Catalog excerpts

20/KVV/xxxx/0306/EN KVD - Steam Extraction Canopy with Supply Air KVD Steam Extraction Canopy with Supply Air The KVD steam extract canopy has been especially adapted to capture, condense and remove steam produced by industrial dishwashers, cooking pots or where grease filtration is not the main requirement. • Condensation is achieved by the use of angled internal baffles and deflectors • Efficient exhaust is maintained by using lateral side slots combined with the large internal volume • Draft free air distribution directly into the working zone from the front face, low velocity supply diffuser • Modular construction, simplifies design and installation • Adjustment and measurement of airflow using the MSM and T.A.B. measuring tap in combination with damper plate within the spigot. • Manufactured from polished stainless steel AISI 304 • Surface mounted light fittings are available as an accessory QUICK DATA Recommended Exhaust air volumes Recommended Supply air volumes L l/s m3/h H=555 mm H= 400 mm 100...200 l/s / meter length or 360...720 m3/h / meter length LpA < 50 dB(A) 80...150 l/s / meter length or 288...540 m3/h / meter length LpA < 50 dB(A) 1000 305 11 00 1500 445 1600 2000 610 2200 2500 805 2900
Open the catalog to page 1
20/KVV/xxxx/0306/EN KVD - Steam Extraction Canopy with Supply Air Construction The outer casing is in easy to clean stainless steel AISI 304. The plenum roof, connection spigots and control damper are manufactured from galvanized steel, but can be supplied from stainless steel (AISI 304) as an optional extra (excepted MSM). All lower joints of the canopy are fully welded and polished which ensures water tightness. KVD is equipped with a draining tap (3) for removal of any collected condensate. The interior baffles (5) are removable to allow access and cleaning of the inside exhaust plenum....
Open the catalog to page 2
20/KVV/xxxx/0306/EN KVD - Steam Extraction Canopy with Supply Air 10 10 10 10 Pressure drop and sound data, exhaust H = 555/400 Äpm1 = Pressure loss of filters measured from MSM, minimum exhaust pressure loss when the damper plate is open Äpm2 = Maximum exhaust pressure loss when the damper plate is nearly closed. TP = Damper plate KVD-1500 KVD-2000 KVD-2500 KVD-1000
Open the catalog to page 4
KVD - Steam Extraction Canopy with Supply Air 20/KVV/xxxx/0306/EN Pressure drop, supply H = 555/400 Äpm1 = Measure of pressure difference, PA Äpm2 = Maximum supply pressure loss when the damper plate is nearly closed. MSM = Measurement and adjustment device The supply air is controlled by adjusting (1) the damper (2) in the supply spigot and the air flow is measured using the measurement tap (3). Qv = 43,8 x DPm
Open the catalog to page 5
20/KVV/xxxx/0306/EN KVD - Steam Extraction Canopy with Supply Air Suggested specifications General Kitchen canopies are constructed from stainless steel to material specification AISI 304. The kitchen canopies shall be supplied complete with outer casing/main body, pressure measurement taps, extract air spigot connections with damper plates MSM, adjustable baffle plates, condensate channel, drain tap or collection tray and hanging brackets. Outer casing/Main body Outer casing panels shall be constructed of stainless steel to AISI 304 in brushed satin finish. Each joint shall be spot-welded,...
Open the catalog to page 6All HALTON catalogs and technical brochures
-
Halton USS
8 Pages
-
Halton Vita Cell Room (VCR)
2 Pages
-
Halton Rex Expander (RXP)
16 Pages
-
Halton CBD
8 Pages
-
FS Halton AHUs
28 Pages
-
Halton KCD
3 Pages
-
KVE-CM
7 Pages
-
KMC - MobiChef
5 Pages
-
Halton MobiChef
12 Pages
-
R6B
9 Pages
-
Halton Vario
20 Pages
-
Halton FDS
7 Pages
-
Halton FDR
6 Pages
-
Halton FDI
6 Pages
-
Halton FDE
8 Pages
-
Halton FDC
5 Pages
-
ALE/ALU
8 Pages
-
AHF
5 Pages
-
JTH
4 Pages
-
FDC
5 Pages
-
AFB
7 Pages
-
TCG 2013
4 Pages
-
FCU 2013
6 Pages
-
HFB - Airflow Management Damper
17 Pages
-
VHB - Active VAV Diffuser
7 Pages
-
TLD - Wall Diffuser Unit
9 Pages
-
FDB2 -
4 Pages
-
CPA - Passive Chilled Beam
13 Pages
Archived catalogs
-
FCU Vertical Fancoil Unit
4 Pages
-
Halton ? AdaptableClimate
12 Pages
-
Halton ? Ventilation fire safety
12 Pages
-
Halton ? Chilled Beams
12 Pages
-
HALTON-POLLUSTOP
4 Pages
-
UNIPOINT
4 Pages
-
HALTON-KCE
10 Pages
-
HALTON-KSK
6 Pages
-
KCJ
12 Pages
-
Halton - universal grilles
46 Pages
-
Halton - beam design guide
31 Pages