  3. 3.6/7.2/12/24kV Vacuum Circuit Breakers Type VPR

3.6/7.2/12/24kV Vacuum Circuit Breakers Type VPR

3.6/7.2/12/24kV Vacuum Circuit Breakers Type VPR
1 / 23 PagesView full catalog

3.6/7.2/12/24kV Vacuum Circuit Breakers Type VPR

Product catalog summary
Introduction
The document introduces the VPR Series Vacuum Circuit Breakers by Mitsubishi Electric, highlighting their advanced technology and safety features, designed to meet future needs with enhanced environmental and maintenance measures.
Specifications
The VPR Series features Mitsubishi Electric's vacuum interrupter technology, resulting in a compact design that is 16% smaller than previous models. These self-cooling circuit breakers support rated currents from 600 to 3,150A, comply with IEC 62271-100-2012 standards, and have passed type tests for classes M2, E2, and C2, ensuring high reliability and safety.
Safety and Environmental Measures
Safety is enhanced by minimizing exposure to live parts, even in high-rated models, to prevent hazards. Mechanical parts are coated with long-life grease, extending the lubrication cycle from three to six years. The circuit breakers exceed RoHS standards by being free from six hazardous substances and use rust-proof treatments free of hexavalent chromium.
Design and Operation
The VPR Series includes a new withdrawable mechanism with a door-closed option, reducing operating effort and enhancing safety. It offers options for additional auxiliary and earthing switches and is compatible with previous series mounting frames for easy integration.
Technical Information
Advanced technologies like 3D CAD and CAE ensure reliability and safety. The vacuum interrupters are optimized for size and performance, with a 16% size reduction. The document details the VCB structure, operation mechanisms, and thermal fluid analysis for efficient heat release.
Standards and Testing
The document outlines mechanical and electrical endurance classifications according to IEC standards, with tables showing operating sequences for classes M1, M2, E1, and E2. It describes the probability of arc restrike during capacitive current switching tests, with class C2 being highly reliable.
Conclusion
The VPR Series Vacuum Circuit Breakers offer advanced technology, high reliability, and enhanced safety features, making them suitable for future electrical engineering needs.
Mounting and Installation
The document details components and installation requirements, including mounting screws, side-lock plates, and insertion holes. A φ5mm unlocking pin is required for operation, with specific dimensions provided for installation.
Capacitor Tripping Device (CTD)
The CTD allows remote tripping of the circuit breaker without control power, essential for operation under power loss conditions.
Operation Mechanism
The operation mechanism involves a control circuit managing the closing and tripping of the circuit breaker, with detailed diagrams and tables outlining control voltage, current requirements, and timing for AC and DC operations.
Control Circuit Diagrams
Figures illustrate the basic control circuit, showing the state of the circuit breaker, motor circuit, and operation sequence for closing and tripping, highlighting components like limit switches, auxiliary relays, and coils.
Technical Specifications
Tables provide detailed specifications for control voltages, current flow times, and operational ratings, crucial for correct setup and operation.
Surge Protection and Standards
The document discusses surge protection devices and compliance with standards like JEC-2300 and IEC 62271-100, emphasizing adherence to prevent damage and ensure reliable operation.
Operating Environment
Normal service conditions are specified, including temperature, humidity, and pollution levels, with precautions for installation sites to avoid excessive dust, corrosive gases, and vibrations.
Service Life and Maintenance
The service life of the VCBs is specified at 10,000 operations for mechanical and load switching service life. Regular maintenance and inspections are recommended to ensure longevity and performance.
See more

Catalog excerpts

3.6/7.2/12/24kV Vacuum Circuit Breakers Type VPR-1

AMITSUBISHI for a greener tomorrow VPR Series Vacuum Circuit Breakers Safety & Quality

 Open the catalog to page 1
3.6/7.2/12/24kV Vacuum Circuit Breakers Type VPR-2

Milffe) !L&wiJ§) @if ami iaii§% AMIemdj TrbiDQiiignj y§ej @jfj tjt© Ha tesfr Tie.c h n olo.gteS) Vac u u mi <§i§ii BreakerrS] E^silepeJ 1M tjnej pulyjej wjithi in ha need I Bnv/iiionmental llgassesj art Maintenance; IfeajMife^ • Incorporates Mitsubishi Electric vacuum interrupter technology, realizing a more compact vacuum interrupter (VI) 16% smaller than in the previous type* and high reliability (class E2). Self-cooling vacuum circuit breakers (VCBs) that do not require a fan to be mounted on the panel. Available in a wide range, from rated current of 600 to 3,150A. • Compliant with IEC 62271-100-2012...

