Overview: The COMPO Series consists of compact, modular air-treatment units designed for air recirculation, heating, or conditioning with a capacity range of 0-8000 m³/h. These units incorporate TAC5 technology, providing a standardized yet customizable solution for efficient air treatment.
Specifications: The series includes three unit types: rectangular (M), square (U), and flat (P), each differing in cross-section dimensions and airflow capacity for both heating and cooling. They feature various fan models like DS 10-4 and DD 11-11, and operate within a temperature range of -20° to 55°C.
TAC5 Technology: This technology includes high-efficiency DC motors with permanent magnets, ensuring low energy consumption. It offers control options such as constant airflow and pressure, sensor integration (temperature, RH%, CO2), and network configuration options (Modbus, Ethernet, Wi-Fi).
Construction: COMPO units are built with double-walled, insulated panels using 30 mm rock wool for thermal insulation, complying with European environmental standards. The structure is made of anodized aluminum and reinforced polypropylene, with corrosion-resistant outer panels.
Selection Program: A software tool is available for designing COMPO units, allowing users to specify components, generate technical specifications, and pricing. It aids in visualizing physical installation and links to production processes.
Performance Data: Detailed tables provide information on airflow, available pressure, sound pressure, and heating/cooling capacities for various models. Recommendations include not exceeding a front speed of 2.9 m/s for cooling and 4 m/s for heating.
General Recommendations: Users are advised to refer to the selection software for the most accurate and updated information regarding unit specifications and configurations.
BA Unit Overview: The document details the BA unit of the COMPO series, which includes heating or cooling batteries, categorized into Fluid/Air and Electric Element/Air exchangers.
Fluid/Air Exchanger: Constructed with copper tubes and aluminum fins, these exchangers are tested under high pressure and certified by ISO 9001 and TUV. They feature a three-way valve for temperature control and a stainless-steel condensate tray with a fire-resistant trap.
Electric/Air Exchanger: These pre-wired electric batteries come with thermal protections and comply with EN 60,335-1 standards. A regulator modulates power to maintain temperature, with settings adjusted by the fitter.
Filters: COMPO units can be equipped with G4 and F7 filters, both Eurovent certified. G4 filters are flat and made of polyester fibers, while F7 filters are bag-type with synthetic media. Activated charcoal filters are available for deodorizing and purifying air.
Noise Attenuation: Sound baffles made of rock wool can be added to reduce noise, with attenuation values available online.
Mixing Units: Two- or three-way mixing units with counter-rotating valves and servomotors are available, featuring galvanized-steel frames and aluminum blades for improved sealing.
Outdoor Installation: COMPO units can be installed outdoors with options like pre-painted steel for corrosion resistance, a roof for water drainage, and a canopy to prevent rain entry. A positive-pressure shutter protects against air currents and small animals.
Fixation and Accessories: Units come with M8 nuts for secure mounting, and circular adapter parts for intakes and outlets. Flexible sleeves are available for structural sealing.
Version: The document is dated 13/07/2018, noting that specifications are subject to change.
See more

Catalog excerpts

COMPO Series-1

COMPO SERIES COMPO Series Technical Guide Range of compact, modular air-treatment units (0-8000 m³/h)

 Open the catalog to page 1
COMPO Series-2

COMPO SERIES The Compo range meets all your needs in air recirculation, heating or conditioning in a single airflow. Using TAC5 technology, which is standard in the COMPO series, and a smart standardisation of the various modules used in air-treatment units, PLC has developed an «almost customised» complete standardised COMPACT range of air-treatment units, from 0 to 8000 m3/h. Unlike the usual process of first defining each element that makes up a unit and then purchasing each one individually, the Compo range contains an extended stock of standard elements, which can be chosen in order to define...

