Energy Efficiency and Comfort:- eDrive System: Variable speed, direct transmission ventilation system that saves energy.
- Free Cooling/Heating: Utilizes favorable outdoor temperatures to save energy.
- Fresh Air Management: Ensures accurate fresh air percentage to control CO2 levels and comfort.
- Energy Recovery: Options for recovering energy from exhaust air and food refrigeration systems.
Auxiliary Heating and Cooling Systems: The document outlines various auxiliary heating and cooling systems, including electric heaters with modulating triac control, electric pre-heaters for low outdoor temperatures, and hot water coils with frost protection. It also describes high-efficiency gas burners with multiple capacity stages and modulating gas burners for optimized efficiency.
Architectural Integration: Different types of roofcurbs are available for architectural integration, including non-adjustable, adjustable, and multidirectional options. These allow for various airflow configurations and adaptations for replacing old units.
Indoor Air Quality: Features for managing indoor air quality include fresh air management systems, CO2 sensors for adjusting airflow, gravity exhaust dampers, and refillable filters. The document also highlights the importance of double skin panels for preventing bacteria growth and analog dirty filter sensors for preventive maintenance.
Safety Features: Safety features include M0 fireproof insulation, smoke detectors, and fire-stats for fire protection. These components ensure the unit stops operating and adjusts air dampers in case of smoke detection.
CLIMATIC Control System: The CLIMATIC control system is a microprocessor-based system designed for energy efficiency and reliable operation. It includes features like heating priority steps, automatic seasonal changes, noise reduction, and dynamic defrost. Advanced options include enthalpy and humidity control, service and comfort displays, and dry control boards for external control.
Communication Interfaces and Supervision: The document details various communication interfaces such as ModBus, LonWorks®, and BACnet® for connecting to building management systems. ADALINK II is highlighted as a supervision tool for controlling multiple units and optimizing maintenance.
Main Applications: The systems are suitable for cinemas, theaters, convention centers, and large commercial buildings. They offer energy-efficient solutions with thermodynamic heat recovery and are designed for easy installation and accurate ventilation balancing.
General Description of Rooftop FX Solution: The Rooftop FX solution is a cost-effective package for high-efficiency air conditioning using fresh air. It features thermodynamic heat recovery, flexible air balancing, and pressure control. The unit can be fully ducted and is available for 100% fresh air applications.
Main Components and Features: Key components include R410A compressors, fireproof insulation, and corrosion-resistant casing. The CLIMATIC controller offers advanced control features and extended communication capabilities.
Dimensions and Weights: The document provides detailed dimensions and weights for various unit models, along with performance data for cooling and heating modes.
Air Cooled Condensers and Dry Coolers: The document describes air-cooled condensers and dry coolers, highlighting their casing, ventilation, coil characteristics, and performance. It emphasizes their suitability for air conditioning and cooling fluids compatible with copper.
Overview: The document provides a detailed technical description of various cooling and heating systems, focusing on dry coolers, air-cooled condensers, and chillers. It highlights the features, specifications, and applications of these systems, emphasizing their efficiency, installation flexibility, and maintenance requirements.
Key Features and Benefits:- No water consumption and reduced maintenance costs due to direct-driven fans.
- Flexible use in winter, simple installation with steel pipes, and easy temperature control.
- Optimized solutions for noise level, energy consumption, and size.
Dry Coolers:- Capacity range from 20 to 1200 kW.
- Multiple configurations available for power and silence levels.
- Equipped with high-performance finned coils and various motor fan units.
NEOSTAR Air Cooled Condensers:- Designed for refrigeration and air conditioning applications.
- Equipped with high-tech heat exchangers and special coil coatings for corrosion resistance.
- Available in different motor fan configurations for optimized performance.
NEOSTAR WAVE Range:- Optimized for minimal footprint with modular construction.
- Features micro-channel coils for reduced refrigerant charge and easy installation.
- Equipped with high reliability external rotor fans and optional electronic switching fan motors.
ECOLEAN Chillers and Heat Pumps:- Suitable for small offices, shops, hotels, and small commercial buildings.
