Fire and smoke dampers UL Approval – FSD-FLD

Fire and smoke dampers UL Approval – FSD-FLD
1 / 16 PagesView full catalog

Fire and smoke dampers UL Approval – FSD-FLD

Product catalog summary
Overview: This document provides detailed information on the specifications and operations of UL-approved fire and smoke dampers, specifically the FSD-B-U, FSD-A-U, FLD-S-U, and FLD-S-UD models. These dampers are designed to automatically close under fire conditions to prevent the spread of fire and smoke through HVAC systems.
Specifications: The FSD-B-U and FSD-A-U models are 3V type multi-blade dampers with UL555 and UL555S approval, capable of withstanding fire conditions for 90 minutes. The FSD-B-U model achieves Class 1 leakage at 177°C, while the FSD-A-U achieves Class 3. They are constructed with galvanized steel frames and blades, and feature elastomeric seals for airtightness.
Construction Details: These dampers have reinforced corners and blades with structural sections for added rigidity. They are equipped with a thermal actuator and servomotor, available with 24V or 230V power supply options.
Dimensions: Available in various sizes, the dampers have minimum dimensions of 152 x 203 mm and maximum dimensions of 1828 x 1371 mm.
Operation: The dampers are designed to be fail-safe, closing automatically when power is interrupted or when temperatures exceed 74°C. They can be manually reset if closed due to high temperatures.
Installation: Designed for minimal pressure drop, the dampers have blade widths optimized for airflow. Installation requires consideration of blade protrusion and pressure drop.
Periodic Inspection: Regular inspection and maintenance are essential, following standards such as NFPA 92A, NFPA 80, and NFPA 105. Maintenance tasks include checking servomotors, lubricating parts, and ensuring unobstructed operation.
Technical Data: The document includes detailed tables for selecting dampers based on dimensions, airflow, pressure loss, and sound levels, providing guidance for optimal performance in various conditions.
See more

Catalog excerpts

Fire and smoke dampers UL Approval – FSD-FLD-1

FSD-FLD Fire and smoke dampers UL Approval

 Open the catalog to page 1
Fire and smoke dampers UL Approval – FSD-FLD-2

Series FSD-FLD Description FSD-B-U / FSD-A-U 2 Construction details FSD-B-U / FSD-A-U 3 Dimensions FSD-B-U / FSD-A-U 4 Operation FSD-B-U / FSD-A-U 5 Description FLD-S-U / FLD-S-UD 6 Construction details FLD-S-U / FLD-S-UD 7 Dimensions FLD-S-U / FLD-S-UD 7 Operation FLD-S-U / FLD-S-UD 8 Periodic inspection FLD-S-U / FLD-S-UD 9

 Open the catalog to page 2
Fire and smoke dampers UL Approval – FSD-FLD-3

Series FSD-FLD Description The FSD-B-U and FSD-A-U models are 3V type multi-blade fire and smoke dampers approved according to UL standards (UL555 and UL555S). Fire dampers close automatically to prevent fire and smoke from spreading to adjacent fire compartments through HVAC ventilation ductwork. The dampers are approved to withstand fire conditions for 90 minutes according to UL555 standard. The FSD-B-U model achieves Class 1 leakage level according to UL555S at a temperature of 177 °C. The FSD-A-U model achieves Class 3 leakage level according to UL555S at a temperature of 177 °C. The FSD-B-U...

 Open the catalog to page 3
Fire and smoke dampers UL Approval – FSD-FLD-6

Series FSD-FLD FSD-B-U / FSD-A-U Fire and smoke dampers. UL Approval Operation: The FSD-B-U and FSD-A-U models are designed to be fail-safe, allowing the dampers to automatically return to the desired position in the event of a fire and smoke. The damper operates (closes) if the power supply of 24 V (optionally 230 V) to the servomotor is interrupted, whether as a result of a system failure, a command from the control system or by the thermoelectric fusible link when the temperature exceeds 74º C. The damper is open while power is supplied. The damper automatically resets (opens) when 24 V (optionally...

