Catalog excerpts

Halton FDI - 1

• CE marked according to the product standard Product models and Accessories • Various automatic release and position indication options. • Models equipped with either manual or electric actuators. • In the manually operated system, fuse activation temperature options of 50, 72, 100 and 120 °C. • Safety mesh options EN15650:2010 and tested according to the fire test standard EN 1366-2. • Fire resistance class EI 60 (ve,ho,i<->o) S, and in concrete ceilings also E 90 (ho,i<->o) S • Approved for installation in separating brick, concrete, or lightweight plasterboard walls and concrete slabs. • Installation on the wall with the blade shaft in either horizontal or vertical orientation. • Manufacture in accordance with the ISO 9001 quality system. • External quality control management by the Technical Research Centre of Finland, VTT • Installation in circular ventilation ducts of 100...630 mm. • Classification of shutoff damper tightness EN 1751 class 4. • Classification of casing leakage EN 1751 class C. • Suitability for use in ducts with a maximum pressure of 3300 Pa. • Damper closing tests performed at 15 m/s duct velocity. FDI - Fire Damper for Circular Ducts

Open the catalog to page 1
Halton FDI - 2

The size of the installation hole is 0D + 20 mm. Detailed installation instructions, as well as an installer's installation certificate form, are supplied with each product. WEIGHT (kg) ACCESSORIES AND PRODUCT MODELS The manual fire damper can be equipped with a bipolar limitswitch, MS, which indicates the closing of the shutoff blade. The limitswitch has potential-free points (no = normally open and nc = normally closed), which can be used to control other fire dampers equipped with an electric release, e.g., triggering an alarm in the fire suppression system. The maximum operating voltage...

Open the catalog to page 2
Halton FDI - 3

Solenoid operation The manual fire damper can be released using solenoid, by switching on the solenoid operating voltage. The release can be initiated by e.g. a smoke detector, limitswitch, pressure switch or similar, which connects the power supply via e.g. an auxiliary relay. (design value) Enclosure class (minimum) IP20 IP20 Operating Time Ratio ED 100% 100% Electromagnetic operation The fire damper stays open when the electrical circuit is closed. The fire damper is shut by opening the circuit. Note: Interruption of the power supply closes the damper. Uninterrupted power...

Open the catalog to page 3
Halton FDI - 4

Electric actuator wiring diagram The fire damper is installed on concrete or masonry walls and ceilings and on lightweight walls. An opening is always left in the separating element for the casing of the product to be led through the structure. The maximum diameter of the installation hole is the fire damper diameter D + 20 mm. To make installation easier, all products come with an installation/casting frame, which is used to fasten the fire damper to the wall surface or the steel frame of the plasterboard wall. The installation is finished by filling the casting frame from the front of the...

Open the catalog to page 4
Halton FDI - 5

Servicing A manual fire damper can be reset after the fuse temperature has fallen below the release temperature. If the shutoff blade does not lock, the fuse is worn out and must be replaced. The fuse can be changed from outside the fire damper. The fuse of a fire damper equipped with an electric actuator must be replaced if the fuse has been released because of a rise in temperature. To ensure proper operation of fire dampers, they should be inspected regularly. The minimum recommended inspection period is one year or according to the building code It is recommended that the fire damper is...

Open the catalog to page 5
Halton FDI - 6

Product code FDI-D D = connection size 100, 125, 160, 200, 250, 315, 400, 500, 630 Specifics and accessories RE = release type MA Manual FU = fuse release temperature (°C) 72 72 °C AC = accessories N1 Safety mesh, 1 side, installed in actuator side N2 Safety mesh, 2 sides Code example FDI - Fire Damper for Circular Ducts 6

Open the catalog to page 6

All HALTON catalogs and technical brochures

  1. Halton CBD

    8 Pages

  2. FS Halton AHUs

    28 Pages

  3. Halton KCD

    3 Pages

  4. KVE-CM

    7 Pages

  5. R6B

    9 Pages

  6. Halton Vario

    20 Pages

  7. Halton FDS

    7 Pages

  8. Halton FDR

    6 Pages

  9. Halton FDE

    8 Pages

  10. Halton FDC

    5 Pages

  11. ALE/ALU

    8 Pages

  12. AHF

    5 Pages

  13. JTH

    4 Pages

  14. FDC

    5 Pages

  15. AFB

    7 Pages

  16. TCG 2013

    4 Pages

  17. FCU 2013

    6 Pages

  18. FDB2 -

    4 Pages

Archived catalogs

  1. UNIPOINT

    4 Pages

  2. HALTON-KVD

    6 Pages

  3. HALTON-KCE

    10 Pages

  4. HALTON-KSK

    6 Pages

  5. KCJ

    12 Pages