PYROLINE® Con PLC Concrete fire protection ducts with European classification and EI30 to EI90 fire resistance classes according to EN 13501-2
Open the catalog to page 1Fire protection ducts Their protective function If there is a fire, then the fire protection ducts help to ensure the usability of the escape routes by protecting them against possible electrical cable fires, thus preventing the spread of fire. In particular, they fulfil two functions: 1. Fire protection duct is used wherever the environment must be protected against the impacts of cable fires. It encapsulates the fire load, meaning that, in the case of a cable fire, fire and smoke cannot escape from the duct. 2. In addition, it ensures that the cables located in the fire protection duct...
Open the catalog to page 2Fire protection ducts must fulfil certain requirements for them to be used in buildings. They are construction products according to the European Construction Products Regulation CPR (EU No. 305/2011) and thus carry the CE mark. This means that they can be used in all the countries of the EU. Testing and classification During a fire test according to EN 1366-5, a cable fire in the interior of the duct is simulated. The ducts are filled with cables. The cable exits are also tested. This ensures whether fire and smoke can escape from the duct and whether the duct surfaces outside the testing...
Open the catalog to page 3The fire protection duct system PYROLINE® Con PLC In the PYROLINE® Con PLC fire protection duct system, made of water- and frost-resistant fibre glass lightweight concrete fire protection plates, OBO is able to meet all the requirements for a duct system with European classification. With two different wall thicknesses, the OBO PYROLINE® Con PLC fire protection duct system can achieve the fire resistance classes EI30‒EI60 and EI90. The PYROLINE® Con PLC fire protection ducts possess all the construction-relevant proofs of suitability: • Classification report • European Technical Assessment...
Open the catalog to page 405 BSS Broschüre Betonkanal PYROLINE Con PLC DE / en / 2021/05/07 15:33:26 15:33:26 (LLExport_02918) / 2021/05/07 15:33:40 The PYROLINE® Con PLC fire protection duct system is available in: • Two dimensions • Two classifications • Two mounting variants For direct wall and ceiling mounting
Open the catalog to page 5For direct wall and ceiling mounting The PYROLINE® Con D PLC fire protection duct is mounted directly on walls and ceilings. Should other fittings be required, then they can be created easily and flexibly on-site, according to the requirements. The primed fire protection ducts can be painted or papered over, as required. System benefits: • The ducts can be integrated discreetly in the building • Available in 2 different dimensions and classifications • The cover is simply screwed onto the ducts • Individual creation of fittings • Can be perfectly adapted to existing ca
Open the catalog to page 6Installation principle 05 BSS Broschüre Betonkanal PYROLINE Con PLC DE / en / 2021/05/07 15:33:26 15:33:26 (LLExport_02918) / 2021/05/07 15:33:40 Flexible duct routing Mounted fire protection duct on wall and ceiling Mounted fire protection duct with cable outlets Vertical cable routing using cable brackets Wall connection with wall connection collar Cable mounting with separating bracket and separating clamp Combination of suspended fire protection duct and wall duct Discreet installation
Open the catalog to page 7PYROLINE® Con S PLC For suspended mounting The PYROLINE® Con S PLC fire protection duct can be installed on wall brackets or on a support system suspended from the ceiling, for example using brackets or a pendulum suspension. Have pipes or cables from other systems, such as heating, ventilation or sanitary systems already been routed? No problem – they can be elegantly passed under or by-passed using the PYROLINE® Con S PLC fire protection duct. Mounted connectors permit quick connection of the duct sections directly on-site. System benefits: • Pre-mounted connection elements for quick,...
Open the catalog to page 8Installation principle 05 BSS Broschüre Betonkanal PYROLINE Con PLC DE / en / 2021/05/07 15:33:26 15:33:26 (LLExport_02918) / 2021/05/07 15:33:40 Suspended ceiling mounting Wall mounting on brackets Pre-mounted connection fastenings Loose-fitting cover for quick inspection and retroassignment Wall connection with wall connection collar Cables routed as individual cables or cable bundles
Open the catalog to page 9PYROLINE® Con D PYROLINE® Con D fire protection duct EI30 -EI60 Dim. b mm Type PLCD D060810 100 PLCD D061220 200 Fire protection duct made of water- and frost-resistant fibre glass lightweight concrete of material class A1 according to EN 13501-1 for fireproof routing of cables in escape and rescue routes. EI30–EI60 classification as installation duct according to EN 13501-2 on the basis of tests according to EN 1366-5. When there is an internal fire load (cable fire), the duct prevents the spread of fire from one fire section to another. Mounting of the duct directly on walls or under...
Open the catalog to page 10End pieces End piece for PYROLINE® Con D EI60 fire protection duct Dim. B mm Type PLCD E060810 160 PLCD E061220 260 End piece for PYROLINE® Con D EI30 - EI60 fire protection duct, consisting of fibre glass light concrete which is resistant to water and frost for closing the duct ends. End piece for PYROLINE® Con D EI90 fire protection duct Dim. B mm Type PLCD E090810 180 PLCD E091220 280 End piece for PYROLINE® Con D EI90 fire protection duct, consisting of fibre glass light concrete which is resistant to water and frost for closing the duct ends. Accessories Separating bracket for wall...
Open the catalog to page 11PYROLINE® Con S PYROLINE® Con S fire protection duct EI30 -EI60 Dim. h mm Type PLCS D060810 80 PLCS D061220 120 Fire protection duct made of water- and frost-resistant fibre glass lightweight concrete of material class A1 according to EN 13501-1 for fireproof routing of cables in escape and rescue routes. EI30–EI60 classification as installation duct according to EN 13501-2 on the basis of tests according to EN 1366-5. When there is an internal fire load (cable fire), the duct prevents the spread of fire from one fire section to another. Mounting of the duct on wall brackets or as ceiling...
Open the catalog to page 12All OBO Bettermann catalogs and technical brochures
-
Spacer Clips ASG 732 and ASL 733
20 Pages
-
Quick Wire Cable Suspension
20 Pages
-
The Quick Pipe Portfolio
18 Pages
-
Cavity Wall Electronics Box
2 Pages
-
Cavity Wall Boxes
2 Pages
-
Flush-Mounted Boxes
2 Pages
-
Skirting Trunking SL and RAUDUO
40 Pages
-
IBK In-Concrete Duct System
24 Pages
-
OKB Brush Bar Trunking
2 Pages
-
GES R2 Floor Sockets
2 Pages