Technicalinformation FICIENT Insulated Metal Panels TM
Open the catalog to page 1General Information_ Material Specifications Product Information Insulated Battenlok®, Insulated R Panel, Grand V, Grand H 6 Classic, Vintage, Royal, Summit 7 Technical Data_ Environmental, Foam Properties, Fire Resistance, Structural and Roof Listings 8 Panel Weights Per Foot of Width Allowable Loads Summit Wall Panel 1 1 Insulated Battenlok® Roof Panel 12 Insulated R Roof & Wall Panel 14 Royal Wall Panel 16 Classic Wall Panel 1 7 Vintage Wall Panel 20 Grand V Wall Panel 21 Thermal Performance of IMPs 22
Open the catalog to page 2General Information General Information Insulated Metal Panels, or IMPs, are structural wall and roof panels that also provide significant insulation properties. They are typically made of two metal skins on either side of a rigid foam insulation layer. The metal skins are chemically bonded to the foam and act in conjunction with it to provide a composite structural member capable of spanning distances to 10 feet or more while supporting transverse loads. The foam core acts alone to provide the thermal transmission resistance, or R-Value, as part of a building envelope system. Other aspects such...
Open the catalog to page 3General Information can only be measured by testing since the foam provides some support to compression elements in the skin. Compressive strength of the foam by itself is also accurately determined by panel testing. However, in order to provide increased resistance to foot traffic and aid in proper fastener installation, it is often specified separately. ASTM D1621 is used to determine the foam compressive strength in this case. Often, the tensile strength and shear strength of the foam core itself is specified by the designer. Although the tensile strength of the foam is important to the behavior...
Open the catalog to page 4General Information manufacturers publish R-Values inclusive of air film effects. An R-value should never be specified without clear indication of all of these parameters. An example might be: Insulated metal panels must have an R-Value of 14 hr-ft-deg F/BTU when tested to ASTM C1363 at a mean temperature of 75 degrees Fahrenheit with horizontal heat flow. The tested specimen must be at least 64 square feet and incorporate at least two side joints. Air film effects shall not be included in the R-Value. Fire Design Only by providing these specific parameters can the designer be assured of adequate...
Open the catalog to page 5Technical Design Information Product Information ® Eco-ficient INSULATED BattenLok Appearance E xterior profile has a 2" high standing seam with an embossed Mesa pattern as standard and can be smooth on roof slopes less than 3:12 Interior skin has the stucco-embossed Mesa profile Concealed clip attachment to structure Application Roof Gauges E xterior: 24 and 22 I nteriors: 26, 24 and 22 Widths: 30", 36" and 42" T hicknesses: 2", 2 ½", 3" ,4", 5" and 6" L ength: Recommended maximum is 50' 30", 36" or 42" 2" 4" Exterior 2", 2½", 3", 4", 5" or 6" Interior Eco-ficient INSULATED R Panel Appearance...
Open the catalog to page 6Technical Design Information Eco-ficient CLASSIC Appearance Contemporary styling ideal for custom-designed or conventional building construction Exterior skin has 7/16" deep flutes at 6" on the center with minor ribs in between and a stucco-embossed finish Interior skin has a stucco-embossed Mesa profile Application Vertical Wall Gauges E xterior: 26, 24 and 22 I nterior: 26, 24 and 22 Width: 42" Thicknesses: 2", 2 ½", 3", 4", 5" and 6" L ength: Recommended maximum is 50' 42” Exterior Surface 4.2” 4.2” Eco-ficient VINTAGE Appearance Exterior skin with Aztec-embossed pattern resembling old-world...
Open the catalog to page 7Technical Design Information Technical Data : Performance and Certifications The results of the test methods listed in the previous section are presented on the following table, with the exception of ASTM E72, E1592, ASTM C518, and ASTM C1363. ASTM E72 and E1592 are summarized in the Load Tables section of this document and results for ASTM C518 and C1363 (R-values, k-factors, U-factors) can be found on the MBCI website or by calling (877)713-6224. Category Characteristic Test Method Purpose Result Environmental Thermal Transmission ASTM C518 Measure the heat transmission coefficient per unit...
