Product catalog summary
Specifications:
The Halton FDI Fire Damper is CE marked according to EN15650:2010 and tested per EN 1366-2. It offers fire resistance class EI 60 (ve,ho,i<->o) S, and E 90 (ho,i<->o) S in concrete ceilings. It is suitable for installation in brick, concrete, or lightweight plasterboard walls and concrete slabs, with the blade shaft in horizontal or vertical orientation. Manufactured under ISO 9001 quality standards, it is externally quality controlled by VTT, Finland. The damper is designed for circular ducts ranging from 100 to 630 mm, with shutoff damper tightness classified as EN 1751 class 4 and casing leakage as class C. It can withstand a maximum pressure of 3300 Pa and is tested for closure at 15 m/s duct velocity.
Product Models and Accessories:
The FDI offers various automatic release and position indication options, with models available with manual or electric actuators. Manual systems have fuse activation temperatures of 50, 72, 100, and 120 °C. Safety mesh options are available.
Materials:
The casing and blade are made of galvanized steel, with a heat-insulating panel structure for the blade. The blade gasket is silicone, the expanding seal is graphite mass, and the closing springs are stainless steel. Duct gaskets are made from a 1C-polyurethane hybrid.
Dimensions:
The document provides detailed dimensions for various duct sizes, ranging from 100 to 630 mm in diameter.
Functionality:
The FDI fire damper prevents fire and smoke spread in ventilation systems. It is approved for horizontal and vertical installations, meeting fire resistance class EI 60 and E 90 requirements. The damper can be equipped with manual or electric actuators, with a thermal fuse and visual position indicator. The fuse activates at 72 °C for electric actuators, with optional temperatures for manual actuators.
Installation:
The damper is installed in concrete or masonry walls and ceilings, with an installation hole diameter of D + 20 mm. It includes an installation/casting frame and requires gypsum-based firestop mastic for sealing. Detailed installation instructions and a certificate form are provided.
Servicing:
Regular inspections are recommended, with a minimum period of one year. The damper can be reset after the fuse temperature falls below the release temperature. Maintenance should be performed by authorized representatives if issues arise.
Suggested Specifications:
The fire damper should conform to EN 1366-2 and EN 135013 standards, with a double-sealing solution for fire-gas tightness. It should include a position indicator and offer various release options, including electric, electromagnetic, and pneumatic. The casing should meet EN 1751 class C tightness requirements.
Product Code:
The product code includes connection size, release type, fuse release temperature, and accessories. Example: FDI-160, RE=MA, FU=72.
See more

Catalog excerpts

Halton FDI-1

• CE marked according to the product standard Product models and Accessories • Various automatic release and position indication options. • Models equipped with either manual or electric actuators. • In the manually operated system, fuse activation temperature options of 50, 72, 100 and 120 °C. • Safety mesh options EN15650:2010 and tested according to the fire test standard EN 1366-2. • Fire resistance class EI 60 (ve,ho,i<->o) S, and in concrete ceilings also E 90 (ho,i<->o) S • Approved for installation in separating brick, concrete, or lightweight plasterboard walls and concrete slabs. • Installation on the wall with the blade shaft in either horizontal or vertical orientation. • Manufacture in accordance with the ISO 9001 quality system. • External quality control management by the Technical Research Centre of Finland, VTT • Installation in circular ventilation ducts of 100...630 mm. • Classification of shutoff damper tightness EN 1751 class 4. • Classification of casing leakage EN 1751 class C. • Suitability for use in ducts with a maximum pressure of 3300 Pa. • Damper closing tests performed at 15 m/s duct velocity. FDI - Fire Damper for Circular Ducts

 Open the catalog to page 1
Halton FDI-2

The size of the installation hole is 0D + 20 mm. Detailed installation instructions, as well as an installer's installation certificate form, are supplied with each product. WEIGHT (kg) ACCESSORIES AND PRODUCT MODELS The manual fire damper can be equipped with a bipolar limitswitch, MS, which indicates the closing of the shutoff blade. The limitswitch has potential-free points (no = normally open and nc = normally closed), which can be used to control other fire dampers equipped with an electric release, e.g., triggering an alarm in the fire suppression system. The maximum operating voltage and...

 Open the catalog to page 2
Halton FDI-3

Solenoid operation The manual fire damper can be released using solenoid, by switching on the solenoid operating voltage. The release can be initiated by e.g. a smoke detector, limitswitch, pressure switch or similar, which connects the power supply via e.g. an auxiliary relay. (design value) Enclosure class (minimum) IP20 IP20 Operating Time Ratio ED 100% 100% Electromagnetic operation The fire damper stays open when the electrical circuit is closed. The fire damper is shut by opening the circuit. Note: Interruption of the power supply closes the damper. Uninterrupted power supply...

 Open the catalog to page 3
Halton FDI-4

Electric actuator wiring diagram The fire damper is installed on concrete or masonry walls and ceilings and on lightweight walls. An opening is always left in the separating element for the casing of the product to be led through the structure. The maximum diameter of the installation hole is the fire damper diameter D + 20 mm. To make installation easier, all products come with an installation/casting frame, which is used to fasten the fire damper to the wall surface or the steel frame of the plasterboard wall. The installation is finished by filling the casting frame from the front of the device...

 Open the catalog to page 4
Halton FDI-5

Servicing A manual fire damper can be reset after the fuse temperature has fallen below the release temperature. If the shutoff blade does not lock, the fuse is worn out and must be replaced. The fuse can be changed from outside the fire damper. The fuse of a fire damper equipped with an electric actuator must be replaced if the fuse has been released because of a rise in temperature. To ensure proper operation of fire dampers, they should be inspected regularly. The minimum recommended inspection period is one year or according to the building code It is recommended that the fire damper is connected...

 Open the catalog to page 5
Halton FDI-6

Product code FDI-D D = connection size 100, 125, 160, 200, 250, 315, 400, 500, 630 Specifics and accessories RE = release type MA Manual FU = fuse release temperature (°C) 72 72 °C AC = accessories N1 Safety mesh, 1 side, installed in actuator side N2 Safety mesh, 2 sides Code example FDI - Fire Damper for Circular Ducts 6

 Open the catalog to page 6