SCHAKOVolumetric flow controllerVRAR Leakage air flow with control damper closed according to DIN EN 1751, up to class 3 Ferdinand Schad KG SteigstraBe 25-27 D-78600 Kolbingen Telephone +49 (0) 74 63 - 980 - 0 Fax +49 (0) 74 63 - 980 - 200 info@schako.de schako.com

Open the catalog to page 1
VRAR - 2

08/60 - 2 Construction subject to change. Version: 30.03.2020 No return possible!

Open the catalog to page 2
VRAR - 3

Volumetric flow controller VRAR Description A volumetric flow controller is used for pressure-independent volumetric flow regulation in ventilation and air-conditioning systems. It is used to keep the volumetric flow constant (CAV) within specified limits or to control it variably (VAV) as a function of a command variable, for example a room temperature controller, DDC or bus system. For constant volumetric flows, the operating stages CLOSED/Vmin/Vmid/Vmax/OPEN are available in stage operation, controlled via relays or switches. The housing, measuring sensor, control flap, PI controller...

Open the catalog to page 3
VRAR - 4

Volumetric flow controller VRAR All volumetric flow controllers can be assembled with horizontal or vertical damper axis. Field of application - for supply and return air systems - for constant CAV or variable VAV installations. - for positive control Vmin, Vmid, Vmax, “OPEN" or "CLOSED" - For volumetric flow and linear pressure control - in the differential pressure range 50 - 1,000 Pascal - at ambient temperatures 0 ...+...50 °C, requirement: measuring air 0...+ +50 °C/5...95% rH, non-condensing - with command signal 0...10 V DC, 2...10 V DC, via MP bus (Belimo) or Lon, Modbus, KNX,...

Open the catalog to page 4
VRAR - 5

Volumetric flow controller VRAR Construction Housing - Galvanised sheet steel (-SV) - Galvanised sheet steel with DD coating inside (-DD) - Stainless steel 1.4301 (-V2) or 1.4571 (-V4) Damper blade - Galvanised sheet steel (-SV) - Stainless steel 1.4301 (-V2A) or 1.4571 (-V4A) Damper leaf seal - made of PUR, silicone-free - for airtight sealing design to DIN EN 1751 Damper bearing - Brass Measuring cross - Extruded aluminium profile (for stainless steel design with DD coating) Measuring cross support - Plastic (PA6) Model VRAR-... - round design, for spiral duct connection to DIN EN 1506,...

Open the catalog to page 5
VRAR - 6

Volumetric flow controller VRAR Models and dimensions Dimensions with electric controller VRAR-...-DS0, without acoustic cladding with pneumatic controller VRAR-...-DS0, without acoustic cladding Available sizes VRAR-... Construction subject to change.

Open the catalog to page 6
VRAR - 7

Volumetric flow controller VRAR Accessories - dimensions Rubber lip seal (-GD1), on both sides Detail X Flat flange (-FF1/-FF2, pair), on both sides according to DIN 24 154/5 Please note! Duct silencers must be ordered separately! For further information, see duct silencer RS documentation. Available sizes flat flange (-FF1/-FF2)

Open the catalog to page 7
VRAR - 8

Volumetric flow controller VRAR Insertion loss Duct silencer (-RS-N) RS-N-...-50/100, L1=500, without central baffle RS-N-...-50/100, L1=1450, without central baffle RS-N-...-50/100, L1=950, without central baffle Version: 30.03.2020 Construction subject to change. No return possible!

Open the catalog to page 8
VRAR - 9

Volumetric flow controller VRARTechnical data Volumetric flow range VRAR-A..., with electric controller NW (mm) VRAR-A..., with pneumatic controller Attention, the following specifications are important for the programming of the volumetric flow controllers: - this table merely specifies the complete measuring range of the controller (volumetric flow range) - If the customer absolutely wants a calibration curve different from 12 m/s, it must be specified! Once it is approved by the competent department, it can be adjusted correspondingly. - When the air volume drops below the Vmin shown in...

Open the catalog to page 9
VRAR - 10

Volumetric flow controller VRAR Static minimum pressure difference VRAR-A..., with electric controller Construction subject to change.

Open the catalog to page 10
VRAR - 11

Version: 30.03.2020 No return possible! Construction subject to change.

Open the catalog to page 11
VRAR - 12

Version: 30.03.2020 No return possible! Construction subject to change.

Open the catalog to page 12
VRAR - 13

Version: 30.03.2020 No return possible! Construction subject to change.

Open the catalog to page 13
VRAR - 14

Version: 30.03.2020 No return possible! Construction subject to change.

Open the catalog to page 14
VRAR - 15

Version: 30.03.2020 No return possible! Construction subject to change.

