Overview: The document provides comprehensive specifications and operational guidelines for SupraBox Comfort Compact Ventilation Units, covering aspects such as hygiene, housing, heat recovery, filters, connections, fans, accessories, and control systems.
Hygiene Requirements: The units adhere to VDI 6022 standards, featuring smooth, easily cleanable surfaces.
Housing: The design is frameless with double-layered sidewalls made from galvanized steel, offering 40mm insulation for ceiling units and 60mm for standalone units.
Heat Recovery: High-efficiency counter flow heat exchangers are used, achieving over 90% efficiency and ensuring complete separation of supply and return air.
Filters: The units are equipped with fine dust filters, class F7 for supply air and class M5 for return air, with quick release fasteners for easy changes.
Connections: Designed to industry standard sizes, providing ample room for pipe and duct connections.
Fans: Energy-efficient EC-fans are featured, with an optional boost-mode for increased performance.
Accessories: Optional heating and cooling coils are available, along with electronic pre-/supplementary heating coils.
Integrated Controller: A pre-wired integrated controller is included, offering various control functions and an optional heater/cooler.
Efficiency and Air Flow: High efficiency cross counter flow plate heat exchangers are used, with efficiency ratings dependent on operating conditions. Graphics illustrate efficiency ratings under different conditions.
Antifreeze Protection: Sequences for antifreeze protection are described, including differential pressure switch signals and preheating sequences.
Technical Specifications: Detailed specifications for models SupraBox 800 H and SupraBox 1100 H are provided, including dimensions, operating points, fan details, heat recovery efficiency, air filter specifications, and control features.
Sound and Air Performance: Sound power levels and air performance data are provided, with correction values for different frequencies.
Technical Specifications Overview:
  • SupraBox 1500 H: Dimensions: 1670 x 1520 x 700 mm, Air flow volume: 1,500 m³/h, External pressure increase: 200 Pa, Fans: 230 V / 50 Hz, 6 A, 2900 RPM, 2 x 470 W, SFP 3, Heat Recovery: Up to 92% efficiency, Air Filter: Supply air F7, Exhaust air M5, Weight: 298 kg, Max air flow temperature: 40°C.
  • SupraBox 2000 H: Dimensions: 1800 x 1660 x 760 mm, Air flow volume: 2,000 m³/h, External pressure increase: 250 Pa, Fans: 230 V / 50 Hz, 10 A, 2450 RPM, 2 x 800 W, SFP 3, Heat Recovery: Up to 92% efficiency, Air Filter: Supply air F7, Exhaust air M5, Weight: 377 kg, Max air flow temperature: 40°C.
  • SupraBox 3500 H: Dimensions: 2320 x 1925 x 840 mm, Air flow volume: 3,500 m³/h, External pressure increase: 400 Pa, Fans: 400 V / 50 Hz, 5.0 A, 2330 RPM, 2 x 1600 W, SFP 4, Heat Recovery: Up to 92% efficiency, Air Filter: Supply air F7, Exhaust air M5, Weight: 530 kg, Max air flow temperature: 40°C.
  • SupraBox 800 V: Dimensions: 1470 x 1145 x 600 mm, Air flow volume: 800 m³/h, External pressure increase: 150 Pa, Fans: 230 V / 50 Hz, 3 A, 2300 RPM, 2 x 225 W, SFP 2, Heat Recovery: Up to 92% efficiency, Air Filter: Supply air F7, Exhaust air M5, Weight: 209 kg, Max air flow temperature: 40°C.
  • SupraBox 1100 V: Dimensions: 1740 x 1225 x 630 mm, Air flow volume: 1,100 m³/h, External pressure increase: 200 Pa, Fans: 230 V / 50 Hz, 4 A, 2600 RPM, 2 x 320 W, SFP 2, Heat Recovery: Up to 92% efficiency, Air Filter: Supply air F7, Exhaust air M5.
General Features: Frameless housing with 60 mm insulation, coil coated inside and out (RAL 7035), conforms to VDI 6022, integrated control (Plug & Play), energy-efficient EC-fans, high-efficiency heat recovery, service doors and bypass included, interior installation with optional weather-proof model.
Sound and Noise Levels: Detailed sound power levels provided for each model, with correction values for octave bands included.
Accessories: Various accessories available including temperature sensors, CO2 sensors, flexible ducts, shut-off dampers, duct silencers, and reheating coils.
Note: A detailed calculation example is available on page 40.
Technical Specifications Overview:
  • Air Filters: Panel filters with a plastic frame, supply air filter rated F7, exhaust air filter rated M5 (formerly F5), dimensions vary across models.
  • Air Connections: Vertical or horizontal, with duct air speeds ranging from 3.3 m/s to 4.4 m/s, depending on the model.
  • Controller: Includes supply air, exhaust air, and room temperature control. Fans are steplessly adjustable, with a modulating bypass function (0-10V). No control damper through the heat recovery, but a control damper through the bypass.
  • Weight and Dimensions: Weight ranges from 188 kg to 430 kg, dimensions vary by model.
  • Max Air Flow Temperature: Maximum air flow temperature is 40°C, with higher temperatures available upon request.
  • Standard Equipment: Frameless housing with insulation, coil coating inside and out, compliance with VDI 6022, integrated control (Plug & Play), energy-efficient EC-fans, high-efficiency heat recovery, two service doors with a bypass.
  • Sound Power Levels: Provided for different sides of the units, with correction values for octave bands. Sound data is represented as A-weighted apparent sound power levels in dB(A).