- Features R407C scroll compressors and electronic controllers.
- Available in cooling only or heat pump versions with compact design.
General Specifications:- Units are made of galvanized steel with corrosion-resistant coatings.
- Equipped with advanced control systems for efficient operation.
- Various options available for customization, including special coatings and fan configurations.
Overview: The document is a technical catalogue for the ECOLEAN range of
air-cooled chillers and heat pumps, designed for various applications such as offices, hotels, hospitals, and light commercial buildings. It emphasizes high efficiency, low noise operation, and advanced control features.
Specifications: The ECOLEAN units operate on R410A refrigerant and are available in standard and high static pressure versions. They feature brazed plate evaporators, multiple capacity steps, and a range of cooling and heating capacities. Electrical requirements are 400 V/3 Ph/50 Hz.
Operating Limits: The units have specific operating limits for cooling and heating modes, including maximum and minimum outside air temperatures and water temperatures.
Hydraulic Module: The integrated hydraulic module includes components like a single or twin pump, water filter, expansion vessel, and pressure relief valves. It is available in two versions: Hydraulic (HY) and Hydronic (HN), the latter including a buffer tank.
Acoustic Data: The units are designed for low noise operation, with options for further noise reduction through acoustic jackets and cabinets.
Control Features: The CLIMATIC microprocessor-based control system offers advanced features such as scheduling, noise management, dynamic defrost, and master/slave control for multiple units.
Options and Accessories: Various options are available, including epoxy-coated coils, soft starters, antifreeze protection, communication interfaces, and advanced display units.
Main Applications: The ECOLEAN range is suitable for a wide range of applications, providing efficient and quiet operation with advanced control capabilities.
Overview: The NEOSYS General Product Catalogue from June 2013 provides detailed information on the NEOSYS range of liquid chillers and heat pumps, designed for integration into urban or residential environments. The document outlines the main applications, features, specifications, and options available for these units.
Main Applications: The NEOSYS units are suitable for offices, hotels, hospitals, industries, administration, and medium to large commercial buildings.
Key Features: The units offer high efficiency with R410A refrigerant, low noise operation, advanced CLIMATIC control, and integral hydraulic module equipment. Energy-saving options include heat recovery, free-cooling, and eDrive technology. The units come with a 3-year warranty on specific components.
General Description: NEOSYS units are designed to meet architectural constraints and environmental noise regulations. They feature an Active Acoustic Attenuation System™ that adjusts airflow based on building load and sound level requirements. The units can be equipped with a compact hydraulic module and offer options for electronic water flow control.
Energy Saving Options: The NEOSYS range includes eDrive variable speed pump technology, partial heat recovery for hot water production, and free cooling to maximize the use of outside air.
Specifications: The NEOSYS NAC (cooling only) and NAH (heat pump) versions offer cooling capacities from 200 to 1000 kW and heating capacities from 200 to 500 kW. The units are built with galvanized steel casings, low noise scroll compressors, and advanced control systems.
Advanced CLIMATIC Control: The control system provides PI control of water temperature, automatic heating/cooling change-over, and active acoustic attenuation. It supports remote control and communication interfaces like ModBUS®, LonWorks®, or BacNET®.
Options and Accessories: Available options include hydraulic modules, partial heat recovery, winter operation capabilities, anti-corrosion treatments, and various communication interfaces. The units can also be equipped with remote displays and supervision systems.
Dimensions and Weights: The document provides detailed dimensions and weights for different unit sizes, ensuring proper planning for installation and operation.
HYDROLEAN Range: The catalogue also covers the HYDROLEAN range, suitable for residential and light commercial buildings. These units feature R407C scroll compressors, advanced control systems, and are designed for indoor installation with minimal noise and space requirements.
Overview: This document provides technical specifications and details for heat exchangers, focusing on water-cooled chillers and heat pumps. It includes information on evaporators, condensers, acoustic data, electrical data, and various operational parameters.
Specifications:- Evaporator and Condenser: Both are made of AISI 304 stainless steel plate brazed with copper. They have specific water flow rates, volumes, pressure drops, and operating pressures.