 Open the catalog to page 2
3.6/7.2/12/24kV Vacuum Circuit Breakers Type VPR-3

Cutting-edge Technologies Using 3D CAD and CAE VCB Structure to Ensure the Utmost Levels of Reliability and Safety Operating Mechanism Through use of thermal fluid analysis, we have realized efficient release of heat to the cylinder-shaped insulation frame covering the VCB main circuit part, enabling a self-cooling mechanism up to a rated current of 3,150A. Greater performance reliability and extension of the lubrication cycle from three to six years through measures for the operating mechanism such as minimizing the number of parts, reducing the number of moving parts, adopting oilless bearings...

 Open the catalog to page 3
3.6/7.2/12/24kV Vacuum Circuit Breakers Type VPR-4

Type Selection M2, E2, and C2 Classes Described in the Specifications (IEC62271-100) Classification as for Mechanical Endurance ( M1 and M2 ) The IEC standards broadly divide the mechanical operating test into classes M1 and M2. At the control voltages shown in Table 1, class M1 requires the rated operation sequence to be performed 2,000 times in total while class M2 requires the rated operation sequence to be performed 10,000 times in total. At five times the actuating cycle of class M1, class M2 represents a highly reliable operation class. Table 1 M1 and M2 operating sequence. Control voltage...

 Open the catalog to page 4
3.6/7.2/12/24kV Vacuum Circuit Breakers Type VPR-5

Ratings Table 3 List of Ratings (JEC / IEC Standards). Type Closing operating mechanism Table 4 List of Ratings (JEC / IEC Standards). Closing operating mechanism Motor-spring charged mechanism Motor-spring charged mechanism JEC-2300-2010 / IEC 62271-100-2012 Rated normal current (A) Rated frequency (Hz) Rated short-circuit breaking current (kA) Rated short-circuit breaking current (kA) Rated making current (kA) Rated short-time withstand current (kA) Rated making current (kA) Rated short-time withstand current (kA) Rated opening time (s) Power frequency (JEC/IEC) Lightning impulse(JEC/IEC) Type...

 Open the catalog to page 5
3.6/7.2/12/24kV Vacuum Circuit Breakers Type VPR-6

Description and Structure VCB Configuration Mounting Frame Configuration Manual charging handle aperture Primary junction Manual close button (with button cover) Manual trip button Closing spring indicator Secondary junction Front view of mounting frame (with earthing switch) Rear view of mounting frame (with earthing switch) Closing spring charged indication switch (page 21) Additional auxiliary switch (page 22) Padlock device for close and trip button (page 22) Short-circuit capacity earthing (page 24) Mechanical locking device (page 21) Additional shunt tripping coil (page 22) Position switch...

 Open the catalog to page 6
3.6/7.2/12/24kV Vacuum Circuit Breakers Type VPR-7

I600A/630A, 1,200A/1,250A Rating: External Dimensions (Circuit Breaker) Fixed (type-L) Manual close Withdrawable with door closed Code B: with interlock handle aperture Withdrawable with door open Code B: with interlock without interlock Draw-out \ Maximum handle aperture \ displacement Interlock lever Shutter guide \ Additional auxiliary switch (option) 600A/630A, 1,200A/1,250A Rating: External Dimensions (Mounting Frame) this distance keep 126mm or more, or cover busbars with insulation cover. Details of main-circuit terminal Details of main-circuit terminal that this distance keep cover busbars...

