Roth ClimaComfort Compact System

Roth ClimaComfort Compact System
1 / 44 PagesView full catalog

Roth ClimaComfort Compact System

Product catalog summary
System Description
The Roth ClimaComfort® Compact System is a versatile heating and cooling solution designed for use in floors, walls, and ceilings, suitable for both renovations and new constructions. It features a slim profile of 17 mm, enhancing its responsiveness, and utilizes a mineral-based filling and sealing compound instead of traditional heating screed, making it ideal for renovation projects.
System Benefits
Embedded in a thin layer of filling and sealing compound, the system is primarily used in renovation projects. It requires verification of the compound's suitability for specific applications, as it does not meet the minimum thickness under DIN 18560.
Applications and General Information
The system includes high-strength transparent panels with a 14 mm installation height for secure pipe fixing. These panels overlap for easy interconnection and have an adhesive back for secure fixing, making them suitable for low installation heights and weights, ideal for renovations.
System Components
The system comprises the Roth ClimaComfort® Compact System panel, ClimaComfort S5 System Pipes, and a filling and sealing compound. The pipes are resistant to stress cracking and thermal ageing, and the system includes various fittings and connectors for secure installation.
Set-up and Configuration
The system setup adheres to DIN EN 1264 and DIN EN 12831 standards. Insulation requirements vary based on the building structure, with specific guidelines for floors separating residential apartments and those adjacent to unheated rooms.
Performance Data
Heating curves and heat flow density are detailed for different pipe pitches and floor coverings, calculated according to DIN EN 1264 and registered with DIN CERTCO.
Installation Requirements
Installation requires specific subsurface conditions and tools, with detailed assembly instructions provided to ensure proper setup.
Commissioning
Includes pressure testing, water quality checks, functional heating, and curing processes. Floor coverings should be tested by the installer.
Processing Instructions for Filling and Sealing Compound
Instructions are provided for various manufacturers, including Henkel, Bostik, and PCI. The compound is ready-made and requires specific conditions for application.
Standards and Directives
The system complies with various standards and directives, ensuring quality and performance.
Guarantee
A guarantee is provided, ensuring the system's reliability and performance.
System Specifications
The document outlines specifications for the ClimaComfort S5 System Pipe, including installation spacing options of 75 mm, 150 mm, and 225 mm, and a pipe size of 11 x 1.30 mm. Heat flow density and heating medium upper temperature limits are specified, with boundary zone conditions set at tFmax-ti = 9 K and 15 K.
Performance Data
Performance data is provided for various thermal resistances of floor coverings, with detailed tables showing heat flow density at different heating medium temperatures and installation spacings.
Installation Requirements
Structural requirements for subsurfaces emphasize the need for non-yielding, high-tensile, and load-bearing surfaces, with specific requirements for different types of screeds and subsurfaces detailed according to DIN standards.
Recommendations for Wooden and Dry Construction Elements
Guidelines are provided for installing the system on wooden or dry construction elements, including the use of V 100 E 1 chipboards and OSB panels as per DIN 68771, stressing the importance of structural moisture protection and vapour barriers.
Additional Considerations
Instructions for incorporating expansion joints and ensuring proper drying of interior plasterwork are included, along with the need for a suitable primer and sanding for mastic asphalt screed.
Overview
The document provides detailed instructions for the installation and processing of the Roth ClimaComfort® Compact System on various subsurfaces, outlining necessary preparation, priming, smoothing, and adhesive application steps for different types of floor coverings.
Specifications
The document specifies the maximum area for application (25 m²) and the maximum surface temperature for parquet (27 °C), emphasizing the importance of consulting Kiesel application experts for specific guidance.
Procedures
The installation process involves preparing the subsurface by cleaning and applying primers, followed by smoothing with specific compounds, and detailing adhesives and joint mortars suitable for different floor coverings.
Functional Testing
A functional heating process is required after the application of the smoothing agent, which can be walked upon after 3 hours. Functional heating should begin 2 days post-application and last for 2 days, with floor coverings laid 1 day after the heating process.
Recommendations
The document advises maintaining an inlet temperature of 15 °C during cold seasons and ensuring the subsurface is stable, with additional isolation measures for wooden subsurfaces.
Limitations
The document notes that the latest manufacturer instructions take precedence over the provided guidelines, recommending expert advice for unique situations.
Key Products
The document mentions several key products, including Ardex adhesives, Sopro primers, and Weber smoothing agents, each with specific applications depending on the subsurface and floor covering type.
Specifications and Procedures
The document outlines installation and testing procedures for the ClimaComfort Compact System by Sakret-Sachsen, specifying area limits and functional heating protocols.
Installation Steps
1. Prepare the subsurface by smoothing, sanding, and vacuuming.
2. Apply a bonding layer with Wico 499 or an epoxy resin primer.
3. Lay the ClimaComfort Compact System, observing primer drying times.
4. Conduct a leak test before applying the filling and sealing compound.
5. Use Wicoplan 433 DE for filling and sealing.
6. Follow the heating protocol for functional heating.
7. Ensure the adhesive is suitable for floor heating systems when laying floor coverings.
Leak Testing
The leak test can be performed using water, compressed air, or inert gas, with specific test pressures and permissible pressure drops detailed.
Standards and Directives
The document references several German standards and directives, including the Energy Conservation Act and various DIN standards.
Guarantee and Warranty
The Roth ClimaComfort® Compact System comes with a warranty covering material defects or manufacturing faults for up to 10 years, with specific conditions for compliance.
Company Information
Roth Werke GmbH offers a comprehensive range of products and services, including radiant heating and cooling systems, with extensive support through a network of sales professionals and training courses.
See more