- Acoustic Data: Global sound power levels are provided, with options for acoustic jackets to reduce noise.
- Electrical Data: The units operate at 400 V/3 Ph/50 Hz. They include multiple circuits and compressors with specific capacity steps and refrigerant charges.
- Hydraulic Connections: Use Victaulic type connections with specified water inlet/outlet dimensions.
Performance Metrics:- Cooling Mode: Cooling capacities are provided in kW, along with Energy Efficiency Ratios (EER) and European Seasonal Energy Efficiency Ratios (ESEER).
- Heating Mode: Heating capacities and Coefficient of Performance (COP) are detailed.
Operating Limits:- Minimum and maximum temperatures for evaporator and condenser operations are specified, along with water temperature differences.
Options and Accessories:- Includes electrical equipment for control of fans and pumps, pressure regulated water valves, water filters, hot gas by-pass, and various communication interfaces.
- Additional options include low noise operation, anti-vibration mounts, and low water temperature kits.
Main Applications:- Suitable for offices, hotels, hospitals, industrial settings, and medium to large commercial buildings.
General Description:- The MWC unit is designed for high efficiency with R410A refrigerant, compact dimensions, and low noise operation. It is available in water-cooled and split versions for various applications.
Main Components:- Features include multiple scroll compressors, stainless steel brazed plate heat exchangers, and advanced CLIMATIC control systems.
Advanced Control:- CLIMATIC microprocessor-based control offers functions like PI control of water temperature, operation without a buffer tank, and communication interfaces for system integration.
Dimensions and Weights:- Detailed dimensions and weights for different sizes of units are provided, highlighting their compact design for easy installation.
General Overview: This document is a General Product Catalogue from June 2013, detailing various airside products and fan coil units. It includes specifications, operating limits, dimensions, weights, and main applications for different models.
Operating Limits: The document specifies the minimum and maximum evaporator and condenser outlet water temperatures, as well as the minimum and maximum differences in water inlet/outlet temperatures. It also outlines the maximum discharge temperatures for full capacity operation.
Dimensions and Weights: Dimensions are provided in millimeters, and weights are given in kilograms for both operating and non-operating conditions. The document includes footprint measurements in square meters.
Airside Products: The catalogue lists various airside products such as ALLEGRA, COMFAIR HD, ARIA, and others, each with specific features and applications.
Fan Coil Units: Fan coil units are detailed with power ranges from 0.6 to 6.7 kW and airflow rates from 105 to 1500 m3/h. High wall fan coil units and high-pressure modular fan coil units are also described.
Main Applications: The products are suitable for commercial buildings, offices, and hotels. They offer innovative designs, noise performance, and energy-saving features.
General Description: The ALLEGRA range includes nine sizes with wall and ceiling-mounted units, exposed or concealed, with centrifugal fans. The units are versatile and meet various air-conditioning requirements.
Main Components: Components include galvanized steel cabinets, polypropylene filters, aluminum or plastic fan blades, AC and EC motors, copper tube coils, and plastic condensate trays. Control options include remote and wall-mounted controls.
Performance Data: Performance data for different models are provided, including airflow rates, cooling capacities, heating capacities, and sound pressure levels.
Accessories: Available accessories include valves, electric heaters, condensate trays, air inlet grids, and electrostatic filters.
Certifications: The document advises checking the ongoing validity of certificates at eurovent-certification.com and certiflash.com.
General Overview: The document provides detailed specifications and descriptions of various fan coil units, including the COMFAIR HH/HV, ARIA, and ARIA EC models. These units are designed for light commercial buildings, offices, and shops, offering high performance, easy installation, and energy efficiency.
Specifications:- COMFAIR HH/HV: Available in 7 capacity sizes with vertical (HV) or horizontal (HH) configurations. It supports 2 and 4 pipe systems, with options for additional electric heaters. The units are constructed with galvanized sheet metal and include centrifugal fans and copper-aluminum heat exchangers.