 Open the catalog to page 2
COMPO Series-3

Silent, rigid, aesthetic, double-skin modular construction All COMPO devices are double-walled, insulated by 30 mm of rock wool. The structure is made of anodised-aluminium profile members, articulated around modules injected with reinforced polypropylene. COMPO SERIES The outer panels are made of pre-painted steel (RAL9002), painted with siliconised thermally crosslinkable polyester, which is corrosion resistant, and covered with a protective plastic film, to be removed after installation, and are easily detached in order to be able to access the inside parts. The inside is made of galvanised...

 Open the catalog to page 3
COMPO Series-4

GENERAL TECHNICAL SPECIFICATIONS CID • CROSS-SECTION 430X430, length 890 mm according to selection • PANEL COLOUR Beige RAL 9002 0. Available fan pressure for the 4-row heating battery 1. Total noise pressure in dBA radiated in free field at 3 m over system curve 1000 m3/h at 150 Pa 2. Water battery (2 rows) 80/60, air -10°C, 50% RH 3. Water battery (4 rows) 70/50, air -10°C, 50% RH 4. Water battery (4 rows, condensation), condensation temp. 45°C, air -10°C, 50% RH 5. Water battery 7/12, air 25°C, 50% RH 6. R410a battery, evaporation temp. 5°C, air 25°C, 50% RH AVAILABLE SOUND AIRFLOW PRESSURE...

 Open the catalog to page 4
COMPO Series-5

Fan curve DD 9-9 TAC 1/2 GENERAL TECHNICAL SPECIFICATIONS CID 845438 0. Available fan pressure for the 4-row heating battery 1. Total noise pressure in dBA radiated in free field at 3 m over system curve 1000 m3/h at 150 Pa 2. Water battery (2 rows) 80/60, air -10°C, 50% RH 3. Water battery (4 rows) 70/50, air -10°C, 50% RH 4. Water battery (4 rows, condensation), condensation temp. 45°C, air -10°C, 50% RH 5. Water battery 7/12, air 25°C, 50% RH 6. R410a battery, evaporation temp. 5°C, air 25°C, 50% RH • CROSS-SECTION 530x530, length 890 according to selection • PANEL COLOUR Beige RAL 9002

 Open the catalog to page 5
COMPO Series-6

GENERAL TECHNICAL SPECIFICATIONSCID 845439• FANS DD 10-10 TAC 3/4 (CID: 720056)• AIRFLOW 500 to 3000 m3/h • CROSS-SECTION 630 X 630, length 890 mm according to selection • PANEL COLOUR White RAL 9002 0. Available fan pressure for the 4-row heating battery 1. Total noise pressure in dBA radiated in free field at 3 m over system curve 1000 m3/h at 150 Pa 2. Water battery (2 rows) 80/60, air -10°C, 50% RH 3. Water battery (4 rows) 70/50, air -10°C, 50% RH 4. Water battery (4 rows, condensation), condensation temp. 45°C, air -10°C, 50% RH 6. R410a battery, evaporation temp. 5°C, air 25°C, 50% RH...

 Open the catalog to page 6
COMPO Series-7

Fan curve DD 11-11 TAC 1/1 GENERAL TECHNICAL SPECIFICATIONS CID 845440 • CROSS-SECTION 890 x 890, length 890 according to selection • PANEL COLOUR Beige RAL 9002 0. Available fan pressure for the 4-row heating battery 1. Total noise pressure in dBA radiated in free field at 3 m over system curve 1000 m3/h at 150 Pa 2. Water battery (2 rows) 80/60, air -10°C, 50% RH 3. Water battery (4 rows) 70/50, air -10°C, 50% RH 4. Water battery (4 rows, condensation), condensation temp. 45°C, air -10°C, 50% RH 6. R410a battery, evaporation temp. 5°C, air 25°C, 50% RH

 Open the catalog to page 7
COMPO Series-8

GENERAL TECHNICAL SPECIFICATIONS CID 845441 • CROSS-SECTION 630 X 890, length 890 mm according to selection • THERMAL PROTECTION D10A/AC3/10kA • TEMPERATURES -20° to 55°C • PANEL COLOUR Beige RAL 9002 0. Available fan pressure for the 4-row heating battery 1. Total noise pressure in dBA radiated in free field at 3 m over system curve 1000 m3/h at 150 Pa 2. Water battery (2 rows) 80/60, air -10°C, 50% RH 3. Water battery (4 rows) 70/50, air -10°C, 50% RH 4. Water battery (4 rows, condensation), condensation temp. 45°C, air -10°C, 50% RH 6. R410a battery, evaporation temp. 5°C, air 25°C, 50% RH...

