Double-Lok over R

Product catalog summary
General Information: The document provides technical installation guidelines for the Double-Lok® roofing system over an existing "R" panel. It stresses the importance of thoroughly reading the manual before installation and inspecting all materials. In case of discrepancies between project drawings and the manual, the project drawings take precedence.
Design Information: The Double-Lok® roof can be installed over an existing "R" panel with minimal modifications. It allows for venting or additional insulation between the old and new roofs. The installation adds approximately 1.5 lbs per square foot to the existing structure, and a professional engineer should verify the structure's capacity to support this load. Compliance with current building codes is essential, which may require adjustments in purlin spacing.
Product Checklist: The checklist includes components such as Double-Lok® panels, clips, closures, and sealants, specifying dimensions, materials, and intended use to ensure proper installation and compatibility with the existing structure.
Installation Procedures: Detailed instructions are provided for retrofitting the Double-Lok® system, including clip attachment and venting options. The manual outlines specific scenarios such as edge zones, vented roof cavities, and insulated roof cavities, with corresponding installation techniques.
Recommendations: The document advises consulting with a registered professional engineer for load assessments and ensuring all installations comply with the latest building codes. It also suggests surveying the existing roof to determine the need for narrower panels if the existing roof is out of module.
Overview: This document provides technical guidelines for the installation of MBCI's Double-Lok® roof system over existing 'R' panel roofs, including cautions, preparatory requirements, and design specifications.
Cautions: The Double-Lok® roof system does not provide diaphragm capabilities or purlin stability, necessitating additional bracing. The minimum recommended roof slope is 1/4 on 12 to prevent ponding and maintain material warranties. Design details are illustrative and must be adapted to specific environmental conditions and building codes. Installation must comply with OSHA regulations, and deviations from the manual require MBCI's written approval.
Preparatory Requirements: Preparations include cutting back the eave of the existing 'R' panel roof, installing a retrofit eave angle, and ensuring the existing roof is on plane within specified tolerances. Field cutting of panels should be avoided; if necessary, use nibblers, snips, or shears. Adjust trim conditions if different wall panels or conditions exist.
Design Specifications: Details for edge zone conditions and clip spacing must be determined by a professional engineer. Various fasteners and components are specified for different parts of the installation, including self-drillers and long-life screws with washers. Illustrations provide isometric views of edge zone conditions, vented roof cavities, and insulated roof cavities.
Key Components: Retrofit eave angle, rake angle, and support angles are critical for installation. Fasteners are specified by type and location, ensuring secure attachment of panels and components. Sealers and closures are used to ensure weather-tightness and insulation.
See more

Catalog excerpts

Double-Lok over R-1

Metal Roof and Wall Systems double-lok® Over "R" Panel

 Open the catalog to page 1
Double-Lok over R-2

IMPORTANT NOTICE READ THIS MANUAL COMPLETELY PRIOR TO BEGINNING THE INSTALLATION OF THE DOUBLELOK® OVER “R” PANEL ROOFING SYSTEM. ALWAYS INSPECT EACH AND EVERY PANEL AND ALL ACCESSORIES BEFORE INSTALLATION. NEVER INSTALL ANY PRODUCT IF ITS QUALITY IS IN QUESTION. NOTIFY MBCI IMMEDIATELY IF ANY PRODUCT IS BELIEVED TO BE OUT OF TOLERANCE, SPECIFICATION OR HAS BEEN DAMAGED DURING SHIPMENT. IF THERE IS A CONFLICT BETWEEN PROJECT ERECTION DRAWINGS PROVIDED OR APPROVED BY THE MANUFACTURER AND DETAILS IN THIS MANUAL, PROJECT ERECTION DRAWINGS WILL TAKE PRECEDENCE. The Engineering data contained herein...

