Catalog excerpts
AIR HANDLING MADE SIMPLE TB1 FOR THE COMPLETE VENTILATION SOLUTION
Open the catalog to page 1p Model shown: Plate Heat Exchanger Unit. DUTY AND AVAILABILITY VERTICAL MODELS Maximum Duty HORIZONTAL MODELS BPS-07 *Availability Dates in 2016 for unit models.
Open the catalog to page 2Nuaire has been at the forefront of packaged AHU’s for over AT THE FOREFRONT OF PACKAGED SOLUTIONS FOR OVER 20 YEARS 20 years, designing and manufacturing market leading ranges. When launched in 2000, Ecosmart Boxer revolutionised the industry by providing the best solution for performance and energy efficiency, then enhanced it with the Ecosmart ‘plug and play’ control. Fast forward sixteen years and the New Boxer Packaged Solution (BPS) has been designed, engineered and tested to provide the most efficient, best performing, most compact and easiest to select AHU on the market. BPS can be...
Open the catalog to page 3BPS BOXER PACKAGED SOLUTIONS CLASSIFICATION FEATURES BS EN 1886:2007 “Ventilation for buildings — Air handling units — Mechanical performance” sets out the measurement and classification standard for AHUs. THERMAL BRIDGING FACTOR Class Thermal Bridging Factor (kb) TB1 0.75 < Kb < 1 TB2 0.6 < Kb < 0.75 TB3 0.45 < Kb < 0.6 TB4 0.3 < Kb < 0.45 TB5 No requirements EN 1886 - Thermal Bridge - Classifications All of these are measured and rated against tabulated vales to give a grade, 1 being the highest in each classification. The key criteria are: • Air leakage [L] • Thermal bridging [TB] •...
Open the catalog to page 4BPS BOXER PACKAGED SOLUTIONS COMPLYING WITH BUILDING REGULATIONS SECTION 6 (2015 EDITION) The following information is relevant to the selection of fans for Ventilation Systems, indicating the maximum specific fan powers allowed under Part L (Refer to the Non-domestic Building Services Compliance Guide: 2013 Edition for further details). Permissible maximum specific fan power and pressure drop in air distribution systems. Maximum specific fan powers in air distribution systems new and existing buildings. The SFP for the entire system (including both supply & extract fans) shall be less than...
Open the catalog to page 5BPS BOXER PACKAGED SOLUTIONS EXTERNAL FEATURES AND BENEFITS n UNIQUE CONSTRUCTION DESIGN, (PATENT APPLIED) NO REQUIREMENT FOR ADDED SILICONE n HINGED OR REMOVABLE ACCESS PANELS All hinged access panels will be lockable and removable via locked hinges which can be opened for panel removal. All keys are identical and will open any handle or hinge. The hinges do not need to be unlocked in normal n ONE PIECE PACKAGED SOLUTION The BPS unit is a pre-selected catalogue range which is manufactured in sections for ease of manoeuvring on site. Unit modules may be clamped together on site using the...
Open the catalog to page 61. BOXER Package Solution Range 4. Heat V = Vertical Plate Exchanger: T = Thermal Wheel 7. Control type: AT = Ecosmart Adapt (Trend) •Condenser Unit and control by others. "Ecosmart Connect & Adapt models only. HINGED OR REMOVABLE ACCESS PANELS INTEGRAL BASE FRAME WITH SLOTS
Open the catalog to page 7BPS BOXER PACKAGED SOLUTIONS INTERNAL FEATURES AND BENEFITS n HIGHLY ENERGY EFFICIENT HEAT EXCHANGER BPS is available with either a plate or thermal wheel heat exchangers. Thermal Wheels are ErP 2018 compliant. As standard there is a purge sector and bypass provided by interrupting the wheel rotation. The plate HX is available as 2016 or 2018 ErP compliant. The heat exchanger has coefficients of up to 94%+. n DIRECT EXPANSION (DX) All DX coils used in BPS are suitable for reverse cycle, capable of providing heating and cooling. Our DX reverse cycle packages within Ecosmart Connect and Adapt...
Open the catalog to page 8n EASILY REMOVABLE BLOWERS FOR QUICK & EASY MAINTENANCE n HIGHLY ENERGY EFFICIENT THERMAL WHEEL OR PLATE HEAT EXCHANGER n OPTIONAL BUILT IN ECOSMART CLASSIC, CONNECT OR ADAPT CONTROL (Shown below with PAC controller) p Model shown: Thermal Wheel Unit.