 Open the catalog to page 8
COMPO Series-9

COMPO SERIES GENERAL TECHNICAL SPECIFICATIONS CID 845442 0. Available fan pressure for the 4-row heating battery 1. Total noise pressure in dBA radiated in free field at 3 m over system curve 1000 m3/h at 150 Pa 2. Water battery (2 rows) 80/60, air -10°C, 50% RH 3. Water battery (4 rows) 70/50, air -10°C, 50% RH 4. Water battery (4 rows, condensation), condensation temp. 45°C, air -10°C, 50% RH 5. Water battery 7/12, air 25°C, 50% RH 6. R410a battery, evaporation temp. 5°C, air 25°C, 50% RH • CROSS-SECTION 630 x 1430, length 890 according to selection • THERMAL PROTECTION D20A/AC3/10kA (2 fans)...

 Open the catalog to page 9
COMPO Series-10

GENERAL TECHNICAL SPECIFICATIONS CID 845443 • CROSS-SECTION 340 X 890, length 890 mm according to selection • THERMAL PROTECTION D10A/AC3/10kA • TEMPERATURES -20° to 55°C • PANEL COLOUR Beige RAL 9002 0. Available fan pressure for the 4-row heating battery 1. Total noise pressure in dBA radiated in free field at 3 m over system curve 1000 m3/h at 150 Pa 2. Water battery (2 rows) 80/60, air -10°C, 50% RH 3. Water battery (4 rows) 70/50, air -10°C, 50% RH 4. Water battery (4 rows, condensation), condensation temp. 45°C, air -10°C, 50% RH 6. R410a battery, evaporation temp. 5°C, air 25°C, 50% RH...

 Open the catalog to page 10
COMPO Series-11

COMPO SERIES GENERAL TECHNICAL SPECIFICATIONSCID 845444 • FANS DP 9-7 TH TAC 1/1 (CID: 720059) 0. Available fan pressure for the 4-row heating battery 1. Total noise pressure in dBA radiated in free field at 3 m over system curve 1000 m3/h at 150 Pa 2. Water battery (2 rows) 80/60, air -10°C, 50% RH 3. Water battery (4 rows) 70/50, air -10°C, 50% RH 4. Water battery (4 rows, condensation), condensation temp. 45°C, air -10°C, 50% RH 5. Water battery 7/12, air 25°C, 50% RH 6. R410a battery, evaporation temp. 5°C, air 25°C, 50% RH • CROSS-SECTION 430 x 890, length 890 according to selection • THERMAL...

 Open the catalog to page 11

All P. LEMMENS COMPANY catalogs and technical brochures

  1. GLOBAL PX

    23  Pages

  2. GLOBAL LP OUT

    24  Pages

  3. GLOBAL RX TOP

    32  Pages

  4. GLOBAL RX

    44  Pages

  5. Aira

    4  Pages

  6. CUBUS

    4  Pages

  7. GLOBAL PX/RX/LP

    64  Pages

  8. AC series

    4  Pages

  9. AE series

    4  Pages

  10. AIRA series

    4  Pages

  11. BA series

    2  Pages

  12. CUBUS series

    4  Pages

  13. ES series

    2  Pages

  14. LCO series

    6  Pages

  15. REC X series

    4  Pages

  16. TV series

    4  Pages

  17. TAC series

    4  Pages

  18. COMPO series

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.