 Open the catalog to page 2
Double-Lok over R-3

Houston, TX 877-713-6224 Adel, GA 888-446-6224 Atlanta, GA 877-512-6224 Atwater, CA 800-829-9324 Dallas, TX 800-653-6224 Indianapolis, IN 800-735-6224 Jackson, MS 800-622-4136 Lubbock, TX 800-758-6224 Memphis, TN 800-206-6224 Oklahoma City, OK 800-597-6224 Omaha, NE 800-458-6224 Phoenix, AZ 888-533-6224 Richmond, VA 800-729-6224 Rome, NY 800-559-6224 Salt Lake City, UT 800-874-2404 San Antonio, TX 800-598-6224 TABLE OF CONTENTS GENERAL INFORMATION Design Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .DLRF-2 Product...

 Open the catalog to page 3
Double-Lok over R-4

Houston, TX 877-713-6224 Adel, GA 888-446-6224 Atlanta, GA 877-512-6224 Atwater, CA 800-829-9324 Dallas, TX 800-653-6224 Indianapolis, IN 800-735-6224 Jackson, MS 800-622-4136 Lubbock, TX 800-758-6224 Memphis, TN 800-206-6224 Oklahoma City, OK 800-597-6224 Omaha, NE 800-458-6224 GENERAL INFORMATION Phoenix, AZ 888-533-6224 Richmond, VA 800-729-6224 Rome, NY 800-559-6224 Salt Lake City, UT 800-874-2404 San Antonio, TX 800-598-6224 Over “R” Panel DESIGN INFORMATION 1. The new Double-Lok® roof can be installed over an existing "R" panel roof with minimal alterations. The Double-Lok® 2" standoff...

 Open the catalog to page 4
Double-Lok over R-5

Houston, TX 877-713-6224 Adel, GA 888-446-6224 Atlanta, GA 877-512-6224 Atwater, CA 800-829-9324 Dallas, TX 800-653-6224 Indianapolis, IN 800-735-6224 Jackson, MS 800-622-4136 Lubbock, TX 800-758-6224 Memphis, TN 800-206-6224 Oklahoma City, OK 800-597-6224 Omaha, NE 800-458-6224 Phoenix, AZ 888-533-6224 Richmond, VA 800-729-6224 Rome, NY 800-559-6224 Salt Lake City, UT 800-874-2404 San Antonio, TX 800-598-6224 GENERAL INFORMATION Over “R” Panel PRODUCT CHECKLIST • 24 or 22 gauge • Factory-applied mastic • Pre-punched Double-Lok® Double-Lok® Retro-Fit Clip Zee • 10'-6" length • Used at edge zones...

 Open the catalog to page 5
Double-Lok over R-6

Houston, TX 877-713-6224 Adel, GA 888-446-6224 Atlanta, GA 877-512-6224 Atwater, CA 800-829-9324 Dallas, TX 800-653-6224 Indianapolis, IN 800-735-6224 Jackson, MS 800-622-4136 Lubbock, TX 800-758-6224 Memphis, TN 800-206-6224 Oklahoma City, OK 800-597-6224 Omaha, NE 800-458-6224 GENERAL INFORMATION Phoenix, AZ 888-533-6224 Richmond, VA 800-729-6224 Rome, NY 800-559-6224 Salt Lake City, UT 800-874-2404 San Antonio, TX 800-598-6224 Over “R” Panel PRODUCT CHECKLIST Tape Sealer-Tri-Bead • Used at the Retro-Fit eave angle, outside closures, endlaps and trim connections • Used to fill void at minor...

 Open the catalog to page 6
Double-Lok over R-7

Houston, TX 877-713-6224 Adel, GA 888-446-6224 Atlanta, GA 877-512-6224 Atwater, CA 800-829-9324 Dallas, TX 800-653-6224 Indianapolis, IN 800-735-6224 Jackson, MS 800-622-4136 Lubbock, TX 800-758-6224 Memphis, TN 800-206-6224 Oklahoma City, OK 800-597-6224 Omaha, NE 800-458-6224 Phoenix, AZ 888-533-6224 Richmond, VA 800-729-6224 Rome, NY 800-559-6224 Salt Lake City, UT 800-874-2404 San Antonio, TX 800-598-6224 Over “R” Panel GENERAL INFORMATION PRODUCT CHECKLIST Perforated Vent Drip Double-Lok® Retro-Fit Rake Trim PERFORATED ¹⁄₂" 1" 5 ¹⁄₂" 4³⁄₄" 1" 102° 156° 1" 102° 90° 4³⁄₄" 3 ¹⁄₄" FL-254 Variable...

