1. Catalogs
  2. KOOLAIR S.A
  3. Series AR-200 Non-return or positive pressure dampers
video corpo

Series AR-200 Non-return or positive pressure dampers

Series AR-200 Non-return or positive pressure dampers

Series AR-200 Non-return or positive pressure dampers

Product catalog summary
Description and Specifications
The AR-200 is a non-return or positive pressure damper designed with flat fins made from 1.5-mm thick galvanized plate and a U-frame of 2-mm galvanized plate. It features zinc-coated steel shafts that rotate in nylon bushings, and includes zinc-coated steel counterweights. The damper is housed in galvanized steel for wall recessing and counterweight absorption. It is used to allow air flow in one direction, preventing reverse flow, and can maintain positive pressure in ducts or rooms. The standard finish is galvanized, with optional RAL paint available.

Dimensions and Operation
The damper's sensitivity and opening pressure can be adjusted by setting the levers upward or downward. Upward settings allow the damper to open with minimal pressure, suitable for full opening in supply ducts. Downward settings require more pressure, useful for controlling air volume by increasing pressure drop. Counterweights can be adjusted to vary resistance, using a threaded rod and interchangeable weights. Regular maintenance includes inspecting and tightening Allen set screws.

Installation
The AR-200 can be installed vertically or horizontally, with the shaft parallel to the floor. It can be coupled to ducts for air supply or suction, with fins aligned accordingly. Depending on size, the damper may have one or two counterweights, adjustable within 360° of shaft rotation to control air pressure or volume.

Product Codes and Options
Product codes specify configurations such as additional bird or insect screens. An example code is AR-200-AL-X-0600-0300, indicating a non-return damper with untreated bird netting of 600 x 300 dimensions.

Performance Chart
The document includes a chart correlating total pressure (Pa) with front velocity (m/s), calculated from the cross-section dimensions.

Contact Information
KOOLAIR, S.A., located in Móstoles, Madrid, Spain, provides contact details for further inquiries.
See more

Catalog excerpts

Series AR-200 Non-return or positive pressure dampers-1

AR-200 Non-return or positive pressure dampers

 Open the catalog to page 1
Series AR-200 Non-return or positive pressure dampers-2

Chart and Product Codes 4

 Open the catalog to page 2
Series AR-200 Non-return or positive pressure dampers-3

AR-200 non-return or positive pressure damper Dimensions Description Non-return or positive pressure damper with flat fins of 1.5-mm thick galvanized plate and U-frame of 2-mm galvanized plate with zinc-coated steel shafts that turn in nylon bushings. The unit includes zinc-coated steel counterweights and galvanized steel housing for wall recessing and absorption of the counterweight length. Application The AR-200 is a mechanically operated non-return or positive pressure damper which allows air to flow in one direction, preventing air from returning in the opposite direction. The unit can also...

 Open the catalog to page 3
Series AR-200 Non-return or positive pressure dampers-4

Installation The AR-200 is installed in one of the following two ways, depending on how it is to be used: - Air supply: the damper is coupled to the duct with the fins in the same direction as the air flow. - Air suction: the damper is coupled to the duct with the fins toward the fan. The damper is installed in vertical or horizontal position, such that the shaft is parallel to the floor. The unit is fitted with one or two counterweights, depending on damper size. The counterweights can be placed in multiple positions within the 360° of shaft rotation, in order to control the air pressure or...

 Open the catalog to page 4
Series AR-200 Non-return or positive pressure dampers-5

Total pressure - front velocity chart Total pressure (Pa): Pressure drop. Front velocity (m/s): Air velocity calculated from LxH cross-section. Example: AR-200-AL-X-0600-0300 AR-200 non-return damper + untreated bird netting of 600 x 300

 Open the catalog to page 5
Series AR-200 Non-return or positive pressure dampers-6

THIS CATALOGUE IS COPYRIGHTED. Partial or full reproduction of its content is strictly prohibited without express written authorisation from KOOLAIR, S.A. CEN-AR-200-0714-00

 Open the catalog to page 6
Series AR-200 Non-return or positive pressure dampers-7

KOOLAIR, S.A. Calle Urano, 26 Poligono industrial nº 2 – La Fuensanta 28936 Móstoles - Madrid - (España) Tel: +34 91 645 00 33 Fax: +34 91 645 69 62 e-mail: [email protected]

 Open the catalog to page 7

All KOOLAIR S.A catalogs and technical brochures

  1. series FLOOR

    23  Pages

  2. KOOLCOM

    2  Pages

  3. DFRE-P

    1  Page

  4. PE-45

    1  Page

  5. Acoustic

    2  Pages

  6. 36-STE

    2  Pages

  7. S26

    1  Page

  8. 20-SH/21-SH

    1  Page

  9. 20-DH/21-DH

    1  Page

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.