Overview: The NIBE F1345 is a two-stage heat pump designed for heating large buildings using various natural heat sources. It features less than 3 kg of refrigerant per cooling section, eliminating inspection requirements. The system includes two scroll compressors capable of supplying up to 65°C, offering enhanced power control and operational security.
Specifications: Available in sizes of 24, 30, 40, and 60 kW, the heat pump can scale up to 540 kW with multiple units. It includes soft start relays, load monitors, and low-energy circulation pumps. The system is prepared for pool heating and can control up to four heating systems with additional accessories. The COP is up to 4.51 at 0/35°C according to EN 14511.
Installation Methods: The heat pump can utilize rock, surface soil, ground water, and lake as heat sources, each requiring different installation techniques. It is adaptable for various building types and requires minimal space.
Operation: The F1345 transfers energy from the brine to the refrigerant, which is compressed to heat the medium circuit. It can prioritize hot water production and is compatible with external additional heaters.
Installation Guidelines: The heat pump should be installed on a firm base in a noise-insensitive area, with specific clearances for maintenance to minimize noise transmission.
Display and Controls: The unit features an easy-to-read display with a menu system for navigation and settings, including a status lamp and control buttons.
Key Components: The system includes cooling modules, circulation pumps, and a control system, with detailed specifications for each component.
Control Knob and Switch: The control knob allows menu navigation and value adjustments. The switch has three positions: On, Standby, and Emergency mode.
Menu System: The heat pump features five main menus: Indoor Climate, Hot Water, Info, Heat Pump, and Service, with advanced settings accessible through the Service menu.
Pipe Installation: Installation must comply with current norms, with specific temperature limits and requirements for external shut-off valves and proper insulation.
Pressure Expansion Vessel: The brine circuit requires a pressure expansion vessel, dimensioned according to specific diagrams for ethanol or ethylene glycol brine solutions.
Inspection and Collector Guidelines: Heating installations must be inspected by qualified personnel, with guidelines for collector lengths and installation conditions provided.
Control and Basic Functions: The heat pump uses outdoor temperature-controlled heating, with options for hot water production and custom heating curves.
Alarm Indications: The system features a red status lamp and a display for detailed fault information during an alarm, with an alarm log for recording data.
Additional Heat: The F1345 can operate with an additional heater, useful before the completion of collector installation.
Room Control: The F1345 can be enhanced with a room sensor for accurate temperature measurement and stabilization.
External Control (AUX Input): The F1345 can be controlled by external systems via AUX inputs, with functions like compressor blocking and fan speed activation.
Step Controlled Additional Heat: Additional heat is necessary during cold days, managed in steps by external relays.
Master/Slave Configuration: Multiple F1345 units can be interconnected, supporting up to 540 kW in the system.
Software Controlled Output (AUX Output): External connections can be made via a relay function for alarms and pump control.
Load Monitor: Integrated load monitors manage electrical steps to prevent main fuse tripping.
USB Service Outlet: A USB socket is available for software updates and information logging.
Extended Functions: The F1345 supports additional functions like pool heating and solar heating, requiring specific accessories.
Groundwater Pump: With the AXC 50 accessory, a groundwater pump can be connected as a heat source.
Solar Heating: The Solar 42 accessory allows for solar heating integration.
External Circulation Pump: An external pump can be connected for climate system circulation.
MODBUS and SMS Control: The MODBUS 40 accessory enables BMS system integration, while the SMS 40 accessory allows mobile phone control.
Room Unit: The RMU 40 accessory allows control from a different building location.
Air Collector: The NIBE AMB 30 accessory uses outdoor air as a heat source.
Hybrid Operation: The heat pump operates in different modes based on outdoor air temperature, using the AMB 30 module or ground/rock collector as needed.
Installation Specifications: The document lists output data at nominal flow according to EN 255 and EN 14511 standards, specifying output, cooling, and electrical output in kW for different models.
Electrical Data: Rated voltage is 400V 3NAC 50 Hz, with specifications for maximum operating current and recommended fuse protection.
Refrigerant Circuit: The refrigerant used is R407C or R410A, with specific volume and pressure values provided.
Brine and Heating Medium Circuits: Maximum system pressure, flow rates, and temperature ranges are specified, along with sound power and pressure levels.
Dimensions and Weight: The heat pump's dimensions and weight for complete units and cooling modules are listed.
Accessories: Various accessories are available for enhanced functionality, including communication modules and heating solutions.
Compliance and Certification: The document notes that NIBE is ISO-certified under SS-EN ISO 9001:2000 and SS-EN ISO 14001:2004 standards.
See more

