intumescent-pillows-ce-datasheet - 1

Temporary firestop solution for service voids in walls

Open the catalog to page 1
intumescent-pillows-ce-datasheet - 2

FIREPRO® INTUMESCENT PILLOWS CE FIREPRO® INTUMESCENT PILLOWS CE ROCKWOOL Intumescent Pillows CE provide up to 2 hours (EI 120) fire protection for differing services. They are designed to provide fire stopping to metal services, plastic conduits and cables passing through fire resisting compartment walls.

Open the catalog to page 2
intumescent-pillows-ce-datasheet - 3

FIREPRO® INTUMESCENT PILLOWS CE Easy to remove and reinstate when changing services Maintenance free FIREPRO® Intumescent Pillows CE consist of intumescent material encased within a waterproof glass cloth bag. Intumescent Pillows CE are designed to create a temporary or permanent fire seal around all types of services to maintain continuity of fire performance of compartment walls. They are an ideal solution for applications where services are required to be changed or replaced on a regular basis. Under fire conditions, Intumescent Pillows CE expand several times their original volume to...

Open the catalog to page 3
intumescent-pillows-ce-datasheet - 4

FIREPRO® INTUMESCENT PILLOWS CE Performance Fire performance ROCKWOOL Intumescent Pillows CE provide up to 2 hours fire rating where services pass through fire-rated walls. Table 1 Performance in Masonry Supporting Walls - BS EN 1366-3:2009 Rigid wall construction 150mm thick (min.) Intumescent Pillow CE seals 330mm deep laid centrally within the aperture with 75mm projection from each face of wall. Additional FIREPRO® Intumescent Pillows CE to be sewn to provide additional protection to the cable to minimum distance of 300mm either face of the seal. Fire Resistance (min) Integrity (E)...

Open the catalog to page 4
intumescent-pillows-ce-datasheet - 5

FIREPRO® INTUMESCENT PILLOWS CE Table 2 Performance in Masonry Supporting Walls - BS EN 1366-3:2009 Rigid wall construction 150mm thick (min.) Intumescent Pillow CE seals 330mm deep laid centrally within the aperture with 75mm projection from each face of wall. Fire Resistance (min) Integrity (E) 165mm Ø x 5.6-14.2mm thick mild steel pipe (C/U)* 48mm Ø x 3.5-14.2mm thick steel pipe with 300mm local interrupted (LI)** foil faced cermic blanket 7mm thick (C/U)* 113mm Ø x 4.5-14.2mm thick steel pipe with 300mm local interrupted (LI)** foil faced cermic blanket 10mm thick (C/U)* Note: Maximum...

Open the catalog to page 5
intumescent-pillows-ce-datasheet - 6

FIREPRO® INTUMESCENT PILLOWS CE Technical information Standards and approvals FIREPRO® Intumescent Pillows CE have been tested in accordance with BS EN 1366 Part 3: March 2009 achieving fire resistance of up to 2 Hours (EI120) in walls and dependent upon service type - see Tables 1 & 2 (pages 4 & 5). Product information Property Fire Resistance Up to 2 hours integrity and insulation (EI120) Shelf Life N/A if stored in cool, dry, well ventilated area Airborne Sound Insulation Rw (C,Ctr) = 33 (0,-2)

Open the catalog to page 6
intumescent-pillows-ce-datasheet - 7

FIREPRO® INTUMESCENT PILLOWS CE Installation Installation in walls 1. ush P the first Intumescent Pillow CE into the hole to be filled, so that the longest dimension (330mm long) spans across the wall with 75mm projection from either face. the hole tightly with additional Intumescent Pillows CE, staggering the joints, until it is tightly packed. wall penetrations, the pillows are normally self supporting, but for large openings with few penetrations, you may require a steel retaining mesh for support on both sides of the penetration. pillows are used as appropriate to fill smaller gaps....

Open the catalog to page 7
intumescent-pillows-ce-datasheet - 8

FIREPRO® INTUMESCENT PILLOWS CE Specification clauses Health & Safety FIREPRO Intumescent Pillows CE are associated with the following NBS clauses: The safety of ROCKWOOL stone wool is confirmed by current UK and Republic of Ireland health & safety regulations and EU directive 97/69/EC:ROCKWOOL fibres are not classified as a possible human carcinogen. • P12 Fire stopping systems • 345 Intumescent pillows Disclaimers This product should only be utilised for applications as outlined in the relevant ROCKWOOL product datasheet and in accordance with the relevant ROCKWOOL Fire Resistance...

Open the catalog to page 8
intumescent-pillows-ce-datasheet - 9

FIREPRO® INTUMESCENT PILLOWS CE For further information, contact the Technical Solutions Team on 01656 868490 or email technical.solutions@rockwool.co.uk Visit www.rockwool.co.uk to view our complete range of products and services. Copyright ROCKWOOL September 2020

Open the catalog to page 9
intumescent-pillows-ce-datasheet - 10

FIREPRO® INTUMESCENT PILLOWS CE

Open the catalog to page 10
intumescent-pillows-ce-datasheet - 11

FIREPRO® INTUMESCENT PILLOWS CE

Open the catalog to page 11
intumescent-pillows-ce-datasheet - 12

February 2021 ROCKWOOL Limited Pencoed Bridgend CF35 6NY Tel: 01656 862 621 info@rockwool.co.uk rockwool.co.uk

Open the catalog to page 12

All ROCKWOOL catalogs and technical brochures

  1. Fire Duct

    5 Pages

  2. CAVITY

    12 Pages

  3. firepro-book

    109 Pages

  4. CLADDING ROLL

    12 Pages

  5. Twinroll

    8 Pages

  6. FLEXI®

    20 Pages

  7. ROCKFRAME

    4 Pages

  8. Rockwool vrb

    3 Pages

  9. ROCKPRIME®

    2 Pages

  10. RECYCLING

    4 Pages

  11. EDC

    8 Pages

  12. CORE RANGE

    24 Pages

  13. CORROSION

    20 Pages