Open the catalog to page 9BPS BOXER PACKAGED SOLUTIONS - UNIT 12 PERFORMANCE & TECHNICAL INFORMATION BPS PERFORMANCE FOR PLATE HEAT EXCHANGER & THERMAL WHEEL UNITS 1200 ISO 5801 2007 AMCA 300 100% Extract Static 800 100% Supply Static 600 200 sfp 1.9 (Fully Loaded Unit) 0 0.1 Example Selection: 1.5m3/s @ 220Pa complete with LPHW heater, 2018 Thermal Wheel, LPHW frost coil, chilled water, attenuation and Ecosmart Connect control, SFP = 1.4 W(l/s). BPS TECHNICAL INFORMATION Unit Code Voltage / Phase / Frequency *Includes separate supply for 24kW Heater element. ** Add relevant control option. i.e AT, CO, ES. # Add...
Open the catalog to page 10BPS BOXER PACKAGED SOLUTIONS - UNIT 12 PERFORMANCE & TECHNICAL INFORMATION BPS B612V (ErP 2016) NOISE DATA FOR PLATE HEAT EXCHANGER UNITS Plate Heat Exchanger Fan Code B612V B612V B612V B612V B612V Type Open Discharge Open Intake Open Supply Open Extract Breakout BPS B812V (ErP 2018) NOISE DATA FOR PLATE HEAT EXCHANGER UNITS Plate Heat Exchanger Fan Code B812V B812V B812V B812V B812V Type Open Discharge Open Intake Open Supply Open Extract Breakout BPS B812T NOISE DATA FOR THERMAL WHEEL UNITS Thermal Wheel Fan Code B812T B812T B812T B812T B812T Type Open Discharge Open Intake Open Supply...
Open the catalog to page 11BPS BOXER PACKAGED SOLUTIONS - UNIT 12 COIL DATA COIL DATA @ 100% SPEED Note: performance is based on an indoor (or space, room etc.) condition of 21°C @ 50%RH.
Open the catalog to page 12BPS BOXER PACKAGED SOLUTIONS - UNIT 17 PERFORMANCE & TECHNICAL INFORMATION BPS PERFORMANCE FOR PLATE HEAT EXCHANGER & THERMAL WHEEL UNITS 1200 ISO 5801 2007 AMCA 300 200 sfp 1.9 (Fully Loaded Unit) 0 0.1 Example Selection: 1.7m3/s @ 300Pa complete with LPHW heater, 2018 Thermal Wheel, LPHW frost coil, chilled water, attenuation and Ecosmart Connect control, SFP = 1.6 W(l/s). BPS TECHNICAL INFORMATION Unit Code Voltage / Phase / Frequency *Includes separate supply for 36kW Heater element. ** Add relevant control option. i.e AT, CO, ES. # Add relevant handing. i.e L (Left) R (Right). ***...
Open the catalog to page 14BPS BOXER PACKAGED SOLUTIONS - UNIT 17 PERFORMANCE & TECHNICAL INFORMATION BPS B617V & B817V NOISE DATA FOR PLATE HEAT EXCHANGER UNITS * Insert either 6 or 8 in fan code depending on ErP. Plate Heat Exchanger Fan Code B*17V B*17V B*17V B*17V B*17V Type Open Discharge Open Intake Open Supply Open Extract Breakout BPS B817T NOISE DATA FOR THERMAL WHEEL UNITS Thermal Wheel Fan Code B817T B817T B817T B817T B817T Type Open Discharge Open Intake Open Supply Open Extract Breakout THERMAL WHEEL & PLATE HEAT EXCHANGER UNITS - EFFICIENCY B17 THERMAL WHEEL & HEAT EXCHANGER HEAT RECOVERY B17 THERMAL...
Open the catalog to page 15All Nuaire catalogs and technical brochures
-
HAVEN BROCHURE
11 Pages
-
EXTRACT FANS
20 Pages
-
BESPOKE BOXER
15 Pages
-
Q-Aire Catalogue
48 Pages
-
XBOXER XBC
60 Pages
-
ANTI-CONDENSATION UNIT
7 Pages
-
Smoke fans
54 Pages
-
Twin fans
62 Pages
-
OEM solutions
14 Pages
-
AIR HANDLING UNITS CATALOGUE
157 Pages
-
SUPPLY & EXTRACT
131 Pages
Archived catalogs
-
AHU BOXER MSE
2 Pages
-
OEM
11 Pages