  • Accessories: Various accessories available, including preheat coils, reheat coils, aftercoolers, temperature sensors, CO2 sensors, flexible ducts, shut-off dampers, duct silencers, and electric reheating coils.
  • Air Performance: Data provided in terms of air flow volume, external pressure increase, and sound levels for each model.
Overview: The document provides detailed technical specifications and operational guidelines for the SupraBox Comfort ventilation units, including dimensions, control systems, accessories, and installation requirements.
Specifications: Outlines dimensions and configurations of the SupraBox models, specifying materials used, such as galvanized steel for the outer cover and perforated inner pipe, and details sound dampening properties.
Control System: Equipped with a modern DDC-technology controller designed for ease of use and safety, featuring a built-in weekly and yearly clock, multiple user levels, and the ability to connect additional sensors for enhanced temperature control. The control panel supports both German and English languages.
Control Functions: Lists various control functions available as standard, such as filter monitoring, temperature control, fan control, and frost prevention. Describes necessary accessories and inputs required for specific functions.
Accessories: A range of accessories is available, including temperature sensors, hygrostats, RS 485 interfaces, and duct silencers. Provides part numbers and specifications for each accessory, emphasizing their role in enhancing the system's functionality.
Installation Notes: Important guidelines provided, such as maintaining minimum air flow for heating coils and positioning duct temperature sensors to avoid heat interference. Discusses conditions under which preheating is necessary to prevent freezing.
Performance Data: Includes performance data for electric reheating coils, detailing their capacity, voltage requirements, and air flow rates. Provides graphical representations of temperature increases relative to air flow.
Overview: The document provides technical specifications and installation guidelines for SupraBox units, focusing on preheating and cooling systems, including details on electric preheating coils, PTC electronic preheaters, and hot and cold water pump systems.
Preheating Systems:
  • Equipped with electric preheating coils for safe operation in winter, particularly in Central Europe. These coils are single-step, non-controlled, and managed by the SupraBox controller.
  • For sizes 800 and 1100, PTC electronic preheaters are available, adjusting power consumption based on temperature and including a temperature monitor to prevent overheating.
  • Preheating coils are designed for building installations only, with minimal air pressure drop.
Cooling Systems:
  • Cold water pump coolers available for various models, designed to operate with water or water-glycol mixtures, featuring galvanized steel frames, aluminum condensate tubs, and integrated demisters.
  • Cooling performance influenced by air entry temperature, humidity, and air flow volume, with diagrams illustrating cooling output and pressure loss.
Heating Systems:
  • Hot water pump reheaters available for different models, featuring galvanized steel frames and frost prevention thermostats, suitable for both left and right connection sides.
  • Performance diagrams show heat output and pressure loss based on air flow volume and temperature conditions.
Accessories and Installation Kits:
  • Installation kits include electronic heaters, air flow monitors, and necessary valves. Specifies connection diameters, performance ratings, and minimum air flow requirements for each model.
  • 3-way valves included with hot and cold water pump coils, designed for mixing and complying with pressure device guidelines.
Valve Specifications: Internal leakage with a closed valve is specified as 0.05% of kVS in flow direction A-AB and a maximum of 1% in flow direction B-AB. Each installation kit includes appropriate screw connections with seals for all three connections of the valve and the actuator. The nominal diameter of the screw connections matches that of the valves.
Accessories:
  • Actuator for 3-way valves: Type AME 435, Protection IP54, Ambient temperature 0 to 55°C, 24V AC, max. 4.5 VA, continuous adjustment, maximum pulling load 400N, adjustment speed 7.5 s/mm, easy installation.
  • Duct Temperature Sensor: Type EKFC 10/150, Sensor Type NTC 10K, Resistance 10 kΩ at 25°C, Protection IP65, Measurement range -30 to 150°C, Ambient temperature max. 70°C, Sensor pipe Ø 6mm, Installation length 165 mm.
  • Frost Protection Thermostat: Type JTF-5, Protection IP40, control range -10 to +12 °C, switching difference 1 K, Ambient temperature -10 to +55 °C, Sensor: copper gas-filled.
Sound Data Calculation Example: Provides a calculation example for sound data using a SupraBox 2000 H. The nominal operating point is 2000 m³/h with an external pressure increase of 250 Pa. Sound data is represented as the A-weighted apparent sound power level of the housing LWA2 in dB(A). The pressure side apparent sound power level LWA5 is calculated as LWA2 + 2 dB, and the discharge side apparent sound power level LWA6 is LWA2 + 25 dB. Correction values are applied per octave to calculate LWA6(Okt).
See more