Open the catalog to page 8Panel Weights In Pounds Per Square Foot For 36" Wide Panels
Open the catalog to page 9Panel Weights In Pounds Per Square Foot For 42" Wide Panels For panel weights for 24" wide panels, please visit www.ecoficient5eries.com.
Open the catalog to page 10Allowable Load Chart Insulated Battenlok® Roof Panel Allowable Load Chart - (Allowable Stress Design/Allowable Loads in PSF) Panel Depth Support Condition Load Type Connection Support Spacing 2.5' 3' 3.5' 4' 4.5' 5' 5.5' 6' 6.5' 7' 7.5' Live/Press -- 472.95 394.13 337.82 295.60 262.75 236.48 214.87 192.31 173.08 156.49 142.04 Suction no Fab-Lok®7 115.44 96.06 82.19 71.76 63.64 57.13 51.79 47.32 43.53 40.28 37.44 Suction ®7,9 1 Fab-Lok 154.75 128.73 110.11 96.12 85.21 76.45 69.27 63.27 58.17 53.79 49.98 Live/Press -- 462.79 382.48 324.92 281.66 248.00 221.10 199.14 180.92 165.58 152.50 141.25...
Open the catalog to page 13Insulated R Panel Roof & Wall Panel Allowable Load Chart - (Allowable Stress Design/Allowable Loads in PSF)
Open the catalog to page 14Allowable Load Chart Insulated R Panel Roof & Wall Panel Allowable Load Chart - (Allowable Stress Design/Allowable Loads in PSF) Panel Depth Support Condition Load Type Connection Support Spacing 3' 4' 5' 6' 7' 8' 9' 10' 11' 12' 13' Live/Press -- 415.47 298.99 227.37 178.68 143.49 117.03 96.60 80.51 67.66 57.29 48.82 Suction wall3,5 218.31 163.73 130.99 109.16 93.56 81.87 72.77 65.49 59.54 54.58 50.38 Suction roof 218.31 163.73 130.99 109.16 93.56 81.87 72.77 65.49 59.54 54.58 50.38 1 1-Span Live/Press 5" 2-Span 4,5 Suction Live/Press 3-Span and greater 1 417.57 303.13 233.87 187.56 154.50 129.79...
Open the catalog to page 15Allowable Load Chart Royal Wall Panel Allowable Load Chart - (Allowable Stress Design/Allowable Loads in PSF) Panel Depth Support Condition Load Type Connection Support Spacing 3' 4' 5' 6' 7' 8' 9' 10' 11' 12' 13' Pressure 1-Span -- 274.81 206.11 164.89 137.41 117.78 103.05 91.60 79.09 65.37 54.93 46.80 Suction no Fab-Lok®6 73.52 54.89 43.65 36.11 30.69 26.59 23.38 20.79 18.65 16.86 15.32 96.97 72.44 57.66 47.75 40.64 35.27 31.06 27.66 24.87 22.52 20.52 Suction with Fab-Lok ®6,8 Pressure 6" 266.94 196.66 154.43 126.39 106.55 91.86 80.60 71.72 64.57 58.70 53.80 no Fab-Lok®6 97.25 71.64 56.26 46.04...
Open the catalog to page 1745 Pages
76 Pages
69 Pages
96 Pages
79 Pages
2 Pages
4 Pages
4 Pages
4 Pages
8 Pages
6 Pages
8 Pages
20 Pages
4 Pages
32 Pages
20 Pages
102 Pages
76 Pages
60 Pages
32 Pages
94 Pages
28 Pages
76 Pages
48 Pages
76 Pages
62 Pages
108 Pages
4 Pages
4 Pages
8 Pages
8 Pages
4 Pages