PROMASEAL®
32Pages

{{requestButtons}}

Catalog excerpts

PROMASEAL® - 1

Promat PROMASEAL Fire Stopping Installation Guide

Open the catalog to page 1
PROMASEAL® - 2

Promat PROMASEAL® Fire Stopping Installation Guide Introduction CONTACTS Promat Customer Relations Team For Technical enquiries contact 01344 381 400 E-mail: technicaluk@promat.co.uk For Commercial enquiries, contact 01344 381 381 E-mail: salesuk@promat.co.uk Promat Marketing Services Department Telephone: 01344 381 350 Fax: 01344 381 301 E-mail: marketinguk@promat.co.uk

Open the catalog to page 2
PROMASEAL® - 3

ABOUT Promat Promat UK is a subsidiary of Promat International, part of the Etex Group of companies, a global organisation with over 13,500 employees and a presence in more than 42 countries. Promat is a market leader in passive fire protection and high temperature insulation products. The fire protection division offers an extensive range of boards, penetration seals, glazing and spray products designed to provide systems which meet the most stringent requirements of today’s construction projects. THE Promat PROMASEAL® RANGE The Promat PROMASEAL® range of fire stopping products is one of...

Open the catalog to page 3
PROMASEAL® - 4

Product Selector PROMASEAL® Expansion Joint Strip Cavity Non ferrous metals Steel or cast iron Electrical cables Cable trays Single cables PROMASEAL® Fire Barrier PROMASEAL® Fire Compound PROMASEAL® Fire Compound Extra Strength PROMASEAL® Fire Pillows PROMASEAL® Intumescent Sealant PROMASEAL® Silicone Sealant PROMASEAL® Pipe Wrap Promat PROMASLAB™

Open the catalog to page 4
PROMASEAL® - 5

Product Selector Which system(s) to use As penetration can occur in various building elements, there are a number of important criteria that require consideration in determining the appropriate type of sealing system to be used, simplified in the following chart. Fire resistance period? Wall, floor, linear gap? Insulation requirement? Mechanical strength? Thermal expansion Considerations • Size of opening • Ambient conditions • Frequency of change to services • Penetration services • Design life • Parent const

Open the catalog to page 5
PROMASEAL® - 6

Sealing movement joints at junctions for walls and floors. INTRODUCTION Promat PROMASEAL® Expansion Joint Strips are highly compressible, flexible, fire resistant seals which are used where movement joints are formed in the structure of a building. Promat PROMASEAL® Expansion Joint Strips consist of layers of intumescent material bonded to Class 0 foam and have been successfully fire tested and assessed to provide up to 240 minutes in joints in walls and floors. APPLICATIONS Promat PROMASEAL® Expansion Joint Strips are ideal for sealing movement joints at junctions between compartment walls...

Open the catalog to page 6
PROMASEAL® - 7

Promat PROMASEAL® Expansion Joint Strip sizes for blockwork/ masonry/concrete (aerated or normal) wall and floor installations (minimum 150mm thick) NOTE: The block/masonry/concrete walls and floors shall be at least 150mm thick and have at least the same fire rating as that required for the penetration seal. Block/masonry and concrete gap faces will be within the density range of 450 to 2300kg/m3 and gap faces will be free from loose or flaking material. Provides up to 240 minutes fire resistance (integrity). Contact the Customer Relations Team on 01344 381 400 for further information.

Open the catalog to page 7
PROMASEAL® - 8

Promat PROMASEAL® Fire Barrier Certifire Approval No CF 426 6 PRODUCT DESCRIPTION Promat PROMASEAL® Fire Barriers are slabs of high density rock wool with a white endothermic, ablative coating. APPLICATION Promat PROMASEAL® Fire Barriers are used to stop the spread of fire through openings in fire resistant walls and floors where these are used for the passage of building and communications services. Acoustic data is available on this product, please contact the Customer Relations Team on 01344 381 400. 5 Promat PROMASEAL® Fire Barriers are designed to be installed within openings in...

Open the catalog to page 8
PROMASEAL® - 9

Detail 2 Lightweight Partition - The lightweight partitions should be tested to BS 476: Part 22: 1987 to the same or greater period of fire resistance as the Fire Barrier System. Services should be rigidly supported via steel angles, hangers or channels, not further than 500mm from the surface of the sealing system on both faces. Detail 3 Floor Penetration - The aperture must be formed from track sections and be lined with two layers of 12.5mm thick Type 'F' gypsum boards. Promat PROMASEAL® Fire Barrier - Approval Matrix: Up To 60 Minute Walls

Open the catalog to page 9
PROMASEAL® - 10

Promat PROMASEAL® Fire Barrier Certifire Approval No CF 426 Promat PROMASEAL® Fire Barrier - Approval Matrix: Up To 120 Minute Walls

Open the catalog to page 10
PROMASEAL® - 11

Promat PROMASEAL® Fire BarrierCertifire Approval No CF 426 Promat PROMASEAL® Fire Barrier - Approval Matrix: Up To 240 Minute Walls Barrier For other applications, please contact the Promat Customer Relations Team on 01344 381 400.

Open the catalog to page 11
PROMASEAL® - 12

Promat PROMASEAL® Fire Compound INTRODUCTION Promat PROMASEAL® Fire Compound is a white powder, which is mixed with water to the required consistency for installation. When set, Promat PROMASEAL® Fire Compound becomes a hard material with a white matt finish. The actual surface finish of the set product is dependent upon treatment at the time of application. APPLICATIONS Promat PROMASEAL® Fire Compound is used to provide a fire seal around service penetrations in walls and floors. The formless nature of the fire compound prior to setting allows it to be introduced between services and so...

Open the catalog to page 12
PROMASEAL® - 13

Promat PROMASEAL® Fire CompoundCertifire Approval No CF 425 Promat PROMASEAL® Fire Compound - Approval Matrix Maximum Opening Area: 1.44m2 with a maximum service loading of 25% within each penetration seal Wall Thickness: Application Technique: The floors and walls shall be a minimum of 100mm thick. The minimum density for the concrete of the floor or wall is 780kg/m3 and for walls made of concrete blocks is 600kg/m3. Floors: Temporary or permanent shuttering will be required. In all instances where the span of the Promat PROMASEAL® Fire Compound exceeds 600mm, additional reinforcement e.g....

Open the catalog to page 13
PROMASEAL® - 14

* Safe working load of the floor seal is taken as one third of the tensile failure pressure. Safe working load is for temporary foot traffic not permanent loading.