GLOBAL PX/RX/LP

GLOBAL PX/RX/LP
1 / 64 PagesView full catalog

GLOBAL PX/RX/LP

Product catalog summary
Safety Precautions
Personnel must be familiar with instructions before working on the unit. Power should be disconnected before maintenance, and only authorized electricians should handle electrical connections. Caution is advised around rotating parts and sharp edges. Units should be operated with closed doors and panels, and proper insulation is necessary in cold environments.
Symbols and Abbreviations
Key symbols include BW (Backward Curved Fan), FW (Forward Curved Fan), RX (Rotary Heat Exchanger), and PX (Plate Heat Exchanger). Warnings for electrical hazards and airflow directions are provided.
Product Overview
The document describes GLOBAL unit models, including PX, RX, and LP variants, with specifications for air volume, dimensions, and weight. It highlights differences between right and left-hand units and the importance of ordering the correct version.
Wiring Overview
Details the main control board TAC5 DG, including connections for actuators, sensors, and alarms. Specifies input and output configurations for airflow control, temperature sensors, and relay outputs.
Functions
Outlines the operational principles of GLOBAL air handling units, including airflow management, heating, and cooling functionalities.
Commissioning
Instructions for commissioning units using various control interfaces, emphasizing proper setup based on the control device used.
Preventive Maintenance
Recommends regular checks and maintenance to ensure optimal performance and longevity of the units.
Troubleshooting
Guidance on identifying and resolving common issues during unit operation.
Parameters/Commissioning Sheet
Includes detailed parameters and settings required for the commissioning process.
CE Declaration
Confirms compliance with European safety and performance standards.
Specifications and Components
Outlines specifications and components of an air handling unit control system, including the MAIN CONTROL BOARD TAC5 DT - CID026001 and CIRCUIT BOARD SAT 3 - CID372005. Key functionalities include fan status, differential pressure alarm, heating demand, and bypass status.
Installation and Wiring
Emphasizes correct positioning of SAT3 and SAT BA/KW boards before powering the circuit. Wiring diagrams for various configurations are provided.
Operating Modes
The system supports five main operating modes: Airflow control, Torque control, Demand control (0-10V), Pressure control, and Mode Off.
Temperature Control and Free Cooling
Options include supply air temperature and extract air temperature control. Free cooling utilizes outdoor air to cool the building.
Frost Protection
Strategies involve modulating heat exchanger speed or using electrical pre-heating to prevent freezing.
Time Schedule and Commissioning
Controller allows configuration of up to six time slots for operation modes. Commissioning can be performed using the TACtouch touchscreen interface or a basic position switch.
Specifications
The touchscreen controller has a 1.5-meter cable for connection to the control circuit board, with specifications including an operating temperature range of 0 to +50°C and protection class IP20.
Image Management
The basic setup menu activates automatically on startup. The main menu is accessible via a rotary menu, displaying key data such as current operation mode, date and time, and active alarms.
Control and Settings
The control menu allows users to change basic parameters and operation status, including switching the unit on/off and adjusting setpoints.
Alarm and Maintenance
Alarms are displayed on the main screen, and active alarms can be viewed and reset. Maintenance settings include configuring service-related settings and setting maintenance warning intervals.
Basic Setup
Guides users through critical settings such as language, units, airflow regulation, temperature, and fire alarm settings.
Advanced Setup
Requires a code and special training, including settings for stopping fans with 0-10V signals and pressure control.
Boost Mode
Forces supply and extract airflow to a higher setpoint under specific conditions.
Post Ventilation
Automatically activates when an electrical heating coil is used, keeping fans running for a specified time.
Internal and External Coils
Preheating coils prevent moisture and frost issues. External coils require on-site installation and configuration.
Frost Protection
Anti-frost sensors protect water coils from freezing, activating alarms and opening valves if temperatures drop below 4°C.
Freecooling
Configurable based on outdoor and room temperatures, with a factory setting of 0°C for outdoor and 22°C for room temperature.
Modbus and LAN Configuration
Requires additional hardware for communication. Factory settings include an address of 1 and a baud rate of 9600.
Operating Time
Maintenance timers can trigger alarms and switch the unit to 'OFF' mode.
0-10V Output
Configurable outputs for airflow or pressure, with factory settings for specific fan outputs.
Maintenance
Regular maintenance is crucial for optimal operation, including filter replacement and component inspection every 3 to 12 months.
Troubleshooting
The TAC5 control board manages alarms, categorized into auto-resetting and non-auto-resetting types.
Alarm Types and Descriptions
Includes various alarm types such as pressure variation, reference pressure initialization, setpoint fulfillment, data failure, fire alarm, maintenance alarm, communication breakdown, and temperature sensor failures.
Key Procedures and Recommendations
Ensure proper configuration of fire alarm inputs and advanced setup options. Regular maintenance and monitoring of fan operating hours are crucial.
Overview
Provides technical specifications, procedures, and maintenance instructions for a system involving bypass actuators, control boards, and heat exchangers.
Specifications and Procedures
Replacement of damaged position sensors on bypass actuators is necessary. Alarm types include incorrect position of the modulating bypass and maintenance hours limit for filters.
Key Parameters and Commissioning
Main parameters include operating modes like constant airflow, demand control, constant torque, and constant pressure.
Recommendations
Ensure manual reset for certain alarms and configure the REC type in the product setup menu when replacing control boards.
Data Tables
Tables provide range sizes and codes for different global models and configurations.
Conclusion
The document emphasizes the importance of proper maintenance and configuration to ensure system efficiency and reliability.
See more