- ARIA: A horizontal ducted fan coil unit available in 4 sizes, suitable for medium and high static pressure installations. It features a mono-block design with discharge and return spigots, and fresh air connections.
- ARIA EC: Similar to the ARIA model but equipped with an EC fan for lower energy consumption and noise levels. It is available in 4 sizes and supports both 2 and 4 pipe systems.
Performance and Features:- Units offer a range of cooling and heating capacities, with specific water flow rates and pressure drops detailed for each model.
- Sound power levels are measured according to ISO 23741, ensuring compliance with industry standards.
- Various configurations and accessories are available, including thermal and acoustic insulation, electric heaters, regulation valves, and remote controls.
Applications and Benefits:- These fan coil units are ideal for light commercial applications, providing flexibility in installation and significant energy and maintenance savings.
- The ARIA and ARIA EC models are particularly noted for their low energy consumption and ease of maintenance.
Construction and Design:- Units are constructed with galvanized steel and feature internal insulation for enhanced performance and durability.
- Designs are optimized for integration into standard ceiling modules, ensuring a pleasant aesthetic and efficient air distribution.
Specifications: The document outlines the specifications for thermal insulation and anti-condensate lining, air diffusers, fan-motor assembly, heat exchangers, and condensate pumps. The air diffusers are available in ABS white and metallic white colors. The fan-motor assembly includes a single inlet radial fan and a 6-speed electric motor with a single-phase 230V/50 Hz supply. Heat exchangers are made of copper tubes and bonded aluminum fins, with different configurations for 2-pipe and 4-pipe systems.
Procedures: The fan-motor assembly is supplied wired in 3 speeds but can be modified on-site among the 6 available speeds. The EC motor allows continuous airflow and heating/cooling variation thanks to an inverter card. The condensate pump with a floating switch is supplied as standard, with a maximum head of 650 mm.
Norms and Standards: The main drain pan is made of high-density ABS polystyrene foam with a fire retardant B2 rating. The auxiliary drain pan is connected to the main drain pan to collect condensate from the heat exchanger and control valves.
Recommendations: Available accessories include different RAL colors for ABS diffusers, control valves, infrared remote control, standalone controls, and fresh air kits. The document also suggests using EC fans for low energy consumption, which can lead to up to 80% annual energy savings.
Data Summary: The document includes detailed tables with data on airflow, cooling and heating capacities, water flow, pressure drops, fan power, and acoustic data for various models and configurations. The data is presented for both 2-pipe and 4-pipe versions, with specific values for different speeds and sizes.
Applications: The systems are suitable for light commercial buildings, offices, hotels, schools, and hospitals, offering optimal user comfort, low noise levels, and excellent architectural integration.
General Overview: The document is a technical catalogue from June 2013, detailing the specifications and configurations of AXIL unit heaters, EQUITHERM destratifier fans, and MINIAIR compact
air handling units. These products are designed for industrial and large commercial buildings, offering high performance in heating, cooling, and air handling.
Product Specifications:- AXIL Unit Heaters: Available in hot water, chilled water, electrical, and steam heating versions. Operating limits include 120°C and 16 bars for hot water, and 210°C and 20 bars for steam.
- EQUITHERM Fans: Destratifier fans without heating, suitable for large spaces.
- MINIAIR Units: Compact air handling units available in various configurations, including 2 and 4 pipe systems, with options for electric heaters and droplet eliminators.
Main Components:- Galvanized prepainted steel casing, hermetically sealed motors, and heat exchangers with copper or steel tubes and aluminum fins.
- MINIAIR units feature pre-coated steel frames, sandwich panels with mineral wool insulation, and multi-speed fans.
Performance and Applications:- AXIL units offer heating capacities from 12 to 105 kW, suitable for any industrial building.
- MINIAIR units provide airflow rates from 500 to 7400 m3/h, ideal for commercial buildings, offices, and hotels.
Control and Accessories:- Various control options including thermostats, digital clocks, and remote control boards.
- Accessories include multidirectional diffusers, air curtains, mixing boxes, and rain hoods.
