TECHNICAL SPECIFICATIONS Max. size 0: Min. size 0: Tripping pressure: Air flow direction: Free cross section: 710 mm 100 mm DRKr: acc. to customer order RSKr: no specified tripping pressure horizontal or vertical acc. To customer order 100% ATEX The DRKr and RSKr are only approved in specific designs and with appropriate identification for Zones 1, 21 or 2, 22 according to ATEX Directive 2014/34/EU. If the fitter or operator changes the dampers in any way, the ATEX approval becomes null and void. It is important to ensure that the damper and additional equipment are installed in compliance with zoning requirements. In principle, avoid all damage caused by external influences. Never lift dampers by the slats or by the external brass weight. Report any damage, e.g. deformation of slats, dents, impacts or warping of the housing, immediately to the supplier or manufacturer. This may impair the proper functioning of the damper and at best cause dangerous circumstances to occur. ATEX:Und er no circumstances may ATEX dampers be fitted after a fall or impact with visible or concealed damage. These dampers can be fitted or removed to or from a wall or an air conditioning system, or integrated in a duct section. First make sure the air flow is in the proper direction as indicated by the red arrow on the damper housing. Mount the dampers warp-free, on a flat surface and stress-free. Depending on the design, use the threaded holes in the flange or the insert ends. When mounting, make sure that the side marked top is fitted at the top and horizontally. The damper must be adjusted exactly vertically (for horizontal air flow) or exactly horizontally (for vertical air flow). Also avoid drilling swarf, concrete chippings or other installation materials from entering the damper housing. Suction off any soiling inside the housing, otherwise malfunctions may occur. When installation is complete, make sure that the slats and the external tripping mechanism can move freely. Avoid as far as possible any reduction in freedom of movement on customer premises when installing insulation materials, installation ducts, auxiliary structures etc. If this is not observed, it can lead to severe disruptions in operation, e.g. slats touch the damper frame, different tripping pressure, damper fails to open or close, reduced leak tightness, etc. ATEX: All relevant national and international standards and regulations for Ex zones must be observed. On dampers with ATEX functionality in particular, the damper housing must be earthed using the earthing braids attached by the manufacturer. No mechanical changes may be made to the product. In addition, do not attach any components (motors, limit switches, etc.) to the damper if they have not been analyzed for ignition risk by the appropriate manufacturers or approved for ATEX zones. It is prohibited to drill holes or fit bolts or screws in the interior of the dampers. This could lead to damage or disturb damper operation. If there is a risk at the factory that foreign bodies may enter he movement area of the slats, prevent them by suitable means (filters or catchment grills). This prevents the slats from sticking and the possibility of frictional heat developing.

Open the catalog to page 1
Anleitung-DRKr-RSKr - 2

ADJUSTING TRIPPING PRESSURE RSKr: Back-d raught dampers have no specified opening pressure. DRKr: Use brass weights to adjust the tripping pressure to customer specifications on a test stand at the factory. After installation, the tripping pressure is no longer adjustable. If the brass weights fitted externally are positioned above a passageway for people, mount a suitable safety device under them to catch them if they fall. Depending on the degree of soiling of the medium, carry out a dry clean from time to time; it is recommended to clean the seal in particular at regular intervals. In...

Open the catalog to page 2

All Lucoma catalogs and technical brochures

  1. WSG-H3

    1 Pages

  2. RSK

    4 Pages

  3. DRK

    4 Pages

  4. RGKr

    1 Pages

  5. wsg

    8 Pages

  6. New range

    4 Pages

Archived catalogs

  1. AG

    2 Pages

  2. GRILAIR

    6 Pages

  3. DRKr

    1 Pages

  4. DKr

    1 Pages

  5. Fire dampers

    2 Pages

  6. REGLAIR

    6 Pages