Catalog excerpts

Roth ClimaComfort Compact System-1

Energy Systems Roth ClimaComfort® Compact System Technical information and assembly instructions Living full of energy

 Open the catalog to page 1
Roth ClimaComfort Compact System-2

System description Applications and general information _ —3 Structure of the Roth ClimaComforf Compact System _ —9 Insulation requirements for existing buildings_ —9 Performance data Roth ClimaComforf Compact System heating curve, pipe pitch 75 mm _ —10 Roth ClimaComforf Compact System heating curve, pipe pitch 150 mm —10 System heat flow density _ —H Roth ClimaComforf Compact System heat flow density, floor applications -11 Heating, pipe pitch 150 mm, size 17 mm, filling and sealing compound -12 Heating, pipe pitch 225 mm, size 17 mm, filling and sealing compound —12 Thermal resistance of the...

 Open the catalog to page 2
Roth ClimaComfort Compact System-3

System description System benefits The Roth ClimaComfort* Compact System for heating and cooling via floors, walls, and ceilings in both modernisation and new-build projects is noted for its very slim size (just 17 mm) and the excellent responsiveness this helps deliver. Rotfi Wirfca GmbH RjurTiflSthtrtirtttSrierle Heil-uHd KCIhlJtfSteme mil Wilis* rdLirthsrrarttuily Roth ClimaComfort Compacliystom ZertirHjorunflEproflrarrmt RaumllaerwnldlOQritPlft Mflit- und KCihlsySteme bflWaifcJl unrl das NgtmngErnKiU far da; 5c*Chon in Vflrtxndijiig md d«r unljn g^nannUn Rvgul*rnumm«r vrlrl CHefiflft ZerLiftkal...

 Open the catalog to page 3
Roth ClimaComfort Compact System-4

System description ystem components S Roth ClimaComfort® Compact System panel High-strength transparent system panel with 14 mm installation height, of semi-crystalline material. The special panel structure with undercutting supports standardised and secure fixing of pipes. ClimaComfort S5 System Pipes 75 mm11 x 1,30 mm are installed in a coiled or meandering pattern as required using an installation grid of 75 mm. Diagonal installation with spacing of 105 mm is possible. ClimaComfort Compact System panels overlap by 22 mm on both sides to facilitate interconnection of the panels and have an...

 Open the catalog to page 4
Roth ClimaComfort Compact System-5

System description ClimaComfort S5 Pipe dimensions 120 m/5 kg or 240 m/10 kg small diameter for minimum installation heights light yellow pipe with red stripes Pipe layers Production processes Linear elongation coefficient [1/K] Building material class Pipe dimensions Pipe markings Metre details, pipe designation, material, dimensions, manufacturer, pipe class, max. temperature (long-term), oxygen tightness, any testing institute, date of manufacture, A number (manufacturer), running metre details Max. temperature over long term [°C] Max. temperature over short term [°C] Testing and certification...