Open the catalog to page 15
VRAR - 16

Version: 30.03.2020 No return possible! Construction subject to change.

Open the catalog to page 16
VRAR - 17

Version: 30.03.2020 No return possible! Construction subject to change.

Open the catalog to page 17
VRAR - 18

Version: 30.03.2020 No return possible! Construction subject to change.

Open the catalog to page 18
VRAR - 19

Version: 30.03.2020 No return possible! Construction subject to change.

Open the catalog to page 19
VRAR - 20

Version: 30.03.2020 No return possible! Construction subject to change.

Open the catalog to page 20
VRAR - 21

Volumetric flow controller VRAR Radiated noise VRAR with insulated connections on both sides 20 mm mineral wool insulation With a straight supply and return air flow of 3 m each, the VRAR acoustic cladding reduces the radiated noise by 8 dB(A). Construction subject to change.

Open the catalog to page 21
VRAR - 22

Volumetric flow controller VRAR Technical data of the control components Measured value collection and control function The measured value collection is carried out via a flow-favouring double measuring cross. The measuring openings are distributed over the measuring cross according to the median line method. The pressure differential formed on the measuring cross is determined by means of a dynamic or static measuring sensor. The measured values are averaged to give an average value which represents a measuring quantity for the volumetric flow. The controller compares the actual value...

Open the catalog to page 22
VRAR - 23

Volumetric flow controller VRAR Circuit diagrams Circuit diagram electric controller (standard) Compact controller Belimo make: LMV-D3-MP / NMV-D3-MP VAV with analogue command signal VAV with lock (CLOSED) MP bus activation Mode 2-10 V DC with integrated switch Lock mode (CLOSED) In the 2...10 V mode, the following function can be carried out with a 0...10 V signal: Contact closed, function active Contact closed, function active, in mode 2 ...10 V only Contact open * not available for DC 24 V supply Version: 30.03.2020 Construction subject to change. No return possible!

Open the catalog to page 23
VRAR - 24

Function Description / action Status display 24V power supply o.k. - VAV-Compact ready for operation Target volume reached Addressing via MP master (Acknowledgement at the VAV-Compact) Addressing via MP master (with serial number) MP-PP display Communication []| yellow LED (status) is flashing 1.) Synch time 2.) Adaptation time Construction subject to change. LED pattern Adaptation @ LED 1 power Address 0 LED 2 status Synchronisation started by: a) Operating / service unit b) Manual trigger device at the VAV-Compact c) Power ON behaviour Adaptation started by: a) Operating / service unit b)...

