Product catalog summary
Overview: This document is a technical catalogue for the RPM-V and RPMC-V series of variable flow air regulators. These regulators are designed for systems with variable air volume for both input and output air, allowing for real-time adjustment of air volume to enhance the efficiency of air-conditioning systems.
Specifications:
  • Models: RPM-V.01 and RPM-V.02 with control options via 0(2)…10 V signal, MP-BUS, Modbus RTU, BACnet protocols. Optional models include RPM-V.75, RPM-V.78, RPM-V.91, RPM-V.92.
  • Nominal Size: DIM 80 to DIM 630.
  • Length: 450/600 mm depending on nominal size.
  • Air Flow Volume: 18 to 7,900 m³/h, with a maximum of 13,500 m³/h at 12 m/s.
  • Accuracy: ±8% for velocity up to 3 m/s and ±5% for higher velocities.
  • Working Conditions: Maximum air flow speed of 7 m/s, maximum duct pressure of 1000 Pa, suitable for mild climates, and temperature range from 0°C to +50°C.
Technical Data:
  • Air Volume: Detailed tables provide standard and maximum air volume values for various dimensions.
  • Pressure Losses: Values are provided for different operating modes and pressure differences.
  • Noise Data: Sound power levels are detailed for various sizes and pressure differences, with specific acoustic power levels in octave bands.
Recommendations:
  • Ensure steady air circulation across the controller's surface.
  • Install in environments free from abrasive, chemical, and adhesive particles.
  • Consider insulation options for temperature control.
Technical Data Overview: This section provides detailed technical specifications for the RPMC-V series, including data on sound power levels, radiated noise, and air volume control under various pressure differentials.
Sound Power Levels: The sound power levels inside the pipeline are measured at a pressure difference of 500 Pa. Data is presented for various sizes and air flow volumes, with sound levels given in decibels across different frequency bands (63 Hz to 8000 Hz). Specific sound power levels (Lw) and overall sound levels (LwA) are provided for each configuration.
Radiated Noise: The radiated noise levels of the air volume controller are detailed for different air flow volumes (V) and pressure differentials (∆Pst) ranging from 50 Pa to 500 Pa. Noise levels are corrected by filter A and presented in decibels (dB(A)).
Key Parameters:
  • Pressure Differential (∆Pst): 250 Pa and 500 Pa are highlighted as standard conditions for measurements.
  • Size and Volume: Various sizes from 200x100 mm to 1000x1000 mm are covered, with corresponding air flow volumes ranging from 90 m³/h to 43000 m³/h.
Recommendations: For optimal performance, consider the specific size and air flow volume requirements of your application, as well as the acceptable noise levels for your environment.
See more

Catalog excerpts

TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-1

REGULATION REGULATION VARIABLE FLOW VARIABLE FLOW RPM-V - RPMC-V SERIES RPM-V RPMC-V Air flow regulator, with variable flow. Circular Air flow regulator, with variable flow. S

 Open the catalog to page 1
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-2

REGULATION VARIABLE FLOW

 Open the catalog to page 2
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-3

VARIABLE FLOW DAMPER Model RPM-V. The air volume controllers are meant for systems with a variable air volume that is used for input or output air. The required amount of air that is taken into the individual rooms or working areas is variable with respect to time and can be changed according to momentary need when the controllers are installed. Total power of air-conditioning system can be lower. This variable systems enable a more economical operation air-conditioning systems and while ensuring individual well-being on the premises setting. The controller consists of the body of the controller...

 Open the catalog to page 3
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-4

VARIABLE FLOW DAMPER RPM-V 1. Regulator body 2. Controller 3. Controller blade 4. Tab 5. Pressure sampling -p1 6. Pressure sampling -p2 7. Rubber seal RPM-V Air flow control Pressure sensors 5 Muestreo de presión - p1 RPM-V Hoja del controlador 6 Pipe pressureMuestreo de presión - p2 control RPM-V Room pressure control Actuating mechanism Pressure controller Actuating mechanism Pressure controller Static pressure sensor Actuating mechanism Static pressure sensor ∆ρ [Рa] Controller pressure loss RPM-V Recommmended distance from double branch joint ∆ρs [Рa] Static pressure difference between duct...

 Open the catalog to page 4
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-5

SERIES TECHNICAL DATA Air volume Air volume [m³/h] Dimensions AxB [mm] Standard values* Maximum values REGULATION VARIABLE FLOW *Default controller settings

 Open the catalog to page 5
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-6

SERIES TECHNICAL DATA Determination of actual air volume Air volume value is determined by means of the computation from the measured value U5 Sample for the operating mode 2…10V Sample for the operating mode 0…10V Searched for : actual air volume Búsqueda para: volumen de aire efectivo Voltage measured on U Tensión medida en5 : 3,5 V V : 3,5 Vnom = 2800 m .h 2800 = 525 8 Actual air volume aire m³ h-1 El volumen de is 525actual es 525 m .h . Searched for : actual air volume Búsqueda para: volumen de aire efectivo Voltage measured on U5 : 3,5 V Actual air volume is 770 m³ h-1 El volumen de aire...

