Overview: The Kent T4 Power In Ground Unit is designed for areas requiring temporary power, such as trading areas and open-air events. It features a 760mm x 600mm top recessed cover and can accommodate various socket configurations.
Specifications: The Type 4 unit can house up to 4nr 32a 3 phase sockets, with options for smaller configurations including 16A, 32A, or 63A sockets. An additional data panel with RJ45 or XLR audio points can be included. The unit has a 500mm overall depth and is made from grade 316 stainless steel, adhering to FACTA and BS EN124 standards.
Features: Key features include gas rams, up to 4nr IP67 32a 3 phase sockets, a slam lock, and a secondary secure holding down lock. It is suitable for market trading areas and includes a 110mm diameter drain outlet point.
Design Options: The unit can be configured with 1nr 16 Amp 1 Phase plus 3nr 32 Amp 3 Phase sockets, 4nr 32 Amp 1 Phase sockets, or 2nr 63 Amp 3 Phase sockets (for a 650mm deep unit). Additional options include RJ45 datapoints, XLR audio connections, and fiber connections.
Installation Notes: The paviour adjacent to the frame should be bedded using epoxy or polymer modified mortar. A minimum concrete surround of C35/45 is required. The unit includes alternative knockouts for a Ø 125mm cable duct and an IP67 junction box to be resin-filled by an electrical contractor. Connection to a drainage system is necessary.
Load Capacity: The unit is designed to handle a 44-ton truck load, meeting FACTA B and EN124 B125 loading standards.
See more

Catalog excerpts

KENT T4 Power IGU-1

KENT STAINLESS IN GROUND UNITS KENT STAINLESS IN GROUND UNITS KENT T4 Power IGU The Kent Paver in Ground Power Unit, Type 4 unit is an ideal product for trading areas, open air areas with events and exhibitions where temporary power is required. This model, Type 4 has a 760mm x 600mm top recessed cover. The Type 4 was designed to take 4nr 32a 3 phase sockets. The housing can take other combinations smaller than this including 16A, 32A, or 63A Single Phase or Three Phase sockets. An additional data panel with 1 to 4 RJ45 datapoints or XLR audio points can also be added to this unit along with the sockets. The lids can be closed during operation, this necessitates a 500mm overall depth. Features □ Gas Rams □ Up to 4nr IP67 32a 3 Phase sockets □ Slam lock □ Secondary secure holding down lock □ Suitable for market trading areas □ 110mm diameter drain outlet point The hinged recessed cover ensures the units are unobtrusive when not in-use. The In Ground Power Units covers are manufactured in accordance with FACTA and BS EN124 standards. The covers are suitable for 60mm deep paving blocks and are manufactured to meet required loadings. They are fabricated in grade 316 stainless steel as standard. Designed for □ 1nr 16 Amp 1 Phase plus 3nr 32 amp 3 Phase sockets or □ 4nr 32 Amp 1 Phase sockets or □ 2nr 63 Amp 3 Phase sockets (650mm deep unit) Other Options □ RJ45 Datapoints □ XLR Audio Connection □ Fiber Connections This box is used where there are multiple carts with heavy power requirements. Widen the box to add a strip of Data. Deepen the Box to use > 1nr 63 Amp 3 Phase Power. Product Code PAVIOUR DIRECTLY ADJACENT TO FRAME TO BE BEDDED USING AN EPOXY MORTAR OR POLYMER MODIFIED MORTAR ALTERNATIVE KNOCKOUTS FOR 0 125mm CABLE DUCT N.B. ENSURE CONNECTION TO DRAINAGE SYSTEM Specify Kent IGU- Type 4 Unit; 760mm x 600mm top; with a 500mm depth (Closed Use); Grade 316 Stainless Steel; EP031- 3nr 32 amp 3 phase plus 1nr 16 amp 1 phase Sockets