Open the catalog to page 24

All SCHAKO KG catalogs and technical brochures

  1. AUDIX

    2 Pages

  2. DISA

    4 Pages

  3. UC-OH²

    2 Pages

  4. IGA

    2 Pages

  5. CDD

    2 Pages

  6. FBS

    18 Pages

  7. MINOPAB

    6 Pages

  8. PIL

    23 Pages

  9. MWS / MWK

    23 Pages

  10. ERK-SO

    43 Pages

  11. BKSYS

    18 Pages

  12. MINODSA

    6 Pages

  13. DKA

    6 Pages

  14. LAQ

    11 Pages

  15. VMPR/VMPQ

    29 Pages

  16. BKA-EN

    79 Pages

  17. CPL

    15 Pages

  18. AUDIX®

    25 Pages

  19. VREX

    26 Pages

  20. VQEX

    17 Pages

  21. VPEX

    18 Pages

  22. SVA-FS

    11 Pages

  23. NRWG

    22 Pages

  24. COMBIDSC

    26 Pages

  25. DSCXL

    17 Pages

  26. DSCU

    18 Pages

  27. DSCPL

    16 Pages

  28. DSCP

    15 Pages

  29. DSC

    37 Pages

  30. DO

    10 Pages

  31. VRAQ

    46 Pages

  32. UEKU

    6 Pages

  33. UEK

    6 Pages

  34. SS-K

    6 Pages

  35. DQJP

    9 Pages

  36. VOLKOM

    6 Pages

  37. DQJ

    38 Pages

  38. ALPETY

    16 Pages

  39. CTT

    23 Pages

  40. STV

    8 Pages

  41. KWB

    19 Pages

  42. GREENKIT

    20 Pages

  43. FKU

    31 Pages

  44. FKF

    29 Pages

  45. SGA

    5 Pages

  46. DBB

    27 Pages

  47. TVO

    8 Pages

  48. AL

    23 Pages

  49. SVA-FF

    15 Pages

  50. RF

    7 Pages

  51. NBS

    34 Pages

  52. MKAR_MKAQ

    13 Pages

  53. KGF

    11 Pages

  54. KF

    4 Pages

  55. JK

    16 Pages

  56. HK

    16 Pages

  57. FLARE

    13 Pages

  58. FLAQ

    11 Pages

  59. FKW

    28 Pages

  60. FG

    14 Pages

  61. ERK-MB

    38 Pages

  62. DISA-H

    34 Pages

  63. DISA-B

    32 Pages

  64. DISA-601

    41 Pages

  65. DISA-360

    32 Pages

  66. DISA-300

    51 Pages

  67. CNVA

    32 Pages

  68. CNV

    29 Pages

  69. BSK-RPR

    60 Pages

  70. BKP-EN

    40 Pages

  71. BKA-UE

    35 Pages

  72. BAK-250

    17 Pages

  73. BAK-240

    16 Pages

  74. Aquaris-Silent

    38 Pages

  75. Aquaris_KWB

    20 Pages

  76. DISA-W

    43 Pages

  77. PILB/PILBR

    33 Pages

  78. DAV

    19 Pages

  79. 4DE

    18 Pages

  80. 4DF

    13 Pages

  81. DQC

    16 Pages

  82. DQDL

    16 Pages

  83. IDA

    21 Pages

  84. IKA

    23 Pages

  85. ZMD

    17 Pages

  86. DQF

    15 Pages

  87. DQJF

    12 Pages

  88. DQJA/DQJR

    10 Pages

  89. DQJSL

    17 Pages

  90. DQJSLC

    17 Pages

  91. DHV

    18 Pages

  92. DSARR

    7 Pages

  93. QA

    30 Pages

  94. PUSH

    23 Pages

  95. WQA

    12 Pages

  96. DSX-XXL

    23 Pages

  97. AUDIX®-ÜSG

    13 Pages

  98. SIA

    7 Pages

  99. SAR/SAQ/SARP

    13 Pages

  100. WDA

    32 Pages

  101. KGRR

    17 Pages

  102. DBBRR

    11 Pages

  103. WGARR

    7 Pages

  104. WGA

    29 Pages

  105. DKAPPs

    6 Pages

  106. EBE/EBP

    52 Pages

  107. VRAPPs

    20 Pages

  108. MAK

    15 Pages

  109. DISA-Family

    4 Pages

  110. RMS

    11 Pages

  111. EasyBus

    24 Pages

  112. TSR

    5 Pages

  113. RS-F

    7 Pages

  114. RS

    15 Pages

  115. VLV

    31 Pages

  116. VARS

    26 Pages

  117. VAQS

    19 Pages

  118. VAS

    26 Pages

  119. PIANO

    27 Pages

  120. MBM

    10 Pages

  121. MBE/MBP

    27 Pages

  122. DKG

    6 Pages

  123. ALAS-P

    5 Pages

  124. ALAS-F 125

    6 Pages

  125. ALAS

    10 Pages

  126. ALA-SO

    4 Pages

  127. ALA-R

    4 Pages

  128. ALA

    4 Pages

  129. LL

    7 Pages

  130. RR-Complete

    41 Pages

  131. DBBR

    6 Pages

  132. PA

    32 Pages

  133. LK

    12 Pages

  134. IB-R

    15 Pages

  135. IB-Q

    21 Pages

  136. KG

    19 Pages

  137. BSG

    19 Pages

  138. DSX-XXL-W

    25 Pages

  139. AUDIX®-AW

    20 Pages

  140. DSX

    25 Pages

  141. MINODSX

    6 Pages

  142. MINODSA

    6 Pages

  143. DSA

    15 Pages

  144. COMBIPIL

    11 Pages

  145. COMBIDQJ

    11 Pages

  146. MINOPAB

    6 Pages

  147. BDA

    11 Pages

  148. SPB

    10 Pages

  149. DISA-H

    34 Pages

  150. DISA-601

    41 Pages

  151. DISA-360

    32 Pages

  152. DISA-300

    51 Pages

  153. DISA-B

    32 Pages

  154. AQUARIS SILENT

    38 Pages

  155. NBS

    24 Pages

  156. CNV

    29 Pages

  157. CNVA

    32 Pages

  158. JK-LP/JK-LU

    15 Pages

  159. HKP / HKU

    16 Pages

  160. FKW

    16 Pages

  161. FLARE

    13 Pages

  162. RF

    7 Pages

  163. KGF

    9 Pages

  164. SVA-FF

    8 Pages

  165. BKA-Ü

    35 Pages

  166. BSK-RPR

    60 Pages

  167. BKP-EN

    40 Pages

  168. BAK-240

    6 Pages

  169. BAK-250

    14 Pages

  170. KF

    4 Pages