Catalog excerpts

Energy recovery units SupraBox COMFORT-1

Properties of the Compact Ventilation Units Type: SupraBox Comfort Hygiene Requirements The SupraBox Comfort Compact Ventilation Units conform to the current version the norm according to VDI 6022. The units have smooth surfaces (coil coated inside and out – RAL 7035) and are easily cleaned. Housing The units contain a sturdy frameless housing. The sidewalls have a double-layered design. The inside and outside metal sheets are made from 1 mm galvanized (coated) steel plate. The insulation thickness is 40 mm for ceiling units and 60mm for stand-alone units. Heat Recovery High efficiency counter flow heat exchangers with over 90% efficiency are utilized for heat recovery. Complete separation supply air and return air without odor transfer is ensured. Filter Fine dust filters of filter class F7 for supply air and class M5 (formerly F5) for return air are utilized for serial production. Quick release fasteners make changing filters fast and easy. Hot water Heater coil of the Construction Line SupraBox Comfort Pipe and Duct Connections The connections are designed for ample room. The connection sizes are the same as the industry standard sizes. EC-Fans EC-fans in compact design with modern EC-motors from inhouse production make for quiet and energy efficient operation across the entire product line. For temporary increased performance an optional boost-mode is available (upon request). Accessories (optional) For units from the SupraBox Comfort line an optional heating and cooling coil (hot water/cold water) for raising or lowering the room temperature is available. Furthermore additional electronic pre-/supplementary heating coils are offered. Hot water Heater coil of the Construction Line SupraBox Comfort Integrated Controller The SupraBox Compact Ventilation Units are equipped with an integrated controller as standard. All internal components are already pre-wired. Temperature control is possible with an optionally available heater/cooler. Many control functions are integrated into the software and can easily be subsequently activated. A control until for setting operating parameters is enclosed as standard. Controll of the SupraBox Comfort Line Edition: 10/2012 DE • Revisions and errors expected. Reproductions, even excerpts, are only allowed with written approval from Rosenberg Ventilatoren GmbH, Künzelsau – Gaisbach

 Open the catalog to page 1
Energy recovery units SupraBox COMFORT-2

Heat Recovery Efficiency of the Heat Recovery The SupraBox-Units are equipped with high efficiency cross counter flow plate heat exchangers made from corrosionresistant aluminum. The actual efficiency ratings that can be attained depend primarily on the operating conditions. Outdoor Air Temperature and Return Air Humidity During most times of the year the humidity of the return air is irreverent. If supply air and return air flow volumes are identical then the SupraBox attains efficiency ratings over 80%. With falling outdoor temperatures the surface temperature of the plate heat exchanger also...