 Open the catalog to page 7
3.6/7.2/12/24kV Vacuum Circuit Breakers Type VPR-8

1,600A, 2,000A Rating: External Dimensions (Circuit Breaker) Fixed (type-L) Closing spring charge indicator Withdrawable with door closed Manual charging handle aperture Withdrawable with door open Shutter guide Additional auxiliary switch (option) ■ 1,600A, 2,000A Rating: External Dimensions (Mounting Frame) this distance keep 1 26mm or more, or cover busbars with insulation cover. Details of main-circuit terminal Details of main-circuit terminal that this distance keep cover busbars with insulation cover.

 Open the catalog to page 8
3.6/7.2/12/24kV Vacuum Circuit Breakers Type VPR-9

■ 2,500A, 3,000A/3,150A Rating: External Dimensions (Circuit Breaker) Withdrawable with door closed (type-M) Withdrawable with door open (types C, D and G) 2,500A, 3,000A/3,150A Rating: External Dimensions (Mounting Frame) Air clearance for ventilation (more than 400cm; Details of main-circuit terminal that this distance keep cover busbars with insulation cover. edge busbars. Details of main-circuit terminal that this distance keep cover busbars with insulation cover.

 Open the catalog to page 9
3.6/7.2/12/24kV Vacuum Circuit Breakers Type VPR-10

Withdrawable: Standard Connection Diagram (Code A) Note: There is no LSO in a fixed (type-L) This device is not supplied with the VCB; please order separately. The shunt tripping coil (STC) is for DC only; for AC operation, use a capacitor tripping device for conversion to DC. When the auxiliary switch has micro current specifications, are contacts for micro current. the micro current specification auxiliary switch, the tripping coil disconnection monitoring the capacitor tripping device and LS3. In the above wiring diagram; Circuit breaker: Opened state Closing spring : Discharged state Motor...

 Open the catalog to page 10
3.6/7.2/12/24kV Vacuum Circuit Breakers Type VPR-11

Accessories Secondary Connector Lifting Adapter The panel side lead wires connect the input voltage and VCB unit. They are inserted in the control plug section of the VCB. A lifting adapter used to lift the VCB. Please refer to the directions for use in the instruction manual. Number of accessories: 1 per unit Number of accessories: 1 per 1-5 VCBs (min. 1) Code B Manual Charging Handle This handle enables the closed spring to be charged manually by inserting the handle in the front manual charging handle aperture and rotating clockwise for approximately 15 rotations. Shipping Clamp Number of...

 Open the catalog to page 11
3.6/7.2/12/24kV Vacuum Circuit Breakers Type VPR-12

iCIosing Spring Charged Indication Switch Used for charging/discharging output of closing springs. Table 5 Contact ratings. 1: Please refer to the standard connection diagram for 2: Fig. 38 shows a closed spring in a dischrged state. 3: LS3 (limit switch for the spring charge indicator) iTripping Coil Disconnection Monitoring This function monitors disconnection of the tripping coil and control connector based on output from the input terminal. The disconnection monitoring current is 30mA or below. ■ Additional Auxiliary Switch (Additional 5a5b) The switch makes it possible to add 5a5b to a standard...

 Open the catalog to page 12

All MITSUBISHI ELECTRIC catalogs and technical brochures

  1. PLA-ZM-R32

    2  Pages

  2. PLA-M R32

    2  Pages

  3. PLA-SM R410A

    2  Pages

  4. PUMY-P R410A

    2  Pages

  5. MSZ-LN R32

    2  Pages

  6. I-LIFE2 SLIM

    6  Pages

  7. MSZ-AP R32

    2  Pages

Archived catalogs

  1. MSZ-HR R32

    2  Pages

  2. Hybrid VRF

    36  Pages

  3. PLATNUM

    4  Pages

  4. H2i Family

    20  Pages

  5. CITYMULTI

    96  Pages

  6. Low-Rise

    4  Pages

  7. High-Rise

    4  Pages

  8. switchgear

    16  Pages

  9. MELPRO-D

    64  Pages

  10. escalators

    8  Pages

  11. Matalan

    2  Pages

  12. Power Modules

    32  Pages

  13. H2iMSZ-FH

    2  Pages

  14. MFZ-KT R32

    2  Pages

  15. Office

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.