 Open the catalog to page 7
Double-Lok over R-8

Houston, TX 877-713-6224 Adel, GA 888-446-6224 Atlanta, GA 877-512-6224 Atwater, CA 800-829-9324 Dallas, TX 800-653-6224 Indianapolis, IN 800-735-6224 Jackson, MS 800-622-4136 Lubbock, TX 800-758-6224 Memphis, TN 800-206-6224 Oklahoma City, OK 800-597-6224 Omaha, NE 800-458-6224 DESIGN Phoenix, AZ 888-533-6224 Richmond, VA 800-729-6224 Rome, NY 800-559-6224 Salt Lake City, UT 800-874-2404 San Antonio, TX 800-598-6224 Over “R” Panel PRODUCT CHECKLIST Vented Ridge Trim Fastener #2A "A" • Use in place of fasteners #1E and #4 at all stripouts COLOR 1 ¹⁄₄" " 2 ¹⁄₂ 1 ³⁄₈" ROOF PITCH DIM. A LENGTH PART...

 Open the catalog to page 8
Double-Lok over R-9

Houston, TX 877-713-6224 Adel, GA 888-446-6224 Atlanta, GA 877-512-6224 Atwater, CA 800-829-9324 Dallas, TX 800-653-6224 Indianapolis, IN 800-735-6224 Jackson, MS 800-622-4136 Lubbock, TX 800-758-6224 Memphis, TN 800-206-6224 Oklahoma City, OK 800-597-6224 Omaha, NE 800-458-6224 Phoenix, AZ 888-533-6224 Richmond, VA 800-729-6224 Rome, NY 800-559-6224 Salt Lake City, UT 800-874-2404 San Antonio, TX 800-598-6224 Over “R” Panel GENERAL INFORMATION PREPARATORY REQUIREMENTS 1. The eave of the existing "R" panel roof must be cut back so that it does not extend beyond the face of the building side wall....

 Open the catalog to page 9
Double-Lok over R-10

Houston, TX 877-713-6224 Adel, GA 888-446-6224 Atlanta, GA 877-512-6224 Atwater, CA 800-829-9324 Dallas, TX 800-653-6224 Indianapolis, IN 800-735-6224 Jackson, MS 800-622-4136 Lubbock, TX 800-758-6224 Memphis, TN 800-206-6224 Oklahoma City, OK 800-597-6224 Omaha, NE 800-458-6224 DESIGN Phoenix, AZ 888-533-6224 Richmond, VA 800-729-6224 Rome, NY 800-559-6224 Salt Lake City, UT 800-874-2404 San Antonio, TX 800-598-6224 Over “R” Panel RETRO-FIT ISOMETRIC VIEW OF EDGE ZONE CONDITION E D E N ZO E E G AV E AT U Q E E ON E Z AKE G ED AT R L A L UA L A U Q E EQ EXISTING ROOF PANEL L A U Q E L UA DOUBLE-LOK®...

 Open the catalog to page 10
Double-Lok over R-11

Houston, TX 877-713-6224 Adel, GA 888-446-6224 Atlanta, GA 877-512-6224 Atwater, CA 800-829-9324 Dallas, TX 800-653-6224 Indianapolis, IN 800-735-6224 Jackson, MS 800-622-4136 Lubbock, TX 800-758-6224 Memphis, TN 800-206-6224 Oklahoma City, OK 800-597-6224 Omaha, NE 800-458-6224 Phoenix, AZ 888-533-6224 Richmond, VA 800-729-6224 Rome, NY 800-559-6224 Salt Lake City, UT 800-874-2404 San Antonio, TX 800-598-6224 DESIGN Over “R” Panel RETRO-FIT CLIP ATTACHMENT AT EDGE ZONE CONDITION 2” STAND OFF SLIDING CLIP [HW-2129] DOUBLE-LOK® RETRO-FIT CLIP ZEE 2” DOUBLE-LOK® PANEL EXISTING “R” PANEL PURLIN...

 Open the catalog to page 11
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.