
-
MINOPAB
6 Pages
-
BDA
11 Pages
-
SPB
10 Pages
-
CULTRA-Studioline
24 Pages
-
DISA-H
34 Pages
-
DISA-360
32 Pages
-
DISA-300
51 Pages
-
AQUARIS SILENT
38 Pages
-
NBS
24 Pages
-
CNV
29 Pages
-
CNVA
32 Pages
-
JK-LP/JK-LU
15 Pages
-
HKP / HKU
16 Pages
-
FKW
16 Pages
-
FLARE
13 Pages
-
RF
7 Pages
-
KGF
9 Pages
-
SVA-FF
8 Pages
-
BKA-Ü
35 Pages
-
BSK-RPR
60 Pages
-
BKP-EN
40 Pages
-
BAK-240
6 Pages
-
KF
4 Pages