Catalog excerpts

F1345-1

NIBE™ F1345 GROUND SOURCE HEAT PUMP 2 STAGE HEAT PUMP WITH ROCK, EARTH, LAKE OR GROUND WATER AS HEAT SOURCE. • ess than 3 kg refrigerant per cooling section/installation. L This means no inspection requirement. • he two scroll compressors can supply up to 65°C to the T heating system. • ouble compressors give better power control, longer operD ating intervals, less wear and greater operational security. • Display unit with easy-to-read colour screen. – See status and make settings via SMS with the SMS 40 accessory. – Control the heat pump externally, with for example BMS, via the accessory MODBUS 40. • he heat pump is available in the following sizes: 24, 30, 40 T and 60 kW. • p to 540 kW with 9 x F1345 in the same system. U • Soft start relays and load monitor factory installed. • nternally installed low energy circulation pumps (not brine I pump for 40 or 60 kW). • repared for pool heating with POOL 40 accessory. P • repared for control of up to four heating systems with P ECS40/ECS41 accessory. • Coefficient Of Performance (COP) up to 4.51 at 0/35 C according to EN 14511. • eparate cooling modules for compressors and brine pumps S give reliable service and lower noise levels. • asy to remove the cooling modules. E • NIBE Uplink compatible NIBE F1345 NIBE F1345 is a heat pump for heating large buildings, such as apartment buildings, churches and industrial premises. F1345 is a flexible product with advanced control equipment and can be adapted to several system solutions. The ground, bedrock or lakes can be used as the heat source. Groundwater can also be used as a heat source, but this requires an intermediate heat exchanger. Another area of use could also be ventilation recovery in multioccupancy buildings. F1345 can control up to four different climate systems (requires accessory), for example a lower flow temperature in the underfloor heating loops than in the radiators. F1345 is also prepared for control of an external additional heater. At hot water production this can be prioritised, selectable with one or more compressors. This permits simultaneous production of heat and hot water.

 Open the catalog to page 1
F1345-2

INSTALLATION METHOD The term “ground source” covers four different heat sources: rock, surface soil, ground water and lake. Rock - using a ground probe Surface soil - using a surface collector Ideal for refurbishment or adaptation from a fossil fuel heating system. Cost-effective energy collection. In the lower subsoil of the so-called “near-surface geothermal layer” lies a heat source with an almost constant temperature that can be utilised all year round. The heat pump collects stored solar energy from a collector in a hole drilled into the rock. The depth of the hole can vary between 90 –...

 Open the catalog to page 2
F1345-3

HOW DOES F1345 WORK? Principle of operation F1345 consists of two heat pump modules (cooling module), circulation pumps and control system with possibility of additional heat. F1345 is connected to the brine and heating medium circuits. In the heat pump evaporator, the brine (water mixed with antifreeze, glycol or ethanol) releases its energy to the refrigerant, which is vaporised in order to be compressed in the compressor. The refrigerant, of which the temperature has now been raised, is passed to the condenser where it gives off its energy to the heating medium circuit and, if necessary, to...

 Open the catalog to page 3
F1345-4

GOOD TO KNOW ABOUT NIBE F1345 Transport and storage F1345 should be transported and stored vertically in a dry place. Position F1345 on a firm base that can take the weight, preferably on a concrete floor or foundation. Use the heat pump’s adjustable feet to obtain a stable set-up. Install with its back to an outside wall, ideally in a room where noise does not matter, in order to eliminate noise problems. If this is not possible, avoid placing it against a wall behind a bedroom or other room where noise may be a problem. Wherever the unit is located, walls to sound sensitive rooms should be...

 Open the catalog to page 4
F1345-5

GOOD TO KNOW ABOUT NIBE F1345 Dimensions Pipe dimensions Connections (XL1) Heating medium supply, external thread (XL2) Heating medium return, external thread (XL6) Brine in, external thread (XL7) Brine out, external thread

 Open the catalog to page 5
F1345-6

GOOD TO KNOW ABOUT NIBE F1345 Equipment FC1

 Open the catalog to page 6
F1345-7

GOOD TO KNOW ABOUT NIBE F1345 Pipe connections XJ 1 Connector, electrical supply to compressor, cooling module EP14 Connection, heating medium flow Connection, heating medium return XJ 2 Connector, electrical supply to compressor, cooling module EP15 XJ 3 Connector, cooling module EP14 HVAC components EP14 Cooling module EP15 Cooling module Sensors etc. Electrical components AA2 Base card AA3 Input circuit board AA4 Display unit AA4-XJ4 Service outlet (No function) AA7 Extra relay circuit board AA26 Base card 2 FC1 Miniature circuit-breaker XJ 4 Connector, brine pump, cooling module EP14 (only...

 Open the catalog to page 7
F1345-8

GOOD TO KNOW ABOUT NIBE F1345 Pump capacity diagram Heating medium side External available pressure, kPa External available pressure, kPa Externt tillgängligt tryck kPa Externt tillgängligt tryck kPa 2 circulation pumps 2 cirkulationspumpar 1 circulation pump 1 cirkulationspump 2 circulation pumps 2 cirkulationspumpar 1 circulation pump 1 cirkulationspump Electrical output per circulation pump, W Electrical output per circulation pump, W Eleffekt per cirkulationspump The pump is adjustable, the flow can be adjusted in menu 5.1.11. 8 NIBE F1345

 Open the catalog to page 8
F1345-9

GOOD TO KNOW ABOUT NIBE F1345 External available pressure, kPa External available pressure, kPa Externt tillgängligt tryck Externt tillgängligt tryck kPa 2 circulation pumps 2cirkulationspumpar 1 circulation pump 1cirkulationspump 2 circulation pumps 2 cirkulationspumpar 1 circulation pump 1 cirkulationspump Electrical output per circulation pump, W Eleffekt per cirkulationspump Electrical output per circulation pump, W The pump is adjustable, the flow can be adjusted in menu 5.1.11. NIBE F1345 9

 Open the catalog to page 9