Overview: The document provides technical specifications and compliance details for KOOLAIR's smoke exhaust and fire dampers, which adhere to European regulations and carry CE and NF markings.
Product Standards: The smoke exhaust dampers comply with EN 12101-8 for product standards, EN 1366-10 for testing standards, and EN 13501-4 for classification standards. Fire dampers comply with UNE-EN 15650 for product standards, UNE-EN 1366-2 for testing, and UNE-EN 13501-3 for classification.
Declared Features: The document lists various models with their dimensions, installation locations, and classifications. For example, the SMLD model is suitable for vertical ducts and classified as EI-120 (ved i↔o) S 1500 AA multi (500 Pa).
Design and Sizing: The exhaust paths are designed with a minimum width based on the 'flow-through unit' (PU), with values ranging from 0.9 m to 1.8 m, depending on the number of units.
Installation Details: The document specifies installation locations such as in walls, ceilings, or floor slabs, and construction details like the use of mortar or gypsum plates.
Active Protection Principles: The document highlights the importance of smoke exhaust in active protection, with specific parameters for air flow and velocity.
System KOOLCOM: The document mentions the availability of motor-driven fire damper and smoke exhaust monitoring systems.
See more

Catalog excerpts

FIRE protection-1

The KOOLAIR smoke exhaust dampers comply with European regulations and comply with the CE and NF marking. Product standard (defines the general characteristics of the product) Testing standard (defines the tests to determine that the product performs its function) Classification standard (classifies the product according to its fire resistance) Declared smoke exhaust features Dimensions Mounting location Smoke exhaust duct 1366-8 certified vertical duct Smoke exhaust duct 1366-8 certified vertical duct Smoke exhaust duct 1366-8 certified horizontal duct RPK protection grille for use in smoke exhaust dampers SMLD and CEVH KOOLAIR S.A. Polígono Industrial 2. La Fuensanta 28936 Móstoles (Madrid). España Tel: +34 91 645 00 33 Fax: +34 91 645 69 62 www.koolair.co

 Open the catalog to page 1
FIRE protection-2

Construction details Installation location Flexible wall Gypsum plates Flexible wall Gypsum plates Classification standard (classifies the product according to its fire resistance) Qe = 0,5 m3/s*nUP V ≥ 0,5 m/s With the Door Open Flexible wall Gypsum plates Legend: VEH - horizontal exhaust path EV - vertical exhaust path V Qe - flow-through exhaust air flow (PU) Qi - admission air flow Vi - air inlet velocity nUP - number of flow-through units SYSTEM KOOLCOM Available motor-driven fire damper and smoke exhaust monitoring systems. Testing standard (defines the tests to determine that the product...

 Open the catalog to page 2

All KOOLAIR S.A catalogs and technical brochures

  1. series FLOOR

    23  Pages

  2. KOOLCOM

    2  Pages

  3. DFRE-P

    1  Page

  4. PE-45

    1  Page

  5. Acoustic

    2  Pages

  6. 36-STE

    2  Pages

  7. S26

    1  Page

  8. 20-SH/21-SH

    1  Page

  9. 20-DH/21-DH

    1  Page

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.