Overview: The document provides technical specifications and performance data for the eCOMFORT GAC series of air-cooled inverter scroll chillers, ranging from models 170D to 400D. These units are designed for ultra-efficient cooling in both comfort and industrial process applications.
Specifications:
  • Cooling Capacity: Ranges from 178.0 kW to 402.2 kW across different models.
  • Total Absorbed Power: Varies from 53.4 kW to 140.1 kW.
  • Energy Efficiency Ratio (EER): Values range from 2.9 to 3.3.
  • Eurovent Energy Class: Models are classified from A to C.
  • Seasonal Energy Efficiency Ratio (SEER): Approximately 4.8 to 5.0.
  • Sound Power Level: Standard units range from 87.5 dB(A) to 92.9 dB(A), with low noise units slightly quieter.
  • Dimensions: Length varies from 2704 mm to 5248 mm, with a consistent width and height of 2250 mm and 2402 mm respectively.
  • Operating Weight: Ranges from 1387 kg to 2694 kg.
Features:
  • Equipped with robust multi-stage scroll compressors.
  • Environmentally friendly and designed for high accuracy and quiet operation.
  • Standard units include standard AC fans and compressors.
Standards and Certifications:
  • Cooling mode data is Eurovent certified according to EN 14511 standards.
  • SEER is calculated following EN 14825 standards.
  • Complies with ecodesign regulation EU 2016/2281 for space cooling.
Applications: Suitable for both comfort and process cooling applications, providing high efficiency and reliability.
See more

Catalog excerpts

eCOMFORT-1

eCOMFORT EXTENDED RANGE 170 > 400 kW DELIVERS ULTRA-EFFICIENCY TO COMFORT AND INDUSTRIAL PROCESS COOLING APPLICATIONS ACOUSTIC DATA COOLING ONLY UNIT (1) EUROVENT certified data, in accordance with Heating mode : (3) SEER in accordance with standard EN 14825. standard EN 14511 : Condenser \ratei- temperature = 40/45°C (4) Following ecodesign regulation EU 2016/2281 Cooling mode : ^ ° Outdoor air temperature = 7C on space cooling, normalized leaving water Evaporator water temperature = 12/7C (2) ESEER following Eurovent calculation method, in temperature at 7°C, in accordance with standard accordance with standard EN 14511 EN 14825.

 Open the catalog to page 1

All Lennox catalogs and technical brochures

  1. e-MovAir

    5  Pages

  2. Catalogue

    174  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.