 Open the catalog to page 2
Energy recovery units SupraBox COMFORT-3

Heat Recovery Level of Return Air Volume in relation to Supply Air Volume 200% Ventilation heat loss The level of the return air volume in correlation to the supply air also has a strong influence on the efficiency of the heat recovery. If the return air volume is reduced compared to the supply air volume, then the efficiency rating of the heat recovery with regards to the supply air is also decreased. By looking at the resulting ventilation heat loss, an assessment is made possible of the higher return air in regards to the supply air. Since the entire air volume in the room to be ventilated...

 Open the catalog to page 3
Energy recovery units SupraBox COMFORT-4

Standard equipment: • frameless housing with 60 mm insulation • coil coated inside and out (RAL 7035) • conforms to VDI 6022 • integrated control (Plug & Play) • horizontal connections • energy efficient EC-fans • high efficiency heat recovery • 2 service doors; bypass • interior installation Part Number (please note the connection side supply air connections LEFT/RIGHT!) Weather-Proof Model (please note the connection side supply air connections SB080HGLWB00 (LEFT) ; SB080HGRWB00 (RIGHT) 1330 x 1220 x 640 mm incl. controller box and adjustable feet Operating Point Air flow volume Vnenn ext....

 Open the catalog to page 4
Energy recovery units SupraBox COMFORT-5

Sound power level: The sound data represented in the air performance curve is the A-weighted apparent sound power level of the housing LWA2 in dB(A). Pressure side apparent sound power level Lwa5 = Lwa2 + 2 dB Discharge side apparent sound power level Lwa6 = Lwa2 + 20 dB Calculation: Lwa5 per octave: LwA5(Okt) = Lwa5 + correction value (table row LWA5) Lwa6 per octave: LwA6(Okt) = Lwa6 + correction value (table row LWA6)

 Open the catalog to page 5
Energy recovery units SupraBox COMFORT-6

Standard equipment: • frameless housing with 60 mm insulation • coil coated inside and out (RAL 7035) • conforms to VDI 6022 • integrated control (Plug & Play) • horizontal connections • energy efficient EC-fans • high efficiency heat recovery • 2 service doors; bypass • interior installation Article No. (please note the connection side supply air connections LEFT/RIGHT!) Weather-Proof Model (please note the connection side supply air connections LEFT/RIGHT!) 1500 x 1420 x 660 mm incl. controller box and adjustable feet Operating Point Air flow volume V 1.100 m3/h Fans Voltage Max. power consumption RPM Wattage SFP-class...

 Open the catalog to page 6
Energy recovery units SupraBox COMFORT-7

Sound power level: The sound data represented in the air performance curve is the A-weighted apparent sound power level of the housing LWA2 in dB(A). Pressure side apparent sound power level Lwa5 = Lwa2 + 1 dB Discharge side apparent sound power level Lwa6 = Lwa2 + 24 dB Calculation: Lwa5 per octave:: LwA5(Okt) = Lwa5 + correction value (table row Lwa5) Lwa6 per octave: LwA6(Okt) = Lwa6 + correction value (table row Lwa6)

 Open the catalog to page 7
Energy recovery units SupraBox COMFORT-9

Sound power level: The sound data represented in the air performance curve is the A-weighted apparent sound power level of the housing LWA2 in dB(A). Pressure side apparent sound power level LWA5 = LWA2 +4 dB Discharge side apparent sound power level LWA6 = LWA2 +27 dB Calculation: Lwa5 per octave: LwA5(Okt) = Lwa5 + correction value (table row Lwa5) Lwa6 per octave: LwA6(Okt) = Lwa6 + correction value (table row Lwa6) Note: a detailed calculation example can be found on page 40 Dimensions: All dimensions are in mm. The model in the drawing is shown with supply air connections LEFT. The model...

 Open the catalog to page 9

Archived catalogs

  1. WORLD OF FANS

    450  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.