Catalog excerpts

GLOBAL PX/RX/LP-1

GLOBAL PX/RX/LP Operation and maintenance instructions Applicable to program versions TAC5 – Version DT 2.8.12 & DG 2.7.3 GLOBAL LP(FW) GLOBAL PXFW

 Open the catalog to page 1
GLOBAL PX/RX/LP-2

6.1 Commissioning with Touchscreen interface 2 This document is an overview of technical specifications. Please do refer to our selection software for detailed and up-to-date information.

 Open the catalog to page 2
GLOBAL PX/RX/LP-3

This document is an overview of technical specifications. Please do refer to our selection software for detailed and up-to-date information. 3

 Open the catalog to page 3
GLOBAL PX/RX/LP-4

Disclaimer Danger/Warning/Caution • All staff concerned shall acquaint themselves with these instructions before beginning any work on the unit. Any damages to the unit or its components caused by improper handling or misuse by the purchaser or the installer cannot be considered subject to guarantee if these instructions have not been followed correctly. • Make sure that the power supply to the unit is disconnected before performing any maintenance or electrical work! • All electrical connections must be carried out by an authorized installer and in accordance with local rules and controls. RANGE...

 Open the catalog to page 4
GLOBAL PX/RX/LP-5

PLEATED FILTER ROTARY HEAT EXCHANGER PLATE HEAT EXCHANGER Must be connected by a qualified Electrician. Warning! Hazardous voltage. HEATING COIL COOLING COIL PRESSURE SENSOR SLIP CLAMP FLEXIBLE CONNECTION CIRCULAR DUCT CONNECTION (WATER / ELECTRICAL) MOTORIZED DAMPER TEMPERATURE SENSOR This document is an overview of technical specifications. Please do refer to our selection software for detailed and up-to-date information.

 Open the catalog to page 5
GLOBAL PX/RX/LP-6

3.0 Product Overview 3.1 GENERAL OVERVIEW RIGHT HAND UNIT (SUPPLY AIR TO THE RIGHT) GLOBAL PX(FW) GLOBAL PX(FW) LEFT HAND UNIT (SUPPLY AIR TO THE LEFT) This document is an overview of technical specifications. Please do refer to our selection software for detailed and up-to-date information.

 Open the catalog to page 6
GLOBAL PX/RX/LP-7

RIGHT HAND UNIT (SUPPLY AIR TO THE RIGHT) LEFT HAND UNIT (SUPPLY AIR TO THE LEFT) GLOBAL LP 450FW (BOTTOM view) GLOBAL LP 450FW (BOTTOM view) GLOBAL LP 600 - 2000FW (BOTTOM view) GLOBAL LP 600 - 2000FW (BOTTOM view) ATTENTION Right and left hand units have different article numbers and should be ordered accordingly. Main version described in the manuals is always the hand right version. The difference between left and right LP units is the factory placement of the controls box on opposite sides. This document is an overview of technical specifications. Please do refer to our selection software...

 Open the catalog to page 7
GLOBAL PX/RX/LP-8

3.2 COMPONENTS GLOBAL PX GLOBAL PX TOPFW 1. Main power switch 2. Main power switch for electrical coils (both internal pre-hating and post-heating) 11. Drain pan and drain pipe 13. Internal post-heating water or electrical coil (accessory) 14. Motorized damper (at outdoor air side - accessory) 15. Motorized damper (at exhaust air side - accessory) 6. Kit CA -airflow measurement (option) 7. Outdoor air filter (bag or pleated) 18. Slip Clamps (accessory) 8. Extract air filter (bag or pleated) 19. Water connection for postheating (accessory) 12. Pre-heating electrical antifrost coi 9. Heat exchanger...

