Halton FDS

Halton FDS

Halton FDS

Product catalog summary
Specifications:
The Halton FDS is a multi-blade-type fire damper designed for both rectangular and circular ducts. It complies with EN 1366-2 and EN 13501-3 standards, achieving a fire resistance class of ES 60. It can be upgraded to EIS 60 with additional duct insulation. The damper is suitable for installation in concrete, masonry, and lightweight plasterboard walls, with both vertical and horizontal blade directions possible. It is manufactured under ISO 9001 quality standards and is suitable for ducts ranging from 200 mm x 200 mm to 1500 mm x 800 mm. The casing tightness meets EN 1751, Class C, and it can handle a maximum pressure of 3300 Pa and air speed of 15 m/s.
Product Models and Accessories:
The FDS offers various automatic release and position indication options, with models available with either electrical or pneumatic actuators. Accessories include modular casing extensions, circular connections, and several actuator options such as Belimo BF 24-T-2 HL and BF 230-T-2 HL.
Materials:
The casing and blades are made of galvanized steel, with ceramic cloth blade gaskets and rubber compound duct gaskets.
Installation:
The damper can be installed in both concrete/masonry and lightweight walls. Installation requires an opening size of product dimensions plus 60 mm in both directions. The gap between the damper and the wall is filled with noncombustible wool. Detailed installation instructions are provided with each product.
Function:
The FDS prevents fire and smoke spread in ventilation ducts. It features a thermal release operation with a nominal fuse release temperature of 72 °C. The damper can be connected to the MSH control and testing system for integration with building automation systems.
Servicing:
Regular inspections are recommended, with a minimum inspection period of one year. An inspection opening should be installed near the damper as per building codes.
Suggested Specifications:
The fire damper should be made of galvanized steel, approved for both concrete/masonry and lightweight walls, and include a position indicator and thermal fuse. Release options include electric, pneumatic, and solenoid releases.
Product Code:
The product code format is FDS/S-W-H-D, where S indicates duct connection type, W is width, H is height, and D is connection size. Accessories and release types are specified with additional codes.
See more

Catalog excerpts

Halton FDS-1

Multi-blade-type Fire Damper for Rectangular and Circular Ducts • Type-approved unit compliant with the EN 1366-2 and EN 13501-3 standards. • Fire resistance class ES 60. • Possibility of use as an EIS 60 damper with additional duct insulation (as indicated in national building code). • Installation in separating concrete or masonry walls and ceilings and for lightweight plasterboard walls. • Possibility of wall installation in both vertical and horizontal blade direction. • External quality control management by VTT, the Technical Research Centre of Finland. • Manufacture in accordance with the ISO 9001 quality standard. • Suitability for rectangular ducts from size 200 mm x 200 mm to 1500 mm x 800 mm. • Fire damper casing tightness compliant with EN 1751, Class C. • Suitability for use in ducts with a maximum pressure of 3300 Pa and maximum air speed of 15 m/s. Product models and Accessories • Several automatic release and position indication options • Models equipped with either electrical or pneumatic actuators • Modular damper casing extension for different wall thicknesses • Option of circular connection FDS - Multi-blade-type Fire Damper for Rectangular and Circular Ducts

 Open the catalog to page 1
Halton FDS-2

V Vertical blade direction only H Horizontal blade direction only X Both horizontal and vertical blade direction allowed FDS - Multi-blade-type Fire Damper for Rectangular and Circular Ducts

 Open the catalog to page 2
Halton FDS-3

ACCESSORIES AND PRODUCT MODELS Actuators Pneumatic, AT100 (rotating actuator), P0 Belimo BF 24-T-2 HL, operating voltage AC/DC 24 V (fuse: 72 °C, includes limit switch), B1 Belimo BF 230-T-2 HL, operating voltage AC 230 V (fuse: 72 °C, includes limit switch), B2 ACCESSORIES The fire damper can be equipped with a bipolar limit switch, which indicates the closing of the shut-off blade. The limit switch has potential-free contacts (no=normally open and nc=normally closed), which can be used to control other fire dampers equipped with an electric release (e.g., triggering an alarm in the fire suppression...

 Open the catalog to page 3
Halton FDS-4

FDS - Multi-blade-type Fire Damper for Rectangular and Circular Ducts Function The FDS is a rectangular fire damper, which prevents fire and smoke from spreading in ventilation ducts. Approved fire resistance classes are (EN 1366-2): ■ Ceilings: ES 60 ■ Walls: ES60, E90 (both concrete/masonry and lightweight walls) The fire damper is equipped with either an electrical or pneumatic actuator. Under all options, a fuse responds to a rise in temperature, causing a spring-return blade to close. Alternatively, the damper may be released by a system using an electric motor or using solenoids with a...

 Open the catalog to page 4
Halton FDS-5

Electric actuator wiring diagram A Connect via safety isolating transformer! 230 VAC **) PNEU. INLET (5-10 BAR) FOR A PLASTIC TUBE 0 6 MM 1 SPRING-RETURN ACTUATOR 2 QUICK EXHAUST VALVE 4 FUSIBLE LINK VALVE 5 OPTION: SOLENOID VALVE 9 OPTION: OPEN/CLOSED SWITCHES 10 OPTION: MANUAL VALVE NOTE: ADDITIONAL SOLENOID VALVE MAX. 10 METRES FROM FIRE DAMPER - Multi-blade-type Fire Damper for Rectangular and Circular Ducts Malton 5

 Open the catalog to page 5
Halton FDS-6

Servicing To ensure proper operation of the fire dampers, they should be inspected regularly. It is recommended that the fire damper be connected to automatic control and testing system MSH (24-V system). Dampers not connected to an automatic testing system shall be tested periodically. The minimum recommended inspection period is one year or according to building code. An inspection opening shall be installed in the proximity of the fire damper as indicated in the building code (not part of the product). Upon failure during testing of the fire damper, maintenance service shall be ordered from...

 Open the catalog to page 6
Halton FDS-7

Product code FDS/S-W-H-D S = Type of duct connections R Rectangular connections W = Width S=R: 200, +50, ..., 1500 H = Height S=R: 200, 300, +50, ..., 800 D = Connection size S=C: 630, 800 Specifics and accessories RE = Release type B1 BF-24-T-2 HL, fuse: 72 °C AC = Accessories CE Casing extension, 210 mm, for structural thickness > 200 mm L2 Limit switches, 2 pcs, Bernstein, with pneumatic motor M1 Solenoid valve, 24 VAC, with pneumatic motor M2 Solenoid valve, 230 VAC, with pneumatic motor N1 Safety mesh, 1 side, installed in actuator side N2 Safety mesh, 2 sides FDS - Multi-blade-type...

 Open the catalog to page 7