Technical Data:- Detailed tables provide information on airflow rates, heating capacities, fan speeds, and sound pressure levels for each product model.
- Dimensions and weights are specified for different configurations and installation types.
Conclusion: The catalogue provides comprehensive technical details and configurations for industrial heating and cooling solutions, emphasizing high performance, durability, and ease of installation.
Overview: The document provides detailed specifications and descriptions of the MINIAIR+ series, which are air-to-air heat recovery units designed for both commercial and residential buildings. These units are engineered for energy saving and air renewal, featuring easy installation and maintenance.
Main Components:- F7 and F8 soft bag filters
- Air filter pressure switch
- Antifreeze thermostat
- 230V damper motor
- 3-way valves
- Frequency converter fan motors
Performance Specifications:- Airflow rates range from 100 to 6000 m3/h.
- Units are compliant with the 2009/125/EC ErP directive.
- Multiple fan speeds and poles are available, with a minimum protection degree of IP20 to IP55.
- Electrical power supply options include 230 V/1 Ph/50 Hz and 430 V/3 Ph/50 Hz.
Operational Modes:- Winter operation includes recovery efficiency and heating capacity specifications.
- Summer operation details recovery efficiency and cooling capacity.
- Units feature automatic modes for heating, cooling, and free-cooling, with antifreeze and electric heater options.
Installation Configurations:- Horizontal and vertical configurations are possible, with specific types (A, B, C, D) for different air flow arrangements.
Dimensions and Weights:- Detailed dimensions are provided for various models, with weights ranging from 39 to 273 kg.
Available Versions and Accessories:- Multiple versions with different filter configurations (G4, F6, F7, F8) are available.
- Accessories include electric heaters, water heating/cooling coils, adiabatic cooling sections, and various control options.
Control Systems:- Remote 3-point control and modulating control options are available for fan speed and temperature regulation.
Overview: The document provides a detailed description of various Lennox control systems and air handling units, focusing on their specifications, functionalities, and applications. It includes information on electronic kits, hydronic kits, remote controls, and modular air handling units, as well as specific products like the ADNOVA units for telecom shelters.
Specifications and Features:- Electronic Kit (LXMAPRQU): Includes a temperature analogical regulator with three NTC sensors and an electronic board. It supports automatic modes for heating, cooling, and free-cooling, antifreeze, electric heater control, and more.
- Hydronic Kit (LXMAPV33): Features a 3-way valve with an electric actuator, powered by 230V.
- Remote Controls: Various thermostats and controllers are available, including mechanical and electronic room thermostats, with features like manual or automatic fan speed control, heating/cooling changeover, and energy-saving modes.
- Communicating Controllers: These controllers operate on LONWORKS or BACNET protocols, allowing integration into global HVAC management solutions and enhancing energy efficiency.
Modular Air Handling Units (CLEANAIR LX):- Available in 44 sizes, covering airflow ranges from 1,000 to 100,000 m3/h.
- Constructed with an aluminum frame and insulated panels, ensuring thermal insulation and resistance.
- Options include various coil types, fan sections, safety devices, and built-in control systems.
ADNOVA Units:- Designed for telecom shelters, these units manage temperature efficiently in environments with high thermal loads.
- Available in different configurations (THN, THX, THS) with features like emergency free-cooling, dual power supply, and electronic expansion valves.
Applications: The products are suitable for commercial, residential, and light industrial buildings, as well as telecom shelters, offering energy efficiency, reliability, and high quality.
General Description: The INNOV@ series of Close Control Air Conditioning units are designed for high energy efficiency, compact size, and low noise levels, suitable for environments like computer rooms and datacenters. They offer a reduction in energy consumption by up to 45% compared to traditional technologies. The units are designed to operate continuously throughout the year.
Main Applications:- Computer rooms
- Datacenters
Key Features:- Energy efficiency
- Reliability
- High quality
- Full frontal access for maintenance
Main Components: All components are accessible from the front, including the electrical panel, compressor, fans, humidifier, electrical heaters, expansion valve, and liquid flow filter. The units use internationally recognized quality components and advanced technology like electronic expansion valves and EC motors for energy savings.
