Compact ventilation units
26Pages

{{requestButtons}}

Catalog excerpts

Compact ventilation units - 1

Betriebsanleitung Operating instruction EN Compact ventilation units Series SupraBox COMFORT Rosenberg Ventilatoren GmbH · Maybachstraße 1 · 74653 Künzelsau-Gaisbach BA 112 BB 11/12/A/SupraBox 1 Tel.: +49(0)7940/142-0 · Fax.: +49(0)7940/142-125 · Email: info@rosenberg-gmbh.com · www.rosenberg-

Open the catalog to page 1
Compact ventilation units - 2

Operation and Maintenance Manual for Rosenberg Compact Ventilation Appliance series SupraBox Comfort

Open the catalog to page 2
Compact ventilation units - 3

Operation and Maintenance Manual for Rosenberg Compact Ventilation Appliance series SupraBox Comfort 1. General Safety Information 1.1 Warnings regarding industrial safety measures The following icons inform about certain hazards or safe use. Attention! Danger! Safety Advice! Hazard by electricity or high voltage! Crush hazard! Danger Overhead Hazard Important Advice, Information

Open the catalog to page 3
Compact ventilation units - 4

Operation and Maintenance Manual for Rosenberg Compact Ventilation Appliance series SupraBox Comfort 1.2 Safety Instructions At the time of delivery the Rosenberg SupraBox Comfort series is constructed and produced according to the latest technical standard. Substantial tests of material, function and quality guarantee a high value and a long lifetime. When improperly used by untrained staff or not according to the instructions these machines can be dangerous. Read these instructions carefully prior to unpacking, assembling or performing the maintenance! The system may only be used after...

Open the catalog to page 4
Compact ventilation units - 5

Operation and Maintenance Manual for Rosenberg Compact Ventilation Appliance series SupraBox Comfort 2. Technical Manual 2.1 General Description • According to the EC Machinery Directive stationery ventilation appliances have to be electrically connected to a breaker and a series fuse. It must be possible to disconnect the unit from all poles! The unit corresponds to the requirements of VDI 6022 as well as DIN 1946 T6. Depending on the size of the installation the range of application extends to power volume of 3500 m³/h with a transport density of 1,3kg/m³. The application area includes...

Open the catalog to page 5
Compact ventilation units - 6

Operation and Maintenance Manual for Rosenberg Compact Ventilation Appliance series SupraBox Comfort2.2 Device Overview SupraBox Comfort Temperature control with control of the optional accessories according to the unit size and equipment._

Open the catalog to page 6
Compact ventilation units - 7

Operation and Maintenance Manual for Rosenberg Compact Ventilation Appliance series SupraBox Comfort SupraBox Comfort

Open the catalog to page 7
Compact ventilation units - 8

Operation and Maintenance Manual for Rosenberg Compact Ventilation Appliance series SupraBox Comfort Picture: drawing of the device overview 1 Panel filter exhaust air M5 2 Panel filter incoming air F7 3 Adjustable rounded base 4 Bypass flap 5 Maintenance pan 6 Reverse flow heat exchanger 7 Condensate pan 8 Exhaust fan with EC-motor 9 Incoming air fan with EC-motor 10 Control box incl. control system 11 Main breaker

Open the catalog to page 8
Compact ventilation units - 9

Operation and Maintenance Manual for Rosenberg Compact Ventilation Appliance series SupraBox Comfort 2.3 Device drawings Suprabox 800 H Condensate drain through the hose sleeve 19,4 x 3,7 Condensate drain through the hose sleeve 19,4 x 3,7

Open the catalog to page 9
Compact ventilation units - 10

Operation and Maintenance Manual for Rosenberg Compact Ventilation Appliance series SupraBox Comfort Suprabox 1500 H A hose with appropriate hose sleeve is recommended for the condensate drain 19,4 x 3,7 Condensate drain through the hose sleeve 19,4 x 3,7

Open the catalog to page 10
Compact ventilation units - 11

Operation and Maintenance Manual for Rosenberg Compact Ventilation Appliance series SupraBox Comfort SupraBox 3500 H Condensate drain through the hose sleeve 19,4 x 3,7 The Rosenberg compact series SupraBox Comfort is exclusively made for treating air or gaseous media according to the criteria stated below! The compact ventilation appliancet is suitable for the conveyance of: • Clean air, low dust or low greasy air Slightly aggressive gases or fumes (consult the factory in either case!) Gaseous media up to a density of 1.3 kg/m³ Gaseous media up to a relative humidity of max. 95 % Gaseous...

Open the catalog to page 11
Compact ventilation units - 12

Operation and Maintenance Manual for Rosenberg Compact Ventilation Appliance series SupraBox Comfort 4. Delivery, Transport and Storage 4.1 Delivery The Rosenberg-Suprabox must be checked for damages immediately on delivery. This should be made before unloading the device from the transport vehicle. Furthermore the completeness of the delivery scope must be checked in accordance with the freight documents. Missing parts or damages must be noted immediately on the freight documents and signed by the driver of the transport vehicle. 4.2 Transport The unit will be delivered on a customized...

Open the catalog to page 12
Compact ventilation units - 13

Operation and Maintenance Manual for Rosenberg Compact Ventilation Appliance series SupraBox Comfort Avoid twisting, bending or other physical damages of the housing when hoisting the device! • Keep the control doors closed during transport! Always use proper hoisting machines! Please note that excessive loads on the housing may cause damages! For your own safety use appropriate anti-slip gloves and safety shoes for the transport. For the transport with forklift or pallet truck please note the following instructions: • The transport with industrial trucks requires regular training of the...

Open the catalog to page 13
Compact ventilation units - 14

Operation and Maintenance Manual for Rosenberg Compact Ventilation Appliance series SupraBox Comfort It is forbidden to use chain slings or slinging ropes for the direct load attachment! The slings should not have an inclination angle of more than 60° ! Inclination angle smaller than 60° Inclination angle greater than 60° Picture: Transport by crane Please note that when lifting the functional part the distribution is usually out of balance! This is not visible from outside of the functional part! Low load Heavy load Picture: load distribution Only use carrying devices with the same length....

Open the catalog to page 14
Compact ventilation units - 15

Operation and Maintenance Manual for Rosenberg Compact Ventilation Appliance series SupraBox Comfort 4.3 Storage • Make sure to store the unit in a dry and weather protected area! On receipt of the merchandise the packaging, film and tape must immediately be removed in order to avoid condensation water! Open pallets must be covered by tarps. Protect the functional parts against pollution (e.g. chips, stones, wires etc.). Also the weatherproof functional parts must be covered, as the weather resistance can only be guaranteed after the installation. Keep the storage temperature between -20°...

Open the catalog to page 15

All Rosenberg Ventilatoren catalogs and technical brochures

  1. AIR CURTAINS

    80 Pages

  2. AIR CURTAINS

    84 Pages

  3. EC FANGRID

    2 Pages

  4. FANS

    23 Pages

  5. Ex fans

    120 Pages

  6. EC-Radial Fans

    37 Pages

Archived catalogs

  1. WORLD OF FANS

    450 Pages