1. Catalogs
  2. O.ERRE
  3. TEMPERO ECO V E BP

TEMPERO ECO V E BP

TEMPERO ECO V E BP

TEMPERO ECO V E BP

Product catalog summary
Overview: The TEMPERO ECO V E BP is a centralized heat recovery unit designed for vertical installation, featuring a counterflow heat exchanger with over 90% thermal efficiency. It is equipped with EC centrifugal brushless motors for high performance and low energy consumption.
Specifications: The unit includes synthetic fiber class G4 filters (F7 optional for fresh air), a self-supporting EPS structure with a painted steel outer coat, and a drip tray for condensate drainage. It complies with the ERP 2016 Directive.
Technical Data: The TEMPERO ECO V 250 E BP and TEMPERO ECO V 450 E BP models have different dimensions, flow rates, and power specifications. The 250 model has a flow rate of 250 m3/h, while the 450 model has a flow rate of 400 m3/h.
Installation: The unit is suitable for vertical installation in spaces like closets and laundry rooms. It extracts "foul" air from technical premises and introduces filtered fresh air into "noble" premises.
Efficiency: The unit achieves high energy recovery efficiency, maintaining a comfortable indoor temperature even when external temperatures are low.
By-Pass Version: The By-Pass feature allows the unit to bypass the heat exchanger when heat recovery is not needed, such as in summer.
Motor Technology: The EC brushless motors provide energy savings and long life due to ball-bearing construction.
Filtration: The unit uses G4 filters for both fresh and extracted air, with an optional F7 filter for enhanced protection against air impurities.
Control System: A wireless controller with four operation modes (Away, Home, Party, Timer) is included. Optional control panels can monitor humidity and CO2 levels, forcing air extraction if thresholds are exceeded.
See more

Catalog excerpts

TEMPERO ECO V E BP-1

TEMPERO ECO V E BP CENTRALIZED HEAT RECOVERY UNIT • Heat Recovery Unit with counterflow heat exchanger for VERTICAL installation; • High thermal efficiency: heat exchanger > 90%; • Plug Fan with EC centrifugal brushless motors, high performance, low energy consumption; • Equipped with synthetic fiber class G4 filters (F7 optional on fresh air); • Self-supporting structure made of EPS material with outer coat painted steel; Drip tray to condensate drainage; Suitable for VERTICAL installation; Equipped with automatic BY-PASS; Adjustable speed through wireless controller (included); In Compliance with ERP 2016 Directive. TECHNICAL DATA Model Flow rate Useful capacity Useful capacity FLOW CHARTS • TEMPERO ECO V 450 E BP

 Open the catalog to page 1
TEMPERO ECO V E BP-2

FLUX SCHEME INSTALLATION EXAMPLE The “foul” air is extracted from the so-called “technical” premises of the house (bathroom, kitchen...) and through suitable ducts connected to the plenum reaches the TEMPERO ECO V E BP recovery unit where the heat exchange occurs by mixing with the fresh air before being exhausted. The fresh air, in fact, is introduced from the outside directly from Tempero where it is filtered, crosses the heat exchanger and after reaching the Plenum, it is directed towards the “noble” premises (living room, bedrooms...). IN EVIDENCE MAXIMUM INSTALLATION COMFORT TEMPERO ECO V...

 Open the catalog to page 2

All O.ERRE catalogs and technical brochures

  1. EASY

    2  Pages

  2. GHOST

    2  Pages

  3. MIAMI

    1  Page

  4. IN AXIAL FAN

    3  Pages

  5. EB EX-ATEX

    2  Pages

  6. CS EX-ATEX

    2  Pages

  7. AIRPOWER ABS

    1  Page

  8. FIRENZE

    1  Page

  9. PHONNY MURO

    1  Page

  10. PHONNY TUBO

    1  Page

  11. SMART

    2  Pages

  12. VENTILOR

    1  Page

  13. SILENTE

    2  Pages

  14. HEV

    1  Page

  15. TEMPERO line

    52  Pages

  16. SYSTEMA

    1  Page

  17. T° Control

    48  Pages

  18. Industry

    92  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.