 Open the catalog to page 5
Roth ClimaComfort Compact System-6

System description Roth ClimaComfort® Compact screw fitting For connecting the 11 x 1,30 mm Roth ClimaComfort S5 System Pipe to the Roth manifold with flow rate indicator. Consists of: a brass union nut with 3/4"/11 mm internal thread, brass pipe adapter with Euro cone and clamp ring. Technical data Dimension: Spanner size: Packing unit: Roth ClimaComfort® Compact screw fitting Roth ClimaComfort® Compact T-connection For connecting 2 heating circuits of the same length made from 11 x 1,30 mm Roth ClimaComfort S5 System Pipes to the heating circuit pipe coupling of the Roth manifold with flow...

 Open the catalog to page 6
Roth ClimaComfort Compact System-7

System description Roth ClimaComforf Compact press fitting For directly connecting 11 x 1,30 mm RothClimaComfort S5 System Pipes to other Roth System Pipes. Consists of a brass double nipple with press contour and screw thread for 11 x 1,30 mm Roth ClimaComfort S5 System Pipe, incl. stainless steel crimping sleeve and screw connection. Roth ClimaComfort* Compact press fitting Roth ClimaComforf Compact reducing pipe nipple Brass reducing component, one-sided 1/2" external thread, for connecting pipes and 11 x 1,30 mm Roth ClimaComfort S5 System Pipes, incl. screw connection. ^ ^^jng| Dimension:...

 Open the catalog to page 7
Roth ClimaComfort Compact System-8

System description Roth ClimaComfort® Compact expansion joint profile For the secure separation of field areas and the formation of permanently flexible joints consisting of a closed-cell PE core with stable PET coating and 90° angled, self-adhesive contact zone, 8 mm wide, 40 mm high, and 1800 mm long. > Packing unit: 1 pcs. Roth ClimaComfort® Compact expansion joint profile Roth Pipefix 11 U rail with 25 mm perforated grid for fixing pipes on uneven surfaces (wall and slab), adapted to Roth 11 mm ClimaComfort S5 System Pipes with predefined separation points. The base is selfadhesive. > Dimensions:...

 Open the catalog to page 8
Roth ClimaComfort Compact System-9

Set-up and configuration The calculations for the Roth ClimaComfort® Compact System are based on the basic characteristic curve under DIN EN 1264, Part 2 and the DIN EN 12831 standard heating load calculation. The system layout is based on the sizes calculated in accordance with DIN EN 1264, taking into account the permitted limit values from the system performance charts. tructure of the Roth ClimaComfort® Compact System S Wall Wand Thermosiphon system It can also be used in a thermosiphon system. Roth Clim Plaster Putz Roth Randdämmstreifen edge insulating strip Roth ClimaComfort S5 System...

 Open the catalog to page 9
Roth ClimaComfort Compact System-10

Performance data oth ClimaComfort® Compact System heating curve, pipe pitch 75 mm R Floor structure: 17 mm, filling and sealing compound + tiles (RλB = 0,01 m2K/W), change in inlet temperature 20 °C to 32,7 °C (constant), room temperature 20 °C Inlet temperature Average floor temperature Heat flow density in W/m2 Heat flow density oth ClimaComfort® Compact System heating curve, pipe pitch 150 mm R Floor structure: 17 mm, filling and sealing compound + tiles (RλB = 0,01 m2K/W), change in inlet temperature 20 °C to 32,7 °C (constant), room temperature 20 °C Heat flow density Average floor temperature...

 Open the catalog to page 10
Roth ClimaComfort Compact System-11

Performance data ystem heat flow density S The performance data for the heating and cooling surfaces has been calculated according to DIN EN 1264 and registered with and monitored by DIN CERTCO. DIN CERTCO registration number: 7 F 221-F Installation zone condition tFmax-ti = 9 K ClimaComfort S5 System Pipe 11 x 1,30 mm, filling and sealing compound 17 mm =1,20 W/mK Boundary zone condition tFmax-ti = 15 K System heating medium upper temperature limit System heat flow density limit System heating medium upper temperature limit Thermal resistance floor covering System characteristic curve System...

 Open the catalog to page 11

Archived catalogs

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.