 Open the catalog to page 8
GLOBAL PX/RX/LP-9

This document is an overview of technical specifications. Please do refer to our selection software for detailed and up-to-date information. 9

 Open the catalog to page 9
GLOBAL PX/RX/LP-10

GLOBAL LPFW 1. Main power switch 2. Main power switch for electrical coils (both internal pre-hating and post-heating) 11. Drain pan and drain pipe 13. Internal post-heating water or electrical coil (accessory) 14. Motorized damper (at outdoor air side - accessory) 15. Motorized damper (at exhaust air side - accessory) 6. Kit CA -airflow measurement (option) 7. Outdoor air filter (bag or pleated) 8. Extract air filter (bag or pleated) 18. Slip Clamps (accessory) 9. Heat exchanger (Plate) 19. Water connection for postheating (accessory) 12. Pre-heating electrical antifrost coil 1, 2 and 3 must...

 Open the catalog to page 10
GLOBAL PX/RX/LP-11

GLOBAL LP(FW) GLOBAL LP(FW) EXCHANGER This document is an overview of technical specifications. Please do refer to our selection software for detailed and up-to-date information. 11

 Open the catalog to page 11
GLOBAL PX/RX/LP-12

3.2 COMPONENTS GLOBAL RX GLOBAL RX 1. Main power switch 13. Internal post-heating water or electrical coil (accessory) 2. Main power switch for electrical coils (both internal pre-hating and post-heating) 14. Motorized damper (at outdoor air side - accessory) 18. Slip Clamps (accessory) 19. Water connection for postheating (accessory) 15. Motorized damper (at exhaust air side - accessory) 6. Kit CA -airflow measurement (option) 7. Outdoor air filter (bag) 8. Extract air filter (bag) 9. Heat exchanger (Rotary) 1, 2 and 3 must be installed by an accredited electrician Note: internal electrical...

 Open the catalog to page 12
GLOBAL PX/RX/LP-13

This document is an overview of technical specifications. Please do refer to our selection software for detailed and up-to-date information. 13

 Open the catalog to page 13
GLOBAL PX/RX/LP-14

MAIN CONTROL BOARD TAC5 DG - CID025000BYPASS4 3 2 1 MOTOR CONTROL CABLES CT = output to CT actuator(s) (option - prewired) BYPASS = output to bypass actuator (prewired) IN2 = dPa (pressostat digital input) IN3 = Fire alarm input IN4 = Bypass open / Stop heat recovery IN5 = Real time clock auto/manu Demand/Pressure control IN6 = ON/OFF post heating (IBA/KWout) Torque MODE IN7 = ON/OFF SUPPLY if fire alarm IN8 = ON/OFF EXHAUST if fire alarm Demand/Pressure control Torque control IN12 = PWM input bypass position OUT1 = 0-10V OUTPUT (airflow / pressure) Demand/Pressure control OUT2 = 0-10V OUTPUT...

 Open the catalog to page 14
GLOBAL PX/RX/LP-15

AL1 BYPASS BYPASS MOTOR CONTROL CABLES CT : output to CT actuator(s) (option - prewired) KWout = output for KWout capacity control (option - prewired) IN2 = dPa (pressostat digital input) IN3 = Fire alarm input IN4 = Bypass open / Stop heat recovery IN5 = Real time clock auto/manu Demand/Pressure control = START/STOP IN6 = ON/OFF post heating (IBA/KWout) Torque control IN7 = ON/OFF SUPPLY if fire alarm IN8 = ON/OFF EXHAUST if fire alarm Demand/Pressure control = 0-10V INPUT Torque control IN12 = input pulse from heat exchanger magnet (prewired) OUT1 = 0-10V OUTPUT (airflow / pressure) OUT2 =...

 Open the catalog to page 15
GLOBAL PX/RX/LP-16

4.1 CIRCUIT BOARD SAT 3 - CID372005 The SAT3 circuit board is used for extra functions for which inputs and outputs are not included as standard in the control unit of the air handling unit. All outputs are normally open (N.O.). Maximal load: 230VAC - 4A. The circuit board SAT3 allows for signalling of the following by means of a potential-free contact: • Differential pressure alarm - O.R. 2 SAT3 must be plugged onto the control board circuit (see fig.1). Attention: The SAT3 must be plugged in before the circuit is powered. SAT must be plugged in correctly, wrong positioning can damage both circuits...

 Open the catalog to page 16

All P. LEMMENS COMPANY catalogs and technical brochures

  1. GLOBAL PX

    23  Pages

  2. GLOBAL LP OUT

    24  Pages

  3. GLOBAL RX TOP

    32  Pages

  4. GLOBAL RX

    44  Pages

  5. Aira

    4  Pages

  6. COMPO Series

    24  Pages

  7. CUBUS

    4  Pages

  8. AC series

    4  Pages

  9. AE series

    4  Pages

  10. AIRA series

    4  Pages

  11. BA series

    2  Pages

  12. CUBUS series

    4  Pages

  13. ES series

    2  Pages

  14. LCO series

    6  Pages

  15. REC X series

    4  Pages

  16. TV series

    4  Pages

  17. TAC series

    4  Pages

  18. COMPO series

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.