 Open the catalog to page 6
Fire and smoke dampers UL Approval – FSD-FLD-7

Series FSD-FLD FLD-S-U / FLD-S-UD Fire damper with fusible link V_'_) Description The fire dampers are approved to withstand fire conditions for 90 minutes (1.5 hours) in accordance with UL555. They are 3V type multi-blade operated by the melting of a fusible link calibrated to 74° C. Fire dampers close automatically to prevent fire from spreading to adjacent fire compartments through HVAC ventilation ductwork. The FLD-S-U model is fire rated under static conditions. The FLD-S-U model is fire rated under dynamic conditions. It is designed for system speeds of up to 10 m/s and pressure of up to...

 Open the catalog to page 7
Fire and smoke dampers UL Approval – FSD-FLD-9

Series FSD-FLD Fire dampers with fusible link, FLD-S-U / FLD-S-UD. Approval UL Operation: Complete with thermal fusible link set at 74ºC. They are designed to be fail-safe, allowing the dampers to close automatically when the temperature in the duct reaches the fuse design temperature.. The dampers are designed for the lowest possible pressure drop. The technical department deals with each order individually and supplies the client with a blade width for the desired height and ensures that the dampers have the greatest free area when open and, therefore, the lowest pressure drop. Blade width...

 Open the catalog to page 9
Fire and smoke dampers UL Approval – FSD-FLD-10

Series FSD-FLD Fire dampers with fusible link, FLD-S-U / FLD-S-UD. Approval UL Periodic inspection, testing and maintenance The basic inspection, testing and maintenance procedures are described below. Regular inspection, testing and maintenance are essential to ensure that the fire and smoke dampers in an installation operate as intended. Inspection and maintenance should include periodic testing of all equipment, including dampers, fans, operating devices, controls, etc. Standards such as NFPA 92A, NFPA 80, NFPA105 and local codes must be consulted for guidance with respect to the intervals...

 Open the catalog to page 10
Fire and smoke dampers UL Approval – FSD-FLD-11

Series FSD-FLD Fire damper FSD-B-U / FSD-A-U FLD-S-U / FLD-S-UD. Technical data Selection chart FSD-B-U / FSD-A-U FLD-S-U / FLD-S-UD 1000 kp Selection example: For the given duct dimensions and technical data, we select a 1200 x 200 mm FSD-B-U damper. We use the table on the previous page to find the following data: AL = 0,24 m2 kp = 1,8 kdB(A)= -2 The technical data to achieve a flow rate of 3500 m3/h is required. Referring to the diagram above using this flow rate and the area o 0,24 m2, we obtain a Veff of 4 m/s. With this veocity and taking into account the value of kp, we obtain: Differential...

 Open the catalog to page 11
Fire and smoke dampers UL Approval – FSD-FLD-12

Series FSD-FLD width in mm height in mm free area in m2 effective velocity in relation to the free surface in m/s pressure loss in Pa sound pressure level in dB(A) pressure loss correction factor sound-level correction factor

 Open the catalog to page 12
Fire and smoke dampers UL Approval – FSD-FLD-15

Series FSD-FLD THIS CATALOG IS INTELLECTUAL PROPERTY. The partial or total reproduction of its contents is forbidden without the express and authoritative authorisation of KOOLAIR, S.A. CEN-FSD-FLD-1117-00

 Open the catalog to page 15
Fire and smoke dampers UL Approval – FSD-FLD-16

KOOLAIR, S.A. Calle Urano, 26 Poligono industrial nº 2 – La Fuensanta 28936 Móstoles - Madrid - (España) Tel: +34 91 645 00 33 Fax: +34 91 645 69 62 e-mail: [email protected]

 Open the catalog to page 16

All KOOLAIR S.A catalogs and technical brochures

  1. series FLOOR

    23  Pages

  2. KOOLCOM

    2  Pages

  3. DFRE-P

    1  Page

  4. PE-45

    1  Page

  5. Acoustic

    2  Pages

  6. 36-STE

    2  Pages

  7. S26

    1  Page

  8. 20-SH/21-SH

    1  Page

  9. 20-DH/21-DH

    1  Page

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.