1. Catalogs
  2. MINIB
  3. COIL – KT3
video corpo

COIL – KT3

COIL – KT3

COIL – KT3

Product catalog summary
COIL – KT3 Characteristics
The COIL – KT3 is a heating unit designed for dry environments, featuring a width of 243 mm. It is part of the medium power series of MINIB convectors and includes a 12V fan. This unit is an economical alternative to the COIL-KT, suitable for spaces with lower heating demands.

Dimensions
- Total width: 243 mm
- Construction height: 125 mm
- Length: 900 to 3000 mm

Usage
The COIL-KT3 is ideal for applications where the COIL-KT would be oversized. It provides efficient heating with a fast reaction time.

Temperature Equation
The heat transfer rate (Q) is calculated using the formula:
(Q = QN * (tw - tA)^m / 50), where:
- m = 1.1059 (temperature exponent)
- tW = mean heating water temperature
- tA = mean air temperature
- QN = nominal heat transfer rate for a temperature difference of 50 ºC

Performance Data
The document provides detailed tables showing the heat transfer rates at various lengths (900 mm to 3000 mm) and speeds (minimum, medium, maximum). The data is organized by mean air temperature (tA) and mean water temperature (tW), illustrating the unit's performance under different conditions.

Conclusion
The COIL-KT3 is a versatile and cost-effective heating solution for environments with moderate heating requirements. Its design and specifications make it suitable for a range of applications, ensuring efficient heat distribution.
See more

Catalog excerpts

COIL – KT3-1

MINIB, s. r. o., Støešovická 49, 162 00 Praha 6 CZ, [email protected] tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779 38 www.minib.cz coil – kt 3 CHARACTERISTICS 6 trough identical with the COIL – P; width 243 mm 6 dry environment heating DIMENSIONS total width 243 mm construction height 125 mm length L 900 to 3000 mm USAGE COIL-KT3 is a fast reacting heating unit from the medium power series of MINIB convectors with the 12V fan. The convector COIL-KT3 is an economically advantageous alternative to the COIL-KT unit for applications where heating demands on interior heating are lower and the COIL-KT would be oversized for the space heat losses. CROSS SECTION OF COIL-KT3 LONGITUDINAL SECTION COIL-KT3 Window where: m= 1,1059 temperature exponent tW, A mean heating water temperature, mean air temperature [ºC] QN nominal heat transfer rate for difference of temperatures tw - tA = 50 ºC [W] Q heat transfer rate for other temperatures [W] TEMPERATURE EQUATION Q = Q ( ) N t m w - ta 50 COIL - KT3 with a fan 62 51 63 246 243 125 Ø30 62 136 Ø30 72 101