FireMaster® FastWrap® XL
8Pages

{{requestButtons}}

Catalog excerpts

FireMaster® FastWrap® XL - 1

FireMaster® FastWrap® XL Product Data and Installation Guidelines Product Description Thermal Ceramics FireMaster FastWrap XL is a flexible blanket composed of high temperature fibers classified for applications to 2192°F (1200°C) and fully encapsulated in a durable glass fiber reinforced foil facing for easy handling and installation. Thermal Ceramics FastWrap XL is UL and ULC Listed for 1 and 2 hour fire resistive enclosure protection, zero clearance for kitchen exhaust ducts, electrical circuit protection, and as a component in UL firestop designs for fire resistance rated floors, ceilings, and walls. The core fibers in FastWrap XL are manufactured using Thermal Ceramics patented Superwool® fiber which is an alkaline-earth silicate wool with low biopersistence and therefore increased safety for installers. FastWrap XL is under UL’s Follow-Up Service Program to ensure the consistent quality essential to this life-safety application. Thin and Lightweight at 1-1/2” (38mm) thick, 6 pcf (96 kg/m3) density 2 hour enclosure and firestop system for kitchen exhaust duct Contours easily to complex duct designs Zero clearance to combustibles Grease duct installation UL and ULC Listed with butt joints at all seams on both layers Fully foil encapsulated for fast and clean installation 1, 2 and 3 hour enclosure and firestop system for hazardous exhaust ducts, pressurization ducts, clothes dryer exhaust ducts, trash and linen chutes, and other fire rated HVAC ducts Contains 2192°F (1200°C) rated fibers 1 hour electrical circuit integrity protection Microbial Resistance validated by UL Environment Good sound absorption Engineered and tested solutions for fire protection of structural steel and storage vessels per ASTM E119, ISO 834, and UL1709 Compliant to IMC, NFPA 96, UMC, CMC, CNBC Publication Date: 04 July 2024 Code: BL.21 1 of 8 www.morganthermalceramics.com Email: marketing.tc@morganplc.com Thermal Ceramics is a bus

Open the catalog to page 1
FireMaster® FastWrap® XL - 2

FireMaster® FastWrap® XL Product Data and Installation Guidelines Performance Specifications CSI Spec and AutoCAD available online, www.arcat.com/sd/clients/thermcer.html. Reference Standard Grease Duct Enclosure System Thermal Ceramics FireMaster FastWrap XL is a flexible high temperature insulation rated to 2192°F (1200°C) that is fully encapsulated in FSP facing. The duct enclosure system shall be listed by UL and /or ULC per ASTM E 2336, CAN/ULC S144 and ISO 6944 for 1-, 2- and 3-hour rating and zero clearance to combustibles, and tested per ASTM E84 for a flame/smoke rating less than...

Open the catalog to page 2
FireMaster® FastWrap® XL - 3

FireMaster® FastWrap® XL Product Data and Installation Guidelines B. Installation on HVAC Duct per ISO 6944 (Figure 1) FireMaster FastWrap XL shall be installed by a qualified contractor in accordance with manufacturer’s instructions and laboratory System requires one layer of insulation applied directly to the duct design listings. with 3” (75mm) overlaps at all seams. The insulation is cut to a length sufficient to wrap around the duct and provide a 3” (75mm) Materials and Equipment overlap where the blanket ends meet. Adjacent blankets are • FireMaster FastWrap XL blanket installed to...

Open the catalog to page 3
FireMaster® FastWrap® XL - 4

FireMaster® FastWrap® XL Product Data and Installation Guidelines shown in Figure 2. When this method is used, the FastWrap XL must be mechanically attached on either side of the fire rated assembly using one of the attachment methods described in Section D, spaced a maximum of 1-1/2” (38mm) from the fire rated assembly. Field Fabricated Access Doors - Each access door assembly has four threaded rods 1/4 inch (6mm) in diameter and 5” (127mm) in length, with one welded to each corner of the door opening. Hollow steel tubes, 4-1/2” (114mm) long are installed outside the G. Support Hanger...

Open the catalog to page 4
FireMaster® FastWrap® XL - 5

FireMaster® FastWrap® XL Product Data and Installation Guidelines Maintenance and Repair No maintenance is required when installed in accordance with Thermal Ceramics installation instructions. If damage is limited to the foil facing, aluminum foil tape can be used to repair the foil facing. If an area of blanket is found to be damaged, the following procedure must be incorporated. If the damaged area is larger than 8” (203mm) x 8” (203mm) the entire wrap section must be removed and replaced according to Thermal Ceramics installation instructions. If the damaged area is small (less than 8”...

Open the catalog to page 5
FireMaster® FastWrap® XL - 6

FireMaster® FastWrap® XL Product Data and Installation Guidelines Whilst the values and application information in this datasheet are typical, they are given for guidance only. The values and the information given are subject to normal manufacturing variation and may be subject to change without notice. Morgan Advanced Materials – Thermal Ceramics makes no guarantees and gives no warranties about the suitability of a product and you should seek advice to confirm the product’s suitability for use with Morgan Advanced Materials - Thermal Ceramics. Publication Date: 04 July 2024 Code: BL.21 6...

Open the catalog to page 6
FireMaster® FastWrap® XL - 7

FireMaster® FastWrap® XL Product Data and Installation Guidelines Whilst the values and application information in this datasheet are typical, they are given for guidance only. The values and the information given are subject to normal manufacturing variation and may be subject to change without notice. Morgan Advanced Materials – Thermal Ceramics makes no guarantees and gives no warranties about the suitability of a product and you should seek advice to confirm the product’s suitability for use with Morgan Advanced Materials - Thermal Ceramics. Publication Date: 04 July 2024 Code: BL.21 7...

Open the catalog to page 7
FireMaster® FastWrap® XL - 8

FireMaster® FastWrap® XL Product Data and Installation Guidelines Whilst the values and application information in this datasheet are typical, they are given for guidance only. The values and the information given are subject to normal manufacturing variation and may be subject to change without notice. Morgan Advanced Materials – Thermal Ceramics makes no guarantees and gives no warranties about the suitability of a product and you should seek advice to confirm the product’s suitability for use with Morgan Advanced Materials - Thermal Ceramics. Publication Date: 04 July 2024 Code: BL.21 8...