SCDC Smoke dampers
Open the catalog to page 1Series SCDC SCDC Smoke Evacuation Damper CONTENTS Description 2
Open the catalog to page 2Series SCDC SCDC Smoke Evacuation Damper Description KOOLAIR’s SCDC rectangular smoke evacuation damper is composed of a single body of heat-resistant material, with steel flanges on either side (optional) to facilitate mounting in rectangular ducts, and a single heat resistant closing blade. Tunnel type damper for in-line installation in horizontal ducts for use with both supply and extract, certified according to EN 136610, classified according to EN 13501-4; EI 120 (ved i o) S 1500 AA multi. The SCDC smoke damper has the 0370 - CPR - 2600 certificate of constancy of performance according to...
Open the catalog to page 3Series SCDC SCDC Smoke Evacuation Damper Connections Operating mechanism electrical connections FCU: safety position (end of run) one-pole contact. DCU: waiting position (start of run) one-pole contact. FCB: safety position (end of run) two-pole contact. DCB: waiting position (start of run) two-pole contact. - Manual reset, activated by electric coil (CE and NF marking). 24 V DC. electric shunt release coil. 48V DC electric shunt release coil 24V AC electric shunt release coil 48V AC electric shunt release coil COIL (Supply type) Option to incorporate two start of run limit switches (DCU, DCB)...
Open the catalog to page 4Series SCDC SCDC Smoke Evacuation Damper Connections - Automatic activation and reset by servomotor (CE Marking): SCDC smoke extract dampers are activated and reset by means of a servomotor with a supply voltage of 24 V AC/DC (model BLE24) or 230 V AC (model BLE230). These motors include start and end of run limit switches to monitor the opening/closing status of the damper. • Activated by shunt release coil and reset with electric servomotor (CE and NF marking): 24 V DC electric shunt release coil. 48V DC electric shunt release coil 24V AC electric shunt release coil 48V AC electric shunt release...
Open the catalog to page 5Series SCDC SCDC SMOKE DAMPER FREE AREA TABLE dm2
Open the catalog to page 6Series SCDC SCDC Smoke Evacuation Damper Selection Chart SCDC Vp-ΔPest 100 90 80 70 Key Vp= damper air velocity in m/s. ΔPest= static pressure loss across the damper in Pa. Selection example: To calculate the static pressure loss across a damper for a given flow rate Q(m3/h) the air velocity Vp(m/s) is calculated in relation to the free area Al (dm2) of the damper as set out in the above table “Free area table in dm2” using the formula Vp=(Q/Al)/36. By entering this velocity in the previous table, the static pressure loss is obtained ΔPest. Example: for a flow rate of 2500 m3/h in a 500x300 SCDC...
Open the catalog to page 7Series SCDC SCDC Smoke Evacuation Damper Installation The approval and the certification requirements for the installation of the damper are shown below. DAMPER BODY DUCT SCREW SPAX ABC Ø5.5X50 SCDC damper application in installations which employ ductwork different from that which has been submitted for certification testing: SCDC smoke control dampers, for use in multi-compartment systems (multi), are applicable in ducts that are tested in accordance with EN1366-8 as appropriate for each particular case or manufactured from materials with the same density or greater thickness than those used...
Open the catalog to page 8Series SCDC SCDC Smoke Evacuation Damper Coding Damper model (see table p. 5 Declared Performance) Activation. Components f + MOTOR-BLE24 + MOTOR-BLE230 + SHUNT RELEASE 24 V DC + ER/SR LS + SHUNT RELEASE 48 V DC + ER/SR LS + SHUNT RELEASE 24 V AC + FC/PC + SHUNT RELEASE 48 V AC + FC/PC + SHUNT RELEASE 24 V DC + FC/PC + MOTOR RESET-BL24/48 + SHUNT RELEASE 48 V DC + FC/PC + MOTOR RESET-BL24/48 + SHUNT RELEASE 24 V AC + FC/PC + MOTOR RESET-BL24/48 + SHUNT RELEASE 48 V AC + FC/PC + MOTOR RESET-BL24/48 Accessories r - C1+C2 (rectangular collars on both sides of damper) - C1 (rectangular collar on...
Open the catalog to page 9Series SCDC THIS CATALOG IS INTELLECTUAL PROPERTY. The partial or total reproduction of its contents is forbidden without the express and authoritative authorisation of KOOLAIR, S.A. CEN-SCDC-1117-00
Open the catalog to page 10KOOLAIR, S.A. Calle Urano, 26 Poligono industrial nº 2 – La Fuensanta 28936 Móstoles - Madrid - (España) Tel: +34 91 645 00 33 Fax: +34 91 645 69 62 e-mail: [email protected]
Open the catalog to page 1123 Pages
21 Pages
2 Pages
2 Pages
1 Page
1 Page
2 Pages
18 Pages
6 Pages
35 Pages
2 Pages
15 Pages
14 Pages
2 Pages
145 Pages
15 Pages
12 Pages
7 Pages
6 Pages
9 Pages
20 Pages
22 Pages
20 Pages
19 Pages
19 Pages
19 Pages
1 Page
1 Page
1 Page
1 Page
1 Page
2 Pages
8 Pages
31 Pages
12 Pages
19 Pages
10 Pages
18 Pages
25 Pages
26 Pages
31 Pages
19 Pages