Operating Modes:- Air cooled with remote condenser
- Water cooled with remote dry-cooler
- Chilled water
- Indirect free-cooling
Control System: The microprocessor control, available in Basic or Advanced Graphics versions, manages all functions and allows networking of up to 8 units. It supports various communication protocols and can be customized for specific requirements.
Available Accessories:- Dual fluid
- Potential free alarms contacts
- Water detection kit
- Flash memory
- Microprocessor
- Electronic condenser fans speed control
- Interconnectivity (ModBus, TCP/IP, Bacnet)
- Touch screen graphic display
INNOV@ ENERGY INVERTER: This series introduces modulating cooling capacity for computer rooms and datacenters, offering flexibility and energy efficiency with EC motors and advanced control systems.
R@CKCOOLAIR: Designed for cooling server racks in data centers, offering spot cooling, high efficiency, and full accessibility. Features include high-pressure radial fans, hydrophilic finned coils, and programmable control with LCD display.
Options and Accessories:- Dehumidification with humidity sensor
- Clogged filter sensors
- Water leakage, fire, and smoke sensors
- Additional temperature and humidity sensors
- Condensate water pump
- Water-flow meter with current cooling capacity display
- Integrated IT racks and hotspot cooling solutions
- Automatic airflow control with display visualization
- Serial cards for various protocols
- PCOWEB Hardware for Ethernet protocols
- DATAWEB Software for web connectivity
- Touch-Screen color graphic display
Main Applications:- Medium and small-sized data centers
- Server rooms
Key Features:- EC motor compressor technology
- Flexibility and high-quality standards
Product Specifications:- Chilled water unit with high-performance coil and modulating water valve
- Precise temperature control with PID regulation
- Maximized EER of the chiller and extended free-cooling operation range
- Motor-evaporating/condensing units with variable speed compressors
- Reduced power consumption at partial load
- Simple and economical installation
Ventilation and Airflow Configuration:- Positioning next to the server minimizes ventilation consumption
- Plug fans with backward curved blades for maximum airflow stability
- Optional automatic airflow control for constant airflow
- No ducting systems or raised floors necessary
- Several configurations for modern data centers
Control Systems:- ADALINK II for HVAC installation monitoring
- LennoxVision for supervision and telemaintenance
- Remote monitoring system available for all product ranges
Acoustic Data:- Noise described in terms of frequency bands
- Weighting filters for auditory disturbance
- Free air or noise diffusion with obstacles
- Diffusion of noise in enclosed spaces
Absorption Coefficient and Reverberation Time: The absorption coefficient (α) is a dimensionless number ranging from 0 to 1, defined by frequency. Reverberation time is the duration it takes for sound to decrease by 60 dB after noise emission stops. Examples include concert halls (1-2 seconds) and churches (2-7 seconds). The reverberation time is related to room characteristics.
Acoustic Data and Noise Levels: The document provides formulas for calculating sound levels in rooms, considering direct and reflected fields. The overall noise level from multiple sources is calculated using logarithmic formulas.
Air Filtration Standards: Air filter efficiency is evaluated using various methods, including gravimetric and opacimetric tests. Standards like NF EN779 and EN 1822 are used for classification. Filters are categorized into efficiency classes (G1-G4, M5-M6, F7-F9) based on performance with synthetic and atmospheric dust.
Energy Efficiency and Filter Classification: Since January 2013, EUROVENT members label filters with energy ratings (A to G). The EN 779:2012 standard addresses efficiency variations over a filter's service life, introducing 'minimum efficiency' for certain classes. EN 1822-1:2009 introduces particle counting methods for filter efficiency evaluation.
Filter Classifications: Filters are classified into EPA (E10-E12), HEPA (H13-H14), and ULPA (U15-U17) based on efficiency and penetration rates. Tests are conducted at specified airflows, with different methods for HEPA and ULPA filters.
General Notes: The document emphasizes the importance of proper installation and maintenance by qualified personnel to prevent damage or injury. Specifications are subject to change without notice.