Product catalog summary
Load Bearing Capacity: Ensure even load distribution to avoid exceeding the maximum permitted concentrated load during transport. Use hand-operated pallet trucks with nylon tandem rolls and travel only at walking pace. Lower loads only when stationary.
Opening and Closing the Access Floor for Installations:
Handling the Lifting Tool: Use a vacuum lifting pad for smooth surface panels and a claw lifting tool for textile-covered panels. Attach the lifting tool at the panel edge for easy lifting.
Removing the Floor Panels: Use the lifting tool to lift panels, hold with one hand, and place to the side.
Opening the Access Floor: Remove only necessary panels to maintain horizontal stability, especially at large installation heights. Avoid continuous open rows or islands and areas with free-standing pedestals.
Closing the Access Floor: Remove only necessary stringers and joists, replacing them immediately after installation. Pay attention to the covering and pile direction. Reinstall numbered section panels in their original positions. Clean pedestal heads of impurities and replace dampers.
Refer to sheets no. 10200 to 10220 for cleaning and maintenance instructions.
See more

Catalog excerpts

Operating instructions-1

Lenzlinger Sons Ltd. | Uster (Switzerland) | Shanghai (China) Phone +41 58 944 53 53 | www.lenzlinger.ch P00.270 | 022009 Subject to technical alterations Operating instructions | 10100 Load bearing capacity It should be ensured that there is an even load distribution so that the maximum permitted concentrated load is not exceeded when the goods are being transported. Use hand-operated pallet trucks with nylon tandem rolls for transport and only travel at walking pace. Lower the loads only when stationary! Opening and closing the access floor for installations Handling the lifting tool Remove the floor panels with a smooth surface only with a vacuum lifting pad and those with a textile covering only with a claw lifting tool (do not use screwdrivers etc.). Attach the lifting tool at the edge of the panel (see drawing)to lift the panels easily. correct incorrect Removing the floor panels Only use the lifting tool to lift the floor panels. Hold the floor panel which has been lifted with one hand and then place it to the side. Opening the access floor Important! Only remove as many panels as necessary so that horizontal stability is not adversely affected, in particular for large installation heights. There must not be any continuous, open rows or islands and no areas with free-standing pedestals (see drawing). correct incorrect Closing the access floor Only remove as many stringers and joists as necessary and replace them again immediately after installation. Pay attention to the covering and pile direction of the floor covering. Install the numbered section panels at the same place as previously (number on the underside of the panel and on the wall or floor). Clean the pedestal head of any impurities (cable sections, splinters etc.) and replace the damper. Please take note of our sheets no. 10200 to 10220 for cleaning and maintenance.

 Open the catalog to page 1

All Lenzlinger Access Floors catalogs and technical brochures

  1. Access floors

    20  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.