 Open the catalog to page 6
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-7

SERIES TECHNICAL DATA Sound power level inside the pipeline at pressure difference 50 Pa REGULATION VARIABLE FLOW

 Open the catalog to page 7
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-8

SERIES TECHNICAL DATA Sound power level inside the pipeline at pressure difference 100 Pa REGULATION VARIABLE FLOW

 Open the catalog to page 8
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-9

SERIES TECHNICAL DATA Sound power level inside the pipeline at pressure difference 250 Pa REGULATION VARIABLE FLOW

 Open the catalog to page 9
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-10

SERIES TECHNICAL DATA Sound power level inside the pipeline at pressure difference 500 Pa REGULATION VARIABLE FLOW

 Open the catalog to page 10
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-11

SERIES TECHNICAL DATA Sound power level Lwa [dB (A)] inside the pipeline REGULATION VARIABLE FLOW

 Open the catalog to page 11
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-12

SERIES TECHNICAL DATA Sound power level Lwa [dB (A)] inside the pipeline REGULATION VARIABLE FLOW

 Open the catalog to page 12
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-13

SERIES TECHNICAL DATA Sound power level Lwa [dB (A)] inside the pipeline REGULATION VARIABLE FLOW

 Open the catalog to page 13
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-14

SERIES TECHNICAL DATA Sound power level radiated outside the pipeline - without insulation The radiated noise of the air volume controller is given below V [m³h-1 ] - air flow volume ∆st [Pa] pressure differential REGULATION VARIABLE FLOW LWA [dB(A)] - otal level of acoustic power corrected by

 Open the catalog to page 14
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-15

SERIES TECHNICAL DATA Sound power level Lwa [dB(A)] radiated outside the pipeline, without insulation REGULATION VARIABLE FLOW

 Open the catalog to page 15
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-16

SERIES TECHNICAL DATA Sound power level Lwa [dB(A)] radiated outside the pipeline, without insulation

 Open the catalog to page 16
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-17

SERIES TECHNICAL DATA Sound power level Lwa [dB(A)] radiated outside the pipeline, without insulation REGULATION VARIABLE FLOW

 Open the catalog to page 17
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-18

VARIABLE FLOW DAMPER Model RPMC-V. The air volume controllers are meant for systems with a variable air volume that is used for input or output air. The required amount of air that is taken into the individual rooms or working areas is variable with respect to time and can be changed according to momentary need when the controllers are installed. Total power of air-conditioning system can be lower. This variable systems enable a more economical operation air-conditioning systems and while ensuring individual well-being on the premises setting. The controller consists of the body of the controller...

 Open the catalog to page 18
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-19

VARIABLE FLOW DAMPER Air Volume Air Volume [m³/h] Dimensions AxB [mm] Standard values* Minimal (w ≈ 1m/s) Maximum values Vnom REGULATION VARIABLE FLOW

 Open the catalog to page 19
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-20

SERIES TECHNICAL DATA Determination of actual air volume Air volume value is determined by means of the computation from the measured value U5 Sample for the operating mode 2…10V Searched for : actual air volume Búsqueda para: volumen de aire efectivo Voltage measured on U Tensión medida en5 : 3,5 V V : 3,5 Vnom = 2800 m .h Sample for the operating mode 0…10V 2800 = 525 8 Actual air volume aire m³ h-1 El volumen de is 525actual es 525 m .h . Searched for : actual air volume Búsqueda para: volumen de aire efectivo Voltage measured on U5 : 3,5 V Actual air volume is 770 m³ h-1 El volumen de aire...

 Open the catalog to page 20
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-21

SERIES TECHNICAL DATA Sound power level inside the pipeline at pressure difference 50 Pa REGULATION VARIABLE FLOW *Default controller settings

 Open the catalog to page 21
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-22

SERIES TECHNICAL DATA Sound power level inside the pipeline at pressure difference 50 Pa REGULATION VARIABLE FLOW

 Open the catalog to page 22
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-23

SERIES TECHNICAL DATA Sound power level inside the pipeline at pressure difference 50 Pa REGULATION VARIABLE FLOW *Default controller settings

 Open the catalog to page 23
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-24

SERIES TECHNICAL DATA Sound power level inside the pipeline at pressure difference 100 Pa REGULATION VARIABLE FLOW

 Open the catalog to page 24
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-25

SERIES TECHNICAL DATA Sound power level inside the pipeline at pressure difference 100 Pa REGULATION VARIABLE FLOW *Default controller settings

 Open the catalog to page 25
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-26

SERIES TECHNICAL DATA Sound power level inside the pipeline at pressure difference 100 Pa REGULATION VARIABLE FLOW

 Open the catalog to page 26
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-27

SERIES TECHNICAL DATA Sound power level inside the pipeline at pressure difference 250 Pa REGULATION VARIABLE FLOW

 Open the catalog to page 27
TECHNICAL DATA SHEET VARIABLE FLOW.SAMOVENT-28

SERIES TECHNICAL DATA Sound power level inside the pipeline at pressure difference 250 Pa REGULATION VARIABLE FLOW

 Open the catalog to page 28
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.