Series SF Fire dampers
35Pages

{{requestButtons}}

Catalog excerpts

Series SF Fire dampers - 2

Rectangular and circular fire dampers CONTENTS Description 2

Open the catalog to page 2
Series SF Fire dampers - 3

Rectangular and circular fire dampers Description SCFR-PD with motor KOOLAIR rectangular fire dampers, models SCFR-PD, SCFR-GD, SFR3K1GT and circular fire dampers, models SCFC-PD and SCFC-GD, are approved in accordance with the Technical Building Code according to test standard UNE EN 1366-2 and classified according to EN 13501-3. Fire dampers close automatically to prevent fire and smoke from spreading through ventilation ductwork to adjacent fire compartments. The frame consists of a single sheet of sheet metal with an internal recess reinforced by a slot sheet metal support that prevents...

Open the catalog to page 3
Series SF Fire dampers - 4

Circular fire dampers CE Marking Koolair fire dampers carry the CE marking in compliance with RPC-305/2011/EU, according to EN15650:2010. The SCFR-PD, SCFR-GD, SCFC-PD and SCFC-GD models are certified under NF (NF264 Certification Standard, NF S 61-937-5 fire dampers). The dampers are approved in accordance with European Test Standard UNE-EN 1366-2 and European classification standard UNE-EN 13501-3, where: (E) Integrity (I) Isolation (ho) Installed in Horizontal slab. Mounted in horizontal enclosure. (ve) Installed in wall or stud wall. Mounted in vertical enclosure. (i ↔ o) Symmetric...

Open the catalog to page 4
Series SF Fire dampers - 5

Declared performance The performance specifications of our range of fire dampers (rectangular and circular) are shown in the table below. Rectangular fire dampers Installation location Brick Wall Floor slab Stud wall Construction details Installation location Brick Wall Construction details Floor slab Construction details Installation location

Open the catalog to page 5
Series SF Fire dampers - 6

Declared performance Circular fire dampers Installation location Brick Wall Floor slab Stud wall Construction details Installation location Brick Wall Construction details Floor slab L: Length H: Height Ø: Diameter d: Wall thickness p: Density Details of supporting structure, tested on Stud wall (plasterboard): • Fire resistance rating: EI 90. • 2 sheets of laminated fireproof plasterboard ref. KNAUF cortafuego DF thickness 12.5 mm. • Rock wool panel ref. ProRox SL960 (ROCKWOOL). • 2 sheets of laminated fireproof plasterboard ref. KNAUF cortafuego DF thickness 12.5 mm. • 48 mm U-shap

Open the catalog to page 6
Series SF Fire dampers - 7

Applications FIXED WALL EI-120 (ve i^o) S (RECTANGULAR) The length and height of all models of rectangular fire dampers increases in 50mm increments.

Open the catalog to page 7
Series SF Fire dampers - 9

SCFR-PD Model and dimensions SCFR-PD fire dampers are available in standard sizes (duct size) with a length (L dimension) from 200 to 800 mm increasing in 50mm increments and a height (dimension H) from 100 to 600 mm increasing in 50mm increments. 1- Galvanised steel frame 5- Fixing lug for installing in slab floor (optional)

Open the catalog to page 9
Series SF Fire dampers - 10

SCFR-GD fire dampers are available in standard sizes (duct size) with a length (L dimension) from 850 to 1500 mm increasing in 50mm increments and a height (dimension H) from 200 to 800 mm increasing in 50mm increments. Drive shaft 1- Galvanised steel frame 2- Damper blade

Open the catalog to page 10
Series SF Fire dampers - 11

Series SF SFR3K1GT Model and dimensions SFR3K1GT fire dampers are available in standard sizes (duct size) with a length (L dimension) from 200 to 1500 mm increasing in 50mm increments and a height (dimension H) from 200 to 800 mm increasing in 50mm increments. Drive axis

Open the catalog to page 11
Series SF Fire dampers - 12

The standard dimensions (duct dimensions) of SCFC-PD fire dampers are: 100, 125, 160, 200, 250, 315 and 355 mm. Drive shaft

Open the catalog to page 12
Series SF Fire dampers - 13

Series SF SCFC-GD Model and dimensions The standard dimensions (duct dimensions) of SCFC-GD fire dampers are: 400, 450, 500, 560, 630, 650, 700, 710, 750 and 800 mm.

Open the catalog to page 13
Series SF Fire dampers - 14

Start and end of run position contacts Electrical devices that indicate the position of the damper, i.e. whether it is open or closed, by connected control systems, detection modules, etc. Protection rating > IP42 PC = Start of run FC = End of run Servomotor with reset spring and thermoelectric fusible link (DAS) Allows the damper to be both reset (opened) and activated (closed) remotely. Fitted with a thermoelectric fusible link set at 72 °C (EN 10294) and its own signalling contacts (start and end of run). The servomotors are supplied for 24 V operation C € <© 230 V operation CjE...

Open the catalog to page 14
Series SF Fire dampers - 15

Series SF Installation Fire dampers are part of a building’s fire safety system and therefore special care must be taken with their installation. To install the dampers a perforation in the wall that is 100 mm greater than the nominal dimensions of the damper is required. No additional space is required for the mechanism box as it sits outside the wall or partition. As such, when the fire damper blade is in the closed position, it will be exactly vertical in the firewall, as if it were an extension of this wall, as required by UNE-EN 1366-2. Likewise, the dimensions indicated on the...

Open the catalog to page 15
Series SF Fire dampers - 16

Installation Mounting in stud wall SCFR-PD Wall studs must be offset L no Wall studs must be offset 48 mm channels and uprights in 400 mm spacing 48 mm channels and uprights in 400 mm spacing Screw PL 3.5x25 Screw PL 3.5x35 Rock wool 40 mm of 100 Kg/m3 NOTE: The distance between screws should not exceed 150 mm NOTE: The distance between screws should not exceed 150 mm 00 al + 3 Test conditions: - 15-8577-939 (SCFC-PD): KNAUF “cortafuego DF” fireboard. - 15-8577-1076 (SCFR-PD): KNAUF “cortafuego DF” fireboard. To guarantee the correct fire damper operation, it is essential to read and follow...

Open the catalog to page 16
Series SF Fire dampers - 17

Installation Precautions during assembly The slot section of the damper frame must be sealed in when fitted both horizontally or vertically. There is an option to use fixing lugs fitted on the damper frame for installation in slab. Arrangement of damper and building elements according to DB-SI (CTE). The following conditions apply to horizontal and vertical dampers: - There must be a minimum separation of 75 mm between fire dampers and building elements. - There must be a minimum separation of 200 mm between fire dampers.

Open the catalog to page 17
Series SF Fire dampers - 18

CORRECT INSTALLATION Airflow direction is not critical (ve i↔o) o (ho i↔o) Motor-driven Motor-driven device at 0º INCORRECT INSTALLATION Manual Manual device at top Manual device at bottom Motor-driven Motor-driven device at top

Open the catalog to page 18