FIREFIGHTING SYSTEMS

Product catalog summary
Overview: This document is a technical catalogue detailing the FD Series FDMB Fire Dampers, SV Series Intumescent Grilles, and CI Series Intumescent Collars. It includes specifications, installation guidelines, and performance data for these fire safety products.
FDMB Fire Dampers:
  • Specifications: Designed for installation in solid ceilings and walls, these dampers include components such as damper housing, blades, and thermoelectric mechanisms. Specific dimensions for duct openings are provided.
  • Installation Guidelines: Installation requires reinforcement with profiles and specific screw spacing. Proper sealing around the perimeter is emphasized.
  • Performance Data: A selection table provides flow rates, pressure drops, and sound power levels for various damper sizes and speeds.
SV Series Intumescent Grilles:
  • Specifications: The SV and SVC models are fire-resistant grilles that react at 100ºC to seal ventilation holes, approved according to EN standards.
  • Installation and Use: Suitable for indoor use only, they should not be exposed to temperatures over 40ºC and offer a clearance area of approximately 60%.
CI Series Intumescent Collars:
  • Specifications: Protecta® FR Collars maintain fire resistance in walls and floors, consisting of a steel casing with a reactive graphite-based material.
  • Properties: Suitable for various pipe sizes, providing up to EI 240 fire resistance and high acoustic insulation, with no emissions affecting PVC pipes.
Technical Data:
  • Pressure Loss Calculation: Includes formulas and tables for calculating pressure loss and acoustic output levels.
  • Acoustic Data: Tables provide sound output levels corrected by filter A, with data on acoustic output spectrum in octave ranges.
Technical Specifications:
  • Condition: Ready to use, with steel housing and graphite material.
  • Housing: 1mm powder-coated steel.
  • Conditioning Procedure: EN 13238:2010.
  • Expansion Rate: 17:1.
  • Expansion Pressure: 65.4 N.
  • Density of Graphite: 1409 kg/m³.
  • Normal Expansion Time: Less than 2 minutes.
  • Minimum Expansion Temperature: 105 °C.
  • Durability: International conditions Z2, with humidity class Z1.
  • Service Life: +30 years under normal conditions.
  • Installation Temperature: 5 ˚C to 50 ˚C.
  • CE Marking Classification: ETA-18/0854.
Dimensions:
  • Diameter Range: ø40 to ø315.
Firefighting Systems Catalogue:
  • Series: CFDM, CFDM-V, FDMR, FDMB, SV, SV-C, CI.
  • Fire Resistance (EI): 60, 90, 120.
  • Dimensions: Various diameters and rectangular sizes.
  • Mechanisms and Accessories: Various types indicated by codes.
Installation Guidelines:
  • CI Intumescent Collar: Suitable for flexible or rigid walls and rigid flooring.
  • Installation involves sealing holes with masonry screws or expansion screws, using cement, wood, or steel anchors.
  • Applicable for masonry or concrete walls with a thickness of ≥ 150 mm and cement floors with a thickness of ≥ 150 mm.
See more

Catalog excerpts

FIREFIGHTING SYSTEMS-1

FIREFIGHTING SYSTEMS SAMOVENT TECHNIK FIREFIGHTING SYSTEMS CF - FD - SV - CI SERIES CFDM Fire damper CFDM-V Fire damper with dish valve FDMB Fire damper FDMR Fire damper SV Rectangular fire rated intumescent air transfer grilles SVC Circular fire rated intumescent air transfer grilles

 Open the catalog to page 1
FIREFIGHTING SYSTEMS-2

FIREFIGHTING SYSTEMS

 Open the catalog to page 2
FIREFIGHTING SYSTEMS-3

CF SERIES CFDM - CFDM-V FIRE DAMPER Model CFDM. Model CFDM-V. Fire damper. Model EI60, EI90, EI120. Fire damper with dish valve. Model EI60, EI90, EI120. The CFDM Fire Dampers are shutters in the duct systems of air conditioning devices, which prevent the spread of combustion and fire products from one segment to another by closing the air duct at the points of the fire separation constructions. Both in horizontal as well as vertical, depending on the model. Characteristics: Mechanically operated damper. CE certified acc. to EN 15650. Tested in accordance with EN 1366-2 . Classified acc. to EN...

 Open the catalog to page 3
FIREFIGHTING SYSTEMS-4

CF SERIES CFDM - CFDM-V FIRE DAMPER Model CFDM - CFDM-V .01 Thermal with internal mechanical control. .11 Thermal with internal mechanical control and limit switch. .15 Thermal with internal mechanical control and two limit switches. Dimensiones de la apertura del conducto de la instalación. CFDM Dimensions of the installation duct opening Construction Construcción Construction Construcción Cement or o Yeso Cemento Gyspsum Conducto Duct Cement or o Yeso Cemento Gyspsum CFDM Distribution between fire dampers CFDM Damper clasification Distribución entre Compuertas Cortauegos Fire separating construction...

 Open the catalog to page 4
FIREFIGHTING SYSTEMS-5

Legend: Q = Flow rate Ak = Effective area in m2 Vk = Effective velocity in m/s Pt = Pressure drop in Pa LwA = Sound power in dB(A) FIREFIGHTING SYSTEMS

 Open the catalog to page 5
FIREFIGHTING SYSTEMS-6

Model FDMR. FDMR series circular fire dampers function as separators between two fire sectors. They can be installed in both vertical and horizontal walls. They have a perimeter weatherstrip at both ends to ensure the airtightness between the damper and the air ducts. Characteristics: • Classification EI120 (E) Integrity (I) Isolation (ho) Application in forged ceiling construction. Mounting in horizontal wall. (Ve) Application in wall or flexible wall. Mounting on vertical wall. (i^^o) Symmetrical (regardless of the direction of the air). Suitable for fire in both directions (S) Smoke tightness....

 Open the catalog to page 6
FIREFIGHTING SYSTEMS-7

FD SERIES FDMR TECHNICAL DATA Size 0D Area c Weight [kg] effective [m2] Control mechanism Manual Motorized - 2.9 3.1 0.0031 FIREFIGHTING SYSTEMS FDMR Dumper flap overlapping Z LU c >5 o5 z? < co

 Open the catalog to page 7
FIREFIGHTING SYSTEMS-8

1. Housing 2. Mechanism 3. Opening/closing slat 4. Inspection cover 5. Sensor label 6. Camera register Posición: Carcasa Registro para camara 50 1. Housing 2. Drive mechanism 3. Opening/closing slat 4. Inspection nismo de accionamiento cover 5. Thermoelectric starter mechanism BAT 6. Camera register de apertura/cierre FIREFIGHTING SYSTEMS FDMR Dimensions of the installation duct opening * Valid dimensions for FDMR. * The opening of the installation can be less than DN + 100mm - If the fire protection material can be installed correc

 Open the catalog to page 8
FIREFIGHTING SYSTEMS-9

FD SERIES FDMR Installation in solid wall construction Position: 2. Rigid wall construction Installation in cement or gypsum wall construction El perimetro de la apertura de la instalacion tiene que ser reforzado con perfiles de ye so estandar. 3. Mineral wool (type will depend on construction). FIREFIGHTING SYSTEMS Installation in solid ceiling construction Position 1 Fire damper 2 Solid ceiling construction 3 Cement or plaster 4 Duct * min. 110 - Concrete / min. 125 - Aerated Concrete * Around the perimeter The diagrams shown are for illustrative purposes only.

 Open the catalog to page 9
FIREFIGHTING SYSTEMS-10

FIREFIGHTING SYSTEMS Legend: Vn (m/s): Nominal speed m/s Pt = Pressure drop in Pa LwA: Sound power level in dB(A)

 Open the catalog to page 10
FIREFIGHTING SYSTEMS-11

FD SERIES FDMR TECHNICAL DATA Pressure loss calculation w 2 presure drop Pressureloss air flow velocity at nominal damper Air flow speed in nominal damper section section air density Air density coefficient of local pressure loss for the nominal damper section Local pressure loss coefficient for the nominal cross-section of the damper (see Tab. 11.1.1.) (see Tab. 11.1.1.). FIREFIGHTING SYSTEMS Determination of pressure loss using p=1.2kg.m³ diagram

 Open the catalog to page 11
FIREFIGHTING SYSTEMS-12

FD SERIES FDMR TECHNICAL DATA Acoustic output level corrected by filter A lwa - Lwi + 10 log(S) + Ka [dB(A)] Acoustic output level corrected by filter A [dB] Sound output level Lw1 related to 1 m2 cross-section (see Tab.1) [m2] Duct cross section [dB] Weight filter A correction (see Tab.2) Acoustic output level in octave ranges. LWoct - LW1 + 10 log(S) + Lrel [dB] Acoustic output spectrum in octave range [dB] Acoustic output level Lw1 related to 1 m2 cross-section (see Tab.1) [m2] Duct cross section [dB] Relative level expressing the shape of the spectrum (see Tab.3) Table of acoustic values...

 Open the catalog to page 12
FIREFIGHTING SYSTEMS-13

FD SERIES FDMR TECHNICAL DATA Tab.3 Relative level expressing the shape of the space Lrei f [Hz] w . V 63 125 250 500 1000 2000 4000 8000 FIREFIGHTING SYSTEMS

 Open the catalog to page 13
FIREFIGHTING SYSTEMS-14

SERIE FD FDMB FIRE DAMPER Model FDMB. FDMB series rectangular fire dampers function as separators between two fire sectors. They can be installed in both vertical and horizontal walls. They have a perimeter weatherstrip at both ends to ensure the airtightness between the damper and the air ducts. Caracteristicas: • Classification EI120 (ve ho i^^o) S (E) Integrity (I) Isolation (ho) Application in forged ceiling construction. Mounting in horizontal wall. (Ve) Application in wall or flexible wall. Mounting on vertical wall. (i^^o) Symmetrical (regardless of the direction of the air). Suitable...

 Open the catalog to page 14
FIREFIGHTING SYSTEMS-15

FD SERIES FDMB FIRE DAMPER FDMB.01 Position: 1. Damper housing 2. Mechanical 3. Damper blade 4. Inspection hole cover 5. Sensor label 6. Camera hole FIREFIGHTING SYSTEMS FDMB Installation duct opening dimensions Position: 1.Damper housing 2. Actuating mechanism 3. Damper blade 4. Inspection hole 5. Thermoelectric starting mechanism BAT 6. Camera hole Solid ceiling installation Solid-cement or plaster ceiling Position: 1. Fire damper 2. Solid ceiling 3. Mortar or plaster 4. Duct Installation opening Opening of installation Weichschott System *min.110- Hormigón/min125-Aerated concrete **Around...

 Open the catalog to page 15