COIL – HC

COIL – HC

COIL – HC

Product catalog summary

Product Overview

The COIL - HC with a fan is a highly efficient floor convector designed for both heating and cooling applications. It features a 2-pipe connection system and delivers air tangentially into the interior space, providing effective temperature control.

Key Characteristics

  • Highly effective convector suitable for heating and cooling.
  • 2-pipe connection for combined heating and cooling circuits.
  • Air is blown tangentially across the floor, reaching 3 to 4 meters into the room.
  • Cooling output approximately 1000 W for a 2-meter length unit.
  • Includes an implied condensate outlet.
  • Supplied with connection fittings and flexible 3/8" hoses for heat exchanger connection since May 2009.

Dimensions

  • Total width: 243 mm
  • Construction height: 125 mm
  • Length (L): ranges from 900 mm to 3000 mm

Usage

The COIL - HC convector is specifically designed for floor installation to provide both heating and cooling. The tangential air flow creates a gentle cooling effect in summer, especially in areas away from windows.

Technical Specifications

Temperature Equations

Heating:

Q = QN * ((tW - tA) / 50)^m, where m = 1.0455

Cooling:

Q = QN * ((tW - tA) / 17)^m, where m = 0.864

Where:

  • Q = heat transfer rate at given temperatures [W]
  • QN = nominal heat transfer rate at reference temperatures [W]
  • tW = mean water temperature [°C]
  • tA = mean air temperature [°C]

Heat Transfer Rates

Heat transfer rates are provided for various lengths (900 mm to 3000 mm), mean water temperatures (50°C to 90°C for heating), and mean air temperatures (15°C to 27°C). The data is categorized by fan speed settings: minimum, medium, and maximum.

For example, at 900 mm length and maximum fan speed, heating output ranges from approximately 470 W (50°C water, 22°C air) to 1565 W (90°C water, 22°C air).

Cooling outputs are similarly detailed, with nominal water temperatures around 9°C and air temperatures from 24°C to 27°C, showing increasing cooling capacity with higher water temperature differences and fan speeds.

Installation and Connection

The convector comes with connection fittings and flexible hoses (3/8") for easy integration with heat exchangers. The design includes a condensate outlet to manage moisture during cooling operation.

Summary of Critical Parameters

  • Fan speeds affect heat transfer rates significantly; higher speeds increase capacity.
  • Length of the convector directly correlates with heat transfer capacity.
  • Temperature differences between water and air are critical for performance calculations.
  • Nominal reference temperatures for heating: 70/20°C (water/air).
  • Nominal reference temperatures for cooling: 9/26°C (water/air).

Best Practices and Recommendations

  • Ensure proper connection using supplied fittings and hoses for optimal performance.
  • Consider room layout to maximize tangential air flow effect, especially for cooling.
  • Use temperature equations to adjust expected heat transfer rates for varying operating conditions.
  • Regular maintenance of fan and condensate outlet recommended to maintain efficiency.
See more

Catalog excerpts

COIL – HC-1

MINIB, s. r. o., Støešovická 49, 162 00 Praha 6 CZ, [email protected] tel.: +420 220 180 780, +420 604 767 677 fax: +420 220 180 779 52 www.minib.cz COIL - HC with a fan CHARACTERISTICS 6 very effective convector for heating and cooling 6 2-pipe connection 6 air is blown tangentially into the interior 6 cooling output approximately 1000 W for the 2-meter long convector 6 implied condensate outlet DIMENSIONS total width 243 mm construction height 125 mm length L 900 to 3000 mm USAGE COIL – HC is the MINIB floor convector specially designed for both heating and cooling of the space. The convector has the 2-pipe connection and common cooling and heating circuit. The air is tangentially blown across the floor of the room to a distance of 3 to 4 m – so that in summer there is a lightly flowing cool air effect in locations remote from the windows. This convector has been supplied with connection fittings and flexible hoses “3/8” for connection of the heat exchanger since 1st May 2009. coil – HC CROSS SECTION OF COIL-HC Window LONGITUDINAL SECTION COIL-HC Ø30 125 243 89 66 58 118 48 59 245 Ø18 Ø30 56 112 152 72 TEMPERATURE EQUATION FOR HEATING where: m= 1,0455 temperature exponent tW, A mean heating water temperature, mean air temperature [ºC] QN nominal heat transfer rate for temperatures tw /tA = 70/20 ºC [W] Q heat transfer rate for other temperatures [W] Q = Q ( ) N t m w - ta 50 TEMPERATURE EQUATION FOR COOLING where: m= 0,864 teplotní exponen tW, A mean heating water temperature, mean air temperature [ºC] QN nominal heat transfer rate for temperatures tw /tA = 9/26 ºC [W] Q heat transfer rate for other temperatures [W] Q